Wash. Admin. Code § 296-24-59212 - Hydrostatic testing
(1)
You must ensure that an internal examination of cylinders and shells to be tested is made prior to the hydrostatic tests in addition to an external visual examination.
(2) You must ensure that portable fire
extinguishers are hydrostatically tested whenever they show new evidence of
corrosion or mechanical injury.
(3)
You must ensure that hydrostatic tests are performed on extinguisher hose
assemblies which are equipped with a shut-off nozzle at the discharge end of
the hose. The test interval shall be the same as specified for the extinguisher
on which the hose is installed.
(4)
You must ensure that carbon dioxide hose assemblies with a shut-off nozzle are
hydrostatically tested at 1,250 psi (8,620 kPa).
(5) You must ensure that dry chemical and dry
powder hose assemblies with a shut-off nozzle are hydrostatically tested at 300
psi (2,070 kPa).
(6) Hose
assemblies passing a hydrostatic test do not require any type of recording or
stamping.
(7) You must ensure that
hose assemblies for carbon dioxide extinguishers that require a hydrostatic
test are tested within a protective cage device.
(8) You must ensure that carbon dioxide
extinguishers and nitrogen or carbon dioxide cylinders used with wheeled
extinguishers are tested every five years at 5/3 of the service pressure as
stamped into the cylinder. Nitrogen cylinders which comply with 29 C.F.R.
173.34(e)(15) may be hydrostatically tested every ten years.
(9) You must ensure that all stored pressure
and Halon 1211 types of extinguishers are hydrostatically tested at the factory
test pressure not to exceed two times the service pressure.
(10) You must ensure that acceptable
self-generating type soda acid and foam extinguishers are tested at 350 psi
(2,410 kPa).
(11)You must not use
air or gas pressure for hydrostatic testing.
(12)You must remove from service and from the
workplace extinguisher shells, cylinders, or cartridges which fail a
hydrostatic pressure test, or which are not fit for testing.
(13)You must meet the following requirements
for gas cylinders:
(a)The equipment for
testing compressed gas type cylinders must be of the water-jacket type. The
equipment must be provided with an expansion indicator which operates with an
accuracy within 1% of the total expansion or 0.1 cc (.1 mL) of
liquid.
(b) The equipment for
testing noncompressed gas type cylinders must consist of the following:
(i) A hydrostatic test pump, hand or power
operated, capable of producing not less than 150% of the test pressure, which
must include appropriate check valves and fittings;
(ii) A flexible connection for attachment to
fittings to test through the extinguisher nozzle, test bonnet, or hose outlet,
as is applicable; and
(iii) A
protective cage or barrier for personal protection of the tester, designed to
provide visual observation of the extinguisher under test.
Notes
Statutory Authority: RCW 49.17.010, [49.17].040, and[49.17].050 . 01-11-038, § 296-24-59212, filed 5/9/01, effective 9/1/01.