(1)
Use and identification of grounded and grounding conductors.
(a)Identification of conductors.
(i) A conductor used as a grounded conductor
must be identifiable and distinguishable from all other conductors.
(ii) A conductor used as an equipment
grounding conductor must be identifiable and distinguishable from all other
conductors.
(b)
Polarity of connections. No grounded conductor may be attached to
any terminal or lead so as to reverse designated polarity.
(c)Use of grounding terminals and
devices. A grounding terminal or grounding-type device on a receptacle,
cord connector, or attachment plug may not be used for purposes other than
grounding.
(2)
Branch circuits.
(a)Identification of multiwire branch
circuits. Where more than one nominal voltage system exists in a
building containing multiwire branch circuits, you must identify each
ungrounded conductor of a multiwire branch circuit, where accessible, by phase
and system. You must permanently post the means of identification at each
branch-circuit panelboard.
(b)Receptacles and cord
connectors.
(i) Receptacles installed
on 15- and 20-ampere branch circuits must be of the grounding type except as
permitted for replacement receptacles in (b)(iv) of this subsection. You must
only install grounding-type receptacles on circuits of the voltage class and
current for which they are rated, except as provided in Table S-4 and Table
S-5.
(ii) Receptacles and cord
connectors having grounding contacts must have those contacts effectively
grounded except for receptacles mounted on portable and vehicle-mounted
generators in accordance with subsection (7)(c) of this section and replacement
receptacles installed in accordance with (b)(iv) of this subsection.
(iii) You must ground the grounding contacts
of receptacles and cord connectors shall be grounded by connection to the
equipment grounding conductor of the circuit supplying the receptacle or cord
connector. The branch circuit wiring method must include or provide an
equipment grounding conductor to which the grounding contacts of the receptacle
or cord connector must be connected.
(iv) Replacement of receptacles must comply
with the following requirements:
(A) Where a
grounding means exists in the receptacle enclosure or a grounding conductor is
installed, you must use grounding-type receptacles and you must connect them to
the grounding means or conductor;
(B) You must provide ground-fault
circuit-interrupter protected receptacles where replacements are made at
receptacle outlets that are required to be so protected elsewhere in this part;
and
(C) Where a grounding means
does not exist in the receptacle enclosure, the installation must comply with
one of the following provisions:
(I) A
nongrounding-type receptacle may be replaced with another nongrounding-type
receptacle; or
(II) A
nongrounding-type receptacle may be replaced with a ground-fault
circuit-interrupter-type of receptacle that is marked "No Equipment Ground;" an
equipment grounding conductor may not be connected from the ground-fault
circuit-interrupter-type receptacle to any outlet supplied from the
ground-fault circuit-interrupter receptacle; or
(III) A nongrounding-type receptacle may be
replaced with a grounding-type receptacle where supplied through a ground-fault
circuit-interrupter; you must mark the replacement receptacle "GFCI Protected"
and "No Equipment Ground;" an equipment grounding conductor may not be
connected to such grounding-type receptacles.
(v) Receptacles connected to circuits having
different voltages, frequencies, or types of current (AC or DC) on the same
premises must be of such design that the attachment plugs used on these
circuits are not interchangeable.
(c)
Ground-fault circuit interrupter
protection for personnel.
(i) All
125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or
on rooftops must have ground-fault circuit-interrupter protection for
personnel.
(ii) The following
requirements apply to temporary wiring installations that are used during
construction-like activities, including certain maintenance, remodeling, or
repair activities, involving buildings, structures or equipment.
(A)All 125-volt, single-phase, 15-, 20-, and
30-ampere receptacle outlets that are not part of the permanent wiring of the
building or structure and that are in use by personnel must have ground-fault
circuit-interrupter protection for personnel.
Note 1: A cord connector on an extension cord
set is considered to be a receptacle outlet if the cord set is used for
temporary electric power.
Note 2: Cord sets and devices incorporating the
required ground-fault circuit-interrupter that are connected to the receptacle
closest to the source of power are acceptable forms of
protection.
(B) Receptacles
other than 125 volt, single-phase, 15-, 20-, and 30-ampere receptacles that are
not part of the permanent wiring of the building or structure and that are in
use by personnel must have ground-fault circuit-interrupter protection for
personnel.
(C) Where the
ground-fault circuit-interrupter protection required by (c)(ii)(B) of this
subsection is not available for receptacles other than 125-volt, single-phase,
15-, 20-, and 30-ampere, you must establish and implement an assured equipment
grounding conductor program covering cord sets, receptacles that are not a part
of the building or structure, and equipment connected by cord and plug that are
available for use or used by employees on those receptacles. This program must
comply with the following requirements:
(I) A
written description of the program, including the specific procedures adopted
by the employer, must be available at the job site for inspection and copying
by the director and their authorized representative, and any affected
employee;
(II) You must designate
one or more competent persons to implement the program;
(III) You must visually inspect each cord
set, attachment cap, plug, and receptacle of cord sets, and any equipment
connected by cord and plug, except cord sets and receptacles which are fixed
and not exposed to damage, before each day's use for external defects, such as
deformed or missing pins or insulation damage, and for indications of possible
internal damage. You must not use equipment found damaged or defective until
repaired;
(IV) You must perform the
following tests on all cord sets and receptacles which are not a part of the
permanent wiring of the building or structure, and cord- and plug-connected
equipment required to be grounded:
* You must test all equipment grounding conductors for
continuity and proven to be electrically continuous;
* You must test each receptacle and attachment cap or plug
for correct attachment of the equipment grounding conductor. You must connect
the equipment grounding conductor to its proper terminal; and
* You must perform all required tests before first use;
before equipment is returned to service following any repairs; before equipment
is used after any incident which can be reasonably suspected to have caused
damage (for example, when a cord set is run over); and at intervals not to
exceed three months, except that you must test cord sets and receptacles which
are fixed and not exposed to damage at intervals not exceeding six
months;
(V) You must not
make available or permit the use by employees of any equipment which has not
met the requirements of (c)(ii)(C) of this subsection; and
(VI) You must record tests performed as
required in (c)(ii)(C) of this subsection. This test record must identify each
receptacle, cord set, and cord- and plug-connected equipment that passed the
test and must indicate the last date it was tested or the interval for which it
was tested. You must keep this record by means of logs, color coding, or other
effective means and you must maintain it until replaced by a more current
record. You must make the record available on the job site for inspection by
the assistant secretary and any affected employee.
(d)
Outlet
devices. Outlet devices must have an ampere rating not less than the
load to be served and must comply with the following provisions:
(i) Where connected to a branch circuit
having a rating in excess of 20 amperes, lampholders must be of the heavy-duty
type. A heavy-duty lampholder must have a rating of not less than 660 watts if
of the ad medium type and not less than 750 watts if of any other type;
and
(ii) Receptacle outlets must
comply with the following provisions:
(A) A
single receptacle installed on an individual branch circuit must have an ampere
rating of not less than that of the branch circuit;
(B) Where connected to a branch circuit
supplying two or more receptacles or outlets, a receptacle may not supply a
total cord- and plug-connected load in excess of the maximum specified in Table
S-4; and
(C) Where connected to a
branch circuit supplying two or more receptacles or outlets, receptacle ratings
must conform to the values listed in Table S-5; or, where larger than 50
amperes, the receptacle rating may not be less than the branch-circuit rating.
However, receptacles of cord-and plug-connected arc welders may have ampere
ratings not less than the minimum branch-circuit conductor ampacity.
(e)
Cord
connections. You must install a receptacle outlet wherever flexible
cords with attachment plugs are used. Where flexible cords are permitted to be
permanently connected, receptacles may be omitted.
Table S-4- Maximum Cord- and Plug-Connected Load to
Receptacle
| Circuit rating (amperes) |
Receptacle rating (amperes) |
Maximum load (amperes) |
| 15 or 20 |
15 |
12 |
| 20 |
20 |
16 |
| 30 |
30 |
24 |
Table S-5- Receptacle Ratings for Various Size
Circuits
| Circuit rating (amperes) |
Receptacle rating (amperes) |
| 15 |
Not over 15 |
| 20 |
15 or 20 |
| 30 |
30 |
| 40 |
40 or 50 |
| 50 |
50 |
(3)
Outside conductors, 600 volts,
nominal, or less. The following requirements apply to branch-circuit,
feeder, and service conductors rated 600 volts, nominal, or less and run
outdoors as open conductors.
(a)Conductors on poles.
Conductors on poles must have a separation of not less than 1 foot where not
placed on racks or brackets. Conductors supported on poles must provide a
horizontal climbing space not less than the following:
(i) Power conductors below communication
conductors-30 inches;
(ii) Power
conductors alone or above communication conductors:
(A) 300 volts or less-24 inches;
(B) Over 300 volts-30 inches.
(iii) Communication conductors
below power conductors-Same as power conductors; and
(iv) Communications conductors alone No
requirement.
(b)
Clearance from ground. Open conductors, open multiconductor
cables, and service-drop conductors of not over 600 volts, nominal, must
conform to the minimum clearances specified in Table S-6.
Table S-6 Clearances From Ground
| Installations built before August 13,
2007 |
Installations built on or after August
13, 2007 |
| Distance |
Maximum Voltage |
Conditions |
Voltage to ground |
Conditions |
| 10 feet |
< 600 V |
Above finished grade or sidewalks, or from any platform
or projection from which they might be reached. (If these areas are accessible
to other than pedestrian traffic, then one of the other conditions
applies.) |
< 150 V |
Above finished grade or sidewalks, or from any platform
or projection from which they might be reached. (If these areas are accessible
to other than pedestrian traffic, then one of the other conditions
applies.) |
| 12 feet |
< 600 V |
Over areas, other than public streets, alleys, roads, and
driveways, subject to vehicular traffic other than truck traffic. |
< 300 V |
Over residential property and driveways. Over commercial
areas subject to pedestrian traffic or to vehicular traffic other than truck
traffic. (This category includes conditions covered under the 3.05 m (10.0 ft)
category where the voltage exceeds 150 V.) |
| 4.57 m (15.0 ft) |
< 600 V |
Over areas, other than public streets, alleys, roads, and
driveways, subject to truck traffic. |
301 to 600 V |
Over residential property and driveways. Over commercial
areas subject to pedestrian traffic or to vehicular traffic other than truck
traffic. (This category includes conditions covered under the 3.05 m (10.0 ft)
category where the voltage exceeds 300 V.) |
| 5.49 m (18.0 ft) |
< 600 V |
Over public streets, alleys, roads, and driveways. |
< 600 V |
Over public streets, alleys, roads, and driveways. Over
commercial areas subject to truck traffic. Other land traversed by vehicles,
including land used for cultivating or grazing and forests and orchards. |
(c)
Clearance from building openings.
(i) Service conductors installed as open
conductors or multiconductor cable without an overall outer jacket must have a
clearance of not less than 3 feet from windows that are designed to be opened,
doors, porches, balconies, ladders, stairs, fire escapes, and similar
locations. However, conductors that run above the top level of a window may be
less than 3 feet from the window. You must maintain vertical clearance of final
spans above, or within 3 feet measured horizontally of, platforms, projections,
or surfaces from which they might be reached in accordance with (b) of this
subsection.
(ii) Overhead service
conductors may not be installed beneath openings through which materials may be
moved, such as openings in farm and commercial buildings, and may not be
installed where they will obstruct entrance to these building
openings.
(d)
Above roofs. Overhead spans of open conductors and open
multiconductor cables must have a vertical clearance of not less than 8 feet
above the roof surface. You must maintain the vertical clearance above the roof
level for a distance not less than 3 feet in all directions from the edge of
the roof.
(i) The area above a roof surface
subject to pedestrian or vehicular traffic must have a vertical clearance from
the roof surface in accordance with the clearance requirements in (b) of this
subsection.
(ii) A reduction in
clearance to 3 feet is permitted where the voltage between conductors does not
exceed 300 and the roof has a slope of 4 inches in 12 inches or
greater.
(iii) A reduction in
clearance above only the overhanging portion of the roof to not less than 18
inches is permitted where the voltage between conductors does not exceed 300
if:
(A) The conductors do not pass above the
roof overhang for a distance of more than 6 feet, 4 feet horizontally;
and
(B) The conductors are
terminated at a through-the-roof raceway or approved support.
(iv) The requirement for
maintaining a vertical clearance of 3 feet from the edge of the roof does not
apply to the final conductor span, where the conductors are attached to the
side of a building.
(6)Overcurrent protection.
(a)
600 volts, nominal, or less.
The following requirements apply to overcurrent protection of circuits rated
600 volts, nominal, or less.
(i) You must
protect conductors and equipment from overcurrent in accordance with their
ability to safely conduct current.
(ii) Except for motor running overload
protection, over-current devices may not interrupt the continuity of the
grounded conductor unless all conductors of the circuit are opened
simultaneously.
(iii) You must
provide a disconnecting means on the supply side of all fuses in circuits over
150 volts to ground and cartridge fuses in circuits of any voltage where
accessible to other than qualified persons so that each individual circuit
containing fuses can be independently disconnected from the source of power.
However, a current-limiting device without a disconnecting means is permitted
on the supply side of the service disconnecting means. In addition, a single
disconnecting means is permitted on the supply side of more than one set of
fuses as permitted by the exception in WAC
296-24-95707(10)(d)(vi)
for group operation of motors, and a single
disconnecting means is permitted for fixed electric space-heating
equipment.
(iv) Overcurrent devices
must be readily accessible to each employee or authorized building management
personnel. These overcurrent devices may not be located where they will be
exposed to physical damage or in the vicinity of easily ignitable
material.
(v) Fuses and circuit
breakers must be so located or shielded that employees will not be burned or
otherwise injured by their operation. Handles or levers of circuit breakers,
and similar parts that may move suddenly in such a way that persons in the
vicinity are likely to be injured by being struck by them, must be guarded or
isolated.
(vi) Circuit breakers
must clearly indicate whether they are in the open (off) or closed (on)
position.
(vii) Where circuit
breaker handles on switchboards are operated vertically rather than
horizontally or rotationally, the up position of the handle must be the closed
(on) position.
(viii) Circuit
breakers used as switches in 120-volt and 277-volt, fluorescent lighting
circuits must be listed and marked "SWD."
(ix) A circuit breaker with a straight
voltage rating, such as 240 V or 480 V, may only be installed in a circuit in
which the nominal voltage between any two conductors does not exceed the
circuit breaker's voltage rating. A two-pole circuit breaker may not be used
for protecting a 3-phase, corner-grounded delta circuit unless the circuit
breaker is marked 1[PHI] - 3[PHI] to indicate such suitability. A circuit
breaker with a slash rating, such as 120/240 V or 480Y/277 V, may only be
installed in a circuit where the nominal voltage of any conductor to ground
does not exceed the lower of the two values of the circuit breaker's voltage
rating and the nominal voltage between any two conductors does not exceed the
higher value of the circuit breaker's voltage rating.
(b)
Feeders and branch circuits over
600 volts, nominal. The following requirements apply to feeders and
branch circuits energized at more than 600 volts, nominal.
(i) Feeder and branch-circuit conductors must
have overcurrent protection in each ungrounded conductor located at the point
where the conductor receives its supply or at a location in the circuit
determined under engineering supervision;
(A)
Circuit breakers used for overcurrent protection of three-phase circuits must
have a minimum of three overcurrent relays operated from three current
transformers. On three-phase, three-wire circuits, an overcurrent relay in the
residual circuit of the current transformers may replace one of the phase
relays. An overcurrent relay, operated from a current transformer that links
all phases of a three-phase, three-wire circuit, may replace the residual relay
and one other phase-conductor current transformer. Where the neutral is not
grounded on the load side of the circuit, the current transformer may link all
three phase conductors and the grounded circuit conductor (neutral);
and
(B) If fuses are used for
overcurrent protection, a fuse shall be connected in series with each
ungrounded conductor;
(ii) Each protective device must be capable
of detecting and interrupting all values of current that can occur at its
location in excess of its trip setting or melting point;
(iii) You must coordinate the operating time
of the protective device, the available short-circuit current, and the
conductor used to prevent damaging or dangerous temperatures in conductors or
conductor insulation under short-circuit conditions; and
(iv) The following additional requirements
apply to feeders only:
(A) The continuous
ampere rating of a fuse may not exceed three times the ampacity of the
conductors. The longtime trip element setting of a breaker or the minimum trip
setting of an electronically actuated fuse may not exceed six times the
ampacity of the conductor. For fire pumps, conductors may be protected for
short circuit only; and
(B)Conductors tapped to a feeder may be
protected by the feeder overcurrent device where that overcurrent device also
protects the tap conductor.
(7)
Grounding. This subsection
contains grounding requirements for systems, circuits, and equipment.
(a)
Systems to be grounded. You
must ground systems that supply premises wiring as follows:
(i) You must ground the neutral conductor of
all 3-wire DC systems;
(ii) You
must ground 2-wire DC systems operating at over 50 volts through 300 volts
between conductors:
(A) They supply only
industrial equipment in limited areas and are equipped with a ground
detector;
(B)They are
rectifier-derived from an AC system complying with (a)(iii) through (v) of this
subsection; or
(C)They are
fire-alarm circuits having a maximum current of 0.030 amperes;
(iii) You must ground AC circuits
of less than 50 volts if they are installed as overhead conductors outside of
buildings or if they are supplied by transformers and the transformer primary
supply system is ungrounded or exceeds 150 volts to ground;
(iv) You must ground AC systems of 50 volts
to 1000 volts under any of the following conditions, unless exempted by (a)(v)
of this subsection:
(A) If the system can be
so grounded that the maximum voltage to ground on the ungrounded conductors
does not exceed 150 volts;
(B) If
the system is nominally rated three-phase, four-wire wye connected in which the
neutral is used as a circuit conductor;
(C) If the system is nominally rated
three-phase, four-wire delta connected in which the midpoint of one phase is
used as a circuit conductor; or
(D)
If a service conductor is uninsulated;
(v) AC systems of 50 volts to 1000 volts are
not required to be grounded under any of the following conditions:
(A) If the system is used exclusively to
supply industrial electric furnaces for melting, refining, tempering, and the
like;
(B) If the system is
separately derived and is used exclusively for rectifiers supplying only
adjustable speed industrial drives;
(C) If the system is separately derived and
is supplied by a transformer that has a primary voltage rating less than 1000
volts, provided all of the following conditions are met:
(I)The system is used exclusively for control
circuits;
(II) The conditions of
maintenance and supervision ensure that only qualified persons will service the
installation;
(III) Continuity of
control power is required; and
(IV)
Ground detectors are installed on the control system;
(D) If the system is an isolated power system
that supplies circuits in health care facilities; or
(E) If the system is a high-impedance
grounded neutral system in which a grounding impedance, usually a resistor,
limits the ground-fault current to a low value for 3-phase AC systems of 480
volts to 1000 volts provided all of the following conditions are met:
(I) The conditions of maintenance and
supervision ensure that only qualified persons will service the
installation;
(II) Continuity of
power is required;
(III) Ground
detectors are installed on the system; and
(IV) Line-to-neutral loads are not
served.
(b)
Conductor to be grounded.
The conductor to be grounded for AC premises wiring systems required to be
grounded by (a) of this subsection must be as follows:
(i) You must ground one conductor of a
single-phase, 2-wire system;
(ii)
You must ground the neutral conductor of a single-phase, 3-wire
system;
(iii) You must ground the
common conductor of a multiphase system having one wire common to all
phases;
(iv) You must ground one
phase conductor of a multiphase system where one phase is grounded;
and
(v) You must ground the neutral
conductor of a multiphase system in which one phase is used as a neutral
conductor.
(c)Portable and vehicle-mounted
generators.
(i) The frame of a
portable generator need not be grounded and may serve as the grounding
electrode for a system supplied by the generator under the following
conditions:
(A)The generator supplies only
equipment mounted on the generator or cord- and plug-connected equipment
through receptacles mounted on the generator, or both; and
(B) The noncurrent-carrying metal parts of
equipment and the equipment grounding conductor terminals of the receptacles
are bonded to the generator frame.
(ii) The frame of a vehicle need not be
grounded and may serve as the grounding electrode for a system supplied by a
generator located on the vehicle under the following conditions:
(A)The frame of the generator is bonded to
the vehicle frame;
(B) The
generator supplies only equipment located on the vehicle and cord- and
plug-connected equipment through receptacles mounted on the vehicle;
(C) The noncurrent-carrying metal parts of
equipment and the equipment grounding conductor terminals of the receptacles
are bonded to the generator frame; and
(D) The system complies with all other
provisions of this subsection.
(iii) You must bond a system conductor that
is required to be grounded by the provisions in (b) of this subsection to the
generator frame where the generator is a component of a separately derived
system.
(d)Grounding connections.
(i) For a grounded system, you must use a
grounding electrode conductor to connect both the equipment grounding conductor
and the grounded circuit conductor to the grounding electrode. You must connect
both the equipment grounding conductor and the grounding electrode conductor to
the grounded circuit conductor on the supply side of the service disconnecting
means or on the supply side of the system disconnecting means or overcurrent
devices if the system is separately derived.
(ii) For an ungrounded service-supplied
system, you must connect the equipment grounding conductor to the grounding
electrode conductor at the service equipment. For an ungrounded separately
derived system, you must connect the equipment grounding conductor to the
grounding electrode conductor at, or ahead of, the system disconnecting means
or overcurrent devices.
(iii) On
extensions of existing branch circuits that do not have an equipment grounding
conductor, grounding-type receptacles may be grounded to a grounded cold water
pipe near the equipment if the extension was installed before August 13, 2007.
When any element of this branch circuit is replaced, the entire branch circuit
must use an equipment grounding conductor that complies with all other
provisions of this subsection.
(e)Grounding path. The path to
ground from circuits, equipment, and enclosures must be permanent, continuous,
and effective.
(f)
Supports,
enclosures, and equipment to be grounded.
(i) You must ground metal cable trays, metal
raceways, and metal enclosures for conductors, except that:
(A) Metal enclosures such as sleeves that are
used to protect cable assemblies from physical damage need not be grounded;
and
(B) Metal enclosures for
conductors added to existing installations of open wire, knob-and-tube wiring,
and nonmetallic-sheathed cable need not be grounded if all of the following
conditions are met:
(I) Runs are less than 25
feet;
(II) Enclosures are free from
probable contact with ground, grounded metal, metal laths, or other conductive
materials; and
(III) Enclosures are
guarded against employee contact.
(ii) You must ground metal enclosures for
service equipment.
(iii) You must
ground frames of electric ranges, wall-mounted ovens, counter-mounted cooking
units, clothes dryers, and metal outlet or junction boxes that are part of the
circuit for these appliances.
(iv)
You must ground exposed noncurrent-carrying metal parts of fixed equipment that
may become energized under any of the following conditions:
(A) If within 8 feet vertically or 5 feet
horizontally of ground or grounded metal objects and subject to employee
contact;
(B) If located in a wet or
damp location and not isolated;
(C)
If in electrical contact with metal;
(D) If in a hazardous (classified)
location;
(E) If supplied by a
metal-clad, metal-sheathed, or grounded metal raceway wiring method;
or
(F) If equipment operates with
any terminal at over 150 volts to ground.
(v) Notwithstanding the provisions of (f)(iv)
of this subsection, exposed noncurrent-carrying metal parts of the following
types of fixed equipment need not be grounded:
(A) nclosures for switches or circuit
breakers used for other than service equipment and accessible to qualified
persons only;
(B) Electrically
heated appliances that are permanently and effectively insulated from
ground;
(C) Distribution apparatus,
such as transformer and capacitor cases, mounted on wooden poles, at a height
exceeding 8 feet above ground or grade level; and
(D) Listed equipment protected by a system of
double insulation, or its equivalent, and distinctively marked as
such.
(vi) You must
ground exposed noncurrent-carrying metal parts of cord- and plug-connected
equipment that may become energized under any of the following conditions:
(A) If in hazardous (classified) locations
(see WAC
296-24-95711);
(B) If operated at over 150 volts to ground,
except for guarded motors and metal frames of electrically heated appliances if
the appliance frames are permanently and effectively insulated from
ground;
(C) If the equipment is of
the following types:
(I)Refrigerators,
freezers, and air conditioners;
(II) Clothes-washing, clothes-drying, and
dishwashing machines, sump pumps, and electric aquarium equipment;
(III) Hand-held motor-operated tools,
stationary and fixed motor-operated tools, and light industrial motor-operated
tools;
(IV) Motor-operated
appliances of the following types: Hedge clippers, lawn mowers, snow blowers,
and wet scrubbers;
(V) Cord- and
plug-connected appliances used in damp or wet locations, or by employees
standing on the ground or on metal floors or working inside of metal tanks or
boilers;
(VI) Portable and mobile
X-ray and associated equipment;
(VII) Tools likely to be used in wet and
conductive locations; and
(VIII)Portable hand lamps.
(vii) Notwithstanding
the provisions of (f)(vi) of this subsection, the following equipment need not
be grounded:
(A)Tools likely to be used in
wet and conductive locations if supplied through an isolating transformer with
an ungrounded secondary of not over 50 volts; and
(B) Listed or labeled portable tools and
appliances protected by an approved system of double insulation, or its
equivalent. If such a system is employed, you must distinctively mark the
equipment to indicate that the tool or appliance utilizes an approved system of
double insulation.
(g)
Nonelectrical equipment. You
must ground the metal parts of the following nonelectrical equipment: Frames
and tracks of electrically operated cranes and hoists; frames of
nonelectrically driven elevator cars to which electric conductors are attached;
hand-operated metal shifting ropes or cables of electric elevators; and metal
partitions, grill work, and similar metal enclosures around equipment of over
750 volts between conductors.
(h)
Methods of grounding fixed equipment.
(i) You must ground noncurrent-carrying metal
parts of fixed equipment, if required to be grounded by this part, by an
equipment grounding conductor that is contained within the same raceway, cable,
or cord, or runs with or encloses the circuit conductors. For DC circuits only,
the equipment grounding conductor may be run separately from the circuit
conductors.
(ii) Electric equipment
is considered to be effectively grounded if it is secured to, and in electrical
contact with, a metal rack or structure that is provided for its support and
the metal rack or structure is grounded by the method specified for the
noncurrent-carrying metal parts of fixed equipment in (h)(i) of this
subsection. Metal car frames supported by metal hoisting cables attached to or
running over metal sheaves or drums of grounded elevator machines are also
considered to be effectively grounded.
(iii) For installations made before April 16,
1981, electric equipment is also considered to be effectively grounded if it is
secured to, and in metallic contact with, the grounded structural metal frame
of a building. When any element of this branch circuit is replaced, the entire
branch circuit must use an equipment grounding conductor that complies with all
other provisions of subsection (7) of this section.
(i)
Grounding of systems and circuits
of 1000 volts and over (high voltage). If high voltage systems are
grounded, they must comply with all applicable provisions of (a) through (h) of
this subsection as supplemented and modified by the following requirements:
(i) Systems supplying portable or mobile high
voltage equipment, other than substations installed on a temporary basis, must
comply with the following:
(A) The system
must have its neutral grounded through an impedance. If a delta-connected high
voltage system is used to supply the equipment, a system neutral must be
derived.
(B) You must connect
exposed noncurrent-carrying metal parts of portable and mobile equipment by an
equipment grounding conductor to the point at which the system neutral
impedance is grounded.
(C) You must
provide ground-fault detection and relaying to automatically deenergize any
high voltage system component that has developed a ground fault. You must
continuously monitor the continuity of the equipment grounding conductor so as
to deenergize automatically the high voltage feeder to the portable equipment
upon loss of continuity of the equipment grounding conductor.
(D) The grounding electrode to which the
portable equipment system neutral impedance is connected must be isolated from
and separated in the ground by at least 20 feet from any other system or
equipment grounding electrode, and there must be no direct connection between
the grounding electrodes, such as buried pipe, fence, and so forth.
(ii) You must ground all
noncurrent-carrying metal parts of portable equipment and fixed equipment,
including their associated fences, housings, enclosures, and supporting
structures. However, equipment that is guarded by location and isolated from
ground need not be grounded. Additionally, pole-mounted distribution apparatus
at a height exceeding 8 feet above ground or grade level need not be
grounded.