Wash. Admin. Code § 296-24-94003 - Installation and equipment requirements
(1)
Installation. Air receivers
must be so installed that all drains, handholes, and manholes therein are
easily accessible. Air receivers should be supported with sufficient clearance
to permit a complete external inspection and to avoid corrosion of external
surfaces. You must not under any circumstances bury an air receiver underground
or locate it in an inaccessible place. The receiver should be located as close
to the compressor or after-cooler as is possible in order to keep the discharge
pipe short.
(2)Drains and
traps. All air receivers having an internal and external operating
pressure exceeding 15 psi with no limitation on size, and air receivers having
an inside diameter exceeding six inches, with no limitation on pressure, if
subject to corrosion, must be supplied with a drain pipe and valve at the
lowest point in the vessel; or a pipe may be used extending inward from any
other location to within one-quarter inch of the lowest point. Adequate
automatic traps may be installed in addition to drain valves. The drain valve
on the air receiver must be opened and the receiver completely drained
frequently and at such intervals as to prevent the accumulation of oil and
water in the receiver.
(3)
Gauges and valves.
(a) Every air
receiver must be equipped with an indicating pressure gauge (so located as to
be readily visible) and with one or more spring-loaded safety valves. The total
relieving capacity of such safety valves must be such as to prevent pressure in
the receiver from exceeding the maximum allowable working pressure of the
receiver by more than 10 %.
(b) You
must ensure that no valve of any type is placed between the air receiver and
its safety valve or valves.
(c)
Safety appliances, such as safety valves, indicating devices and controlling
devices, must be constructed, located, and installed so that they cannot be
readily rendered inoperative by any means, including the elements.
(d) You must test all safety valves
frequently and at regular intervals to determine whether they are in good
operating condition.
Notes
Statutory Authority: Chapter 49.17 RCW. 89-11-035 (Order 89-03), § 296-24-94003, filed 5/15/89, effective 6/30/89; Order 73-5, § 296-24-94003, filed 5/9/73 and Order 73-4, § 296-24-94003, filed 5/7/73.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.