Wash. Admin. Code § 296-104-301 - Installation-What control and limit devices are required on automatically fired power boilers after June 1989?
In addition to those requirements listed in WAC 296-104-300, the following are also required:
(1)
All steam power boilers shall be equipped with:
(a) Two high steam pressure limit controls,
the highest of which shall be provided with a manual reset.
(b) Two low-water fuel cutoffs, one of which
shall be provided with a manual reset device and independent of the feed water
controller.
(2) Coil type
flash steam boilers may use two high-temperature limit controls, one of which
shall have a manual reset. This is instead of the low-water fuel
cutoff.
(3) All high temperature
water (greater than 250°F) power boilers shall be equipped with:
(a) Two high-temperature limit controls, the
highest of which shall be provided with a manual reset.
(b) Two low-water fuel cutoffs, one of which
shall be provided with a manual reset device and independent of the feed water
controller.
(4) All
controls and limit devices shall be tested or verified by means acceptable by
the jurisdiction.
(5) For
installations after December 2004 - All automatically fired power boilers with
input greater than 400,000 Btu/hr, including electric boilers with input
greater than 117 kW, shall have a manually operated remote shutdown switch or
circuit breaker. When an existing remote shutdown switch exists, all boilers
may be connected to the existing switch to allow for remote shutdown of all
boilers in the room. When an additional boiler is added to the room where an
existing remote shutdown switch does not exist, all boilers meeting the input
requirements should be added to the new remote shutdown switch. Activation of
the emergency shutdown switch or circuit breaker shall immediately shut off the
fuel or energy supply and initiate the boiler shutdown sequence in accordance
with manufacturer's recommendations where applicable. The shutdown switch
should be located just outside the boiler room door and marked for easy
identification. Consideration should be given to the type and location of the
switch to safeguard against tampering. If the boiler room door is on the
building exterior, the switch should be located just inside the door. If there
is more than one door to the boiler room, there should be a switch located at
each door.
Notes
Statutory Authority: Chapter 70.79 RCW. 04-21-069, § 296-104-301, filed 10/19/04, effective 1/1/05.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.