Wash. Admin. Code § 296-24-33015 - Service stations
(1)
Storage
and handling.
(a)
General
provisions.
(i) You must store liquids
in approved closed containers not exceeding 60 gallons capacity, in tanks
located underground, in tanks in special enclosures as described in (b) of this
subsection, or in aboveground tanks as provided for in subsection (3)(b)(i),
(ii), (iii), and (iv) of this section.
(ii) Aboveground tanks, located in an
adjoining bulk plant, may be connected by piping to service station underground
tanks if, in addition to valves at aboveground tanks, a valve is also installed
within control of service station personnel.
(iii) Apparatus dispensing Category 1 or 2
flammable liquids, or Category 3 flammable liquids with a flashpoint below
100°F (37.8°C), into the fuel tanks of motor vehicles of the public
must not be located at a bulk plant unless separated by a fence or similar
barrier from the area in which bulk operations are conducted.
(iv) The provisions of subsection (1) of this
section must not prohibit the dispensing of flammable liquids with a flashpoint
below 100°F (37.8°C) in the open from a tank vehicle to a motor
vehicle. You must permit such dispensing provided:
(A) The tank vehicle complies with the
requirements covered in the Standard on Tank Vehicles for Flammable Liquids,
NFPA 385-1966.
(B) The dispensing
is done on premises not open to the public.
(C) The dispensing hose does not exceed 50
feet in length.
(D) The dispensing
nozzle is a listed automatic-closing type without a latch-open
device.
(v) You must not
store or handle Category 1 or 2 flammable liquids, or Category 3 flammable
liquids with a flashpoint below 100°F (37.8°C), within a building
having a basement or pit into which flammable vapors may travel, unless such
area is provided with ventilation designed to prevent the accumulation of
flammable vapors therein.
(vi) You
must maintain and reconcile accurate inventory records on all Class I liquid
storage tanks for possible indication of leakage from tanks or
piping.
(b)
Special enclosures.
(i) When
installation of tanks in accordance with WAC
296-24-33005(3)
is impractical because of property or building limitations, tanks for flammable
liquids may be installed in buildings if properly enclosed.
(ii) The enclosure must be substantially
liquid and vaportight without backfill. Sides, top, and bottom of the enclosure
must be of reinforced concrete at least six inches thick, with openings for
inspection through the top only. Tank connections must be so piped or closed
that neither vapors nor liquid can escape into the enclosed space. You must
provide means whereby portable equipment may be employed to discharge to the
outside any liquid or vapors which might accumulate should leakage
occur.
(iii) At automotive service
stations provided in connection with tenant or customer parking facilities at
or below grade level in large buildings of commercial, mercantile, or
residential occupancy, tanks containing Class I liquids, installed of necessity
in accordance with (b)(ii) of this subsection, must not exceed 6,000 gallons
individual or 18,000 gallons aggregate capacity.
(c)
Inside buildings.
(i) Except where stored in tanks as provided
in (b) of this subsection, you must not store any Category 1 or 2 flammable
liquids, or Category 3 flammable liquids with a flashpoint below 100°F
(37.8°C), within any service station building except in closed containers
of aggregate capacity not exceeding 60 gallons. One container not exceeding 60
gallons capacity equipped with an approved pump is permitted.
(ii) Category 1 or 2 flammable liquids, or
Category 3 flammable liquids with a flashpoint below 100°F (37.8°C),
may be transferred from one container to another in lubrication or service
rooms of a service station building provided the electrical installation
complies with Table H-19 and provided that any heating equipment complies with
subsection (5) of this section.
(iii) Category 3 flammable liquids with a
flashpoint at or above 100°F (37.8°C) and Category 4 flammable liquids
may be stored and dispensed inside service station buildings from tanks of not
more than 120 gallons capacity each.
(d)
Labeling. You must not make
any sale or purchase of any Class I, II, or III liquids in containers unless
such containers are clearly marked with the name of the product contained
therein.
(e)
Dispensing into
portable containers. You must not make any delivery of any Category 1 or
2 flammable liquids, or Category 3 flammable liquids with a flashpoint below
100°F (37.8°C), into portable containers unless the container is
constructed of metal, has a tight closure with screwed or spring cover, and is
fitted with a spout or so designed that the contents can be poured without
spilling.
(2)
Dispensing systems.
(a)
Location. Dispensing devices at automotive service stations must
be so located that all parts of the vehicle being served will be on the
premises of the service station.
(b)
Inside location. Approved
dispensing units may be located inside of buildings. You must separate the
dispensing area from other areas in an approved manner. You must mount the
dispensing unit and its piping either on a concrete island or protected against
collision damage by suitable means and located in a position where it cannot be
struck by a vehicle descending a ramp or other slope out of control. You must
provide the dispensing area with an approved mechanical or gravity ventilation
system. When dispensing units are located below grade, you must use only
approved mechanical ventilation and you must protect the entire dispensing area
by an approved automatic sprinkler system. Ventilating systems must be
electrically interlocked with gasoline dispensing units so that the dispensing
units cannot be operated unless the ventilating fan motors are
energized.
(c)
Emergency
power cutoff. You must provide a clearly identified and easily
accessible switch(es) or a circuit breaker(s) at a location remote from
dispensing devices, including remote pumping systems, to shut off the power to
all dispensing devices in the event of an emergency.
(d)
Dispensing units.
(i) You must transfer Category 1 or 2
flammable liquids, or Category 3 flammable liquids with a flashpoint below
100°F (37.8°C), from tanks by means of fixed pumps so designed and
equipped as to allow control of the flow and to prevent leakage or accidental
discharge.
(ii) Only listed devices
may be used for dispensing Category 1 or 2 flammable liquids, or Category 3
flammable liquids with a flashpoint below 100°F (37.8°C). No such
device may be used if it shows evidence of having been dismantled.
(iii) Every dispensing device for Category 1
or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below
100°F (37.8°C), installed after December 31, 1978, must contain
evidence of listing so placed that any attempt to dismantle the device will
result in damage to such evidence, visible without disassembly or dismounting
of the nozzle.
(iv) You must not
dispense Category 1 or 2 flammable liquids, or Category 3 flammable liquids
with a flashpoint below 100°F (37.8°C), by pressure from drums,
barrels, and similar containers. You must use approved pumps taking suction
through the top of the container or approved self-closing faucets.
(v) You must mount the dispensing units,
except those attached to containers, either on a concrete island or protect
them against collision damage by suitable means.
(e)
Remote pumping systems.
(i) This subdivision must apply to systems
for dispensing Category 1 or 2 flammable liquids, or Category 3 flammable
liquids with a flashpoint below 100°F (37.8°C), where such liquids are
transferred from storage to individual or multiple dispensing units by pumps
located elsewhere than at the dispensing units.
(ii) Pumps must be designed or equipped so
that no part of the system will be subjected to pressures above its allowable
working pressure. Pumps installed above grade, outside of buildings, must be
located not less than ten feet from lines of adjoining property which is/or may
be built upon, and not less than five feet from any building opening. When an
outside pump location is impractical, pumps may be installed inside of
buildings, as provided for dispensers in (b) of this subsection, or in pits as
provided in (e)(iii) of this subsection. You must substantially anchor pumps
and protect them against physical damage by vehicles.
(iii) Pits for subsurface pumps or piping
manifolds of submersible pumps must withstand the external forces to which they
may be subjected without damage to the pump, tank, or piping. The pit must be
no larger than necessary for inspection and maintenance and must be provided
with a fitted cover.
(iv) You must
provide a control that will permit the pump to operate only when a dispensing
nozzle is removed from its bracket on the dispensing unit and the switch on
this dispensing unit is manually actuated. This control must also stop the pump
when all nozzles have been returned to their brackets.
(v) You must properly install an approved
impact valve, incorporating a fusible link, designed to close automatically in
the event of severe impact or fire exposure in the dispensing supply line at
the base of each individual dispensing device.
(vi)
Testing. After the
completion of the installation, including any paving, you must test that
section of the pressure piping system between the pump discharge and the
connection for the dispensing facility for at least 30 minutes at the maximum
operating pressure of the system. You must repeat such tests at 5-year
intervals thereafter.
(f)
Delivery nozzles.
(i) You must provide a listed manual or
automatic-closing type hose nozzle valve on dispensers used for the dispensing
of Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a
flashpoint below 100°F (37.8°C).
(ii) You must hold manual-closing type valves
open manually during dispensing. Automatic-closing type valves may be used in
conjunction with an approved latch-open device.
(g)
Special type dispensers.
(i) You must install emergency controls at an
acceptable location, but controls must not be more than one hundred feet from
dispensers.
(ii) You must
conspicuously post instructions for the operation of dispensers.
(3)
Marine
service stations.
(a)
Dispensing.
(i) The dispensing
area must be located away from other structures so as to provide room for safe
ingress and egress of craft to be fueled. Dispensing units must in all cases be
at least 20 feet from any activity involving fixed sources of
ignition.
(ii) Dispensing must be
by approved dispensing units with or without integral pumps and may be located
on open piers, wharves, or floating docks or on shore or on piers of the solid
fill type.
(iii) Dispensing nozzles
must be automatic-closing without a hold-open latch.
(b)
Tanks and pumps.
(i) Tanks, and pumps not integral with the
dispensing unit, must be on shore or on a pier of the solid fill type, except
as provided below.
(ii) Where shore
location would require excessively long supply lines to dispensers, tanks may
be installed on a pier provided that applicable portions of WAC
296-24-33005 relative to spacing,
diking, and piping are complied with and the quantity so stored does not exceed
1,100 gallons aggregate capacity.
(iii) Shore tanks supplying marine service
stations may be located above ground, where rock ledges or high water table
make underground tanks impractical.
(iv) Where tanks are at an elevation which
would produce gravity head on the dispensing unit, the tank outlet must be
equipped with a pressure control valve positioned adjacent to and outside the
tank block valve specified in WAC
296-24-33005(2)(h)(ii),
so adjusted that liquid can not flow by gravity from the tank in case of piping
or hose failure.
(c)
Piping.
(i) Piping between shore
tanks and dispensing units must be as described in WAC
296-24-33007, except that, where
dispensing is from a floating structure, suitable lengths of oil-resistant
flexible hose may be employed between the shore piping and the piping on the
floating structure as made necessary by change in water level or
shoreline.
(ii) You must provide a
readily accessible valve to shut off the supply from shore in each pipeline at
or near the approach to the pier and at the shore end of each pipeline adjacent
to the point where flexible hose is attached.
(iii) Piping must be located so as to be
protected from physical damage.
(iv) You must ground piping handling Category
1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint
below 100°F (37.8°C) shall be grounded to control stray
currents.
(4)
Electrical equipment.
(a)
Application. This subsection applies to areas where Category 1 or
2 flammable liquids, or Category 3 flammable liquids with a flashpoint below
100°F (37.8°C), are stored or handled. For areas where Category 3
flammable liquids with a flashpoint at or above 100°F (37.8°C) or
Category 4 flammable liquids are stored or handled the electrical equipment may
be installed according to the provisions of chapter 296-24 WAC Part L for
ordinary locations.
(b) All
electrical equipment and wiring must be of a type specified by and must be
installed according to chapter 296-24 WAC Part L.
(c) So far as it applies, Table H-19 must be
used to delineate and classify hazardous areas for the purpose of installation
of electrical equipment under normal circumstances. A classified area must not
extend beyond an unpierced wall, roof, or other solid partition.
(d) The area classifications listed must be
based on the assumption that the installation meets the applicable requirements
of this section in all respects.
TABLE H-19
ELECTRICAL EQUIPMENT HAZARDOUS AREAS-SERVICE STATIONS
| Location | Class I, Group D division | Extent of classified area |
| Underground tank: Fill opening_________ | 1 | Any pit, box or space below grade level, any part of which is within the Division 1 or 2 classified area. |
| 2 | Up to 18 inches above grade level within a horizontal radius of 10 feet from a loose fill connection and within a horizontal radius of 5 feet from a tight fill connection. | |
| Vent -Discharging upward_________ | ||
| 1 | Within 3 feet of open end of vent, extending in all directions. | |
| 2 | Area between 3 feet and 5 feet of open end of vent, extending in all directions. | |
| Dispenser: Pits_________ | 1 | Any pit, box or space below grade level, any part of which is within the Division 1 or 2 classified area. |
| Dispenser enclosure_________ | 1 | The area 4 feet vertically above base within the enclosure and 18 inches horizontally in all directions. |
| Outdoor _________ | 2 | Up to 18 inches above grade level within 20 feet horizontally of any edge of enclosure. |
| Indoor: | ||
| With mechanical | ||
| ventilation_________ | ||
| 2 | Up to 18 inches above grade or floor level within 20 feet horizontally of any edge of enclosure. | |
| With gravity ventilation_________ | 2 | Up to 18 inches above grade or floor level within 25 feet horizontally of any edge of enclosure. |
| Remote pump-Outdoor_________ | 1 | Any pit, box or space below grade level if any part is within a horizontal distance of 10 feet from any edge of pump. |
| 2 | Within 3 feet of any edge of pump, extending in all directions. Also up to 18 inches above grade level within 10 feet horizontally from any edge of pump. | |
| Remote pump-Indoor_________ | 1 | Entire area within any pit. |
| 2 | Within 5 feet of any edge of pump, extending in all directions. Also up to 3 feet above floor or grade level within 25 feet horizontally from any edge of pump. | |
| Lubrication or service room_________ | ||
| 1 | Entire area within any pit. | |
| 2 | Area up to 18 inches above floor or grade level within entire lubrication room. | |
| Dispenser for Class I liquids_________ | ||
| 2 | Within 3 feet of any fill or dispensing point, extending in all directions. | |
| Special enclosure inside building per | ||
| WAC 296-24-33013(1)(b) _________ | ||
| 1 | Entire enclosure. | |
| Sales, storage and rest rooms_________ | ||
| (1) | If there is any opening to these rooms within the extent of a Division 1 area, the entire room must be classified as Division 1. |
Footnote (1) Ordinary.
(5)
Heating equipment.
(a)
Conformance. You must
install heating equipment as provided in (b) through (e) of this
subsection.
(b)
Application. Heating equipment may be installed in the
conventional manner in an area except as provided in (c), (d) or (e) of this
subsection.
(c)
Special
room. Heating equipment may be installed in a special room separated
from an area classified by Table H-19 by walls having a fire resistance rating
of at least one hour and without any openings in the walls within eight feet of
the floor into an area classified in Table H-19. You must not use this room for
combustible storage and all air for combustion purposes must come from outside
the building.
(d)
Work
areas. Heating equipment using gas or oil fuel may be installed in the
lubrication, sales, or service room where there is no dispensing or
transferring of Category 1 or 2 flammable liquids or Category 3 flammable
liquids with a flashpoint below 100°F (37.8°C), provided the bottom of
the combustion chamber is at least eighteen inches above the floor and the
heating equipment is protected from physical damage by vehicles. Heating
equipment using gas or oil fuel listed for use in garages may be installed in
the lubrication or service room where Category 1 or 2 flammable liquids, or
Category 3 flammable liquids with a flashpoint below 100°F (37.8°C),
are dispensed provided the equipment is installed at least eight feet above the
floor.
(e)
Electric
heat. Electrical heating equipment must conform to subsection (4) of
this section.
(6)
Drainage and waste disposal. You must make provisions in the area
where Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a
flashpoint below 100°F (37.8°C), are dispensed to prevent spilled
liquids from flowing into the interior of service station buildings. Such
provision may be by grading driveways, raising door sills, or other equally
effective means. You must not dump crankcase drainings and flammable liquids
into sewers but you must store them in tanks or drums outside of any building
until removed from the premises.
(7)
Sources of ignition. In
addition to the previous restrictions of this section, the following must
apply: You must ensure that there is no smoking or open flames in the areas
used for fueling, servicing fuel systems for internal combustion engines,
receiving or dispensing of flammable liquids. You must post conspicuous and
legible signs prohibiting smoking within sight of the customer being served.
You must shut off motors of all equipment being fueled during the fueling
operation.
(8)
Fire
control. You must provide each service station with at least one fire
extinguisher having a minimum approved classification of 6 B, C located so that
an extinguisher will be within 75 feet of each pump, dispenser, underground
fill pipe opening, and lubrication or service room.
Notes
For additional requirements relating to portable fire extinguishers see WAC 296-800-300.