(1) Firefighter's
self-contained breathing apparatus (SCBA) must, at a minimum, meet the
requirements of the 1997 edition of NFPA 1981, Standard on Open-Circuit
Self-Contained Breathing Apparatus for Fire Fighters. Equipment purchased after
the effective date of this rule must meet the 2007 edition of NFPA 1981,
Standard on Open-Circuit Self-Contained Breathing Apparatus for Emergency
Services.
(2) Closed circuit SCBA
must:
(a) Be positive pressure;
(b) Be NIOSH certified; and
(c) Have a minimum 30-minute service
duration.
(3) Members
using SCBAs must operate in teams of two or more.
(4) Except as otherwise provided in this
chapter, fire departments must adopt, maintain and implement a written
respiratory protection program that addresses the requirements of chapter
296-842 WAC, Respiratory protection. This includes program administration,
medical limitations, equipment limitations, equipment selection, inspection,
use, maintenance, training, fit testing procedures, air quality, and program
evaluation.
|
Note:
|
Additional information on respirators and respirator
usage can be found in ANSI Z88.2 - American National Standard for Respiratory
Protection and various NFPA publications (1981, 1404, 1500, etc.).
|
(5)
Reserved.
(6) When the fire
department makes its own breathing air or uses vendor supplied breathing air,
they must maintain documentation certifying breathing air quality. The
breathing air must:
(a) Be tested at least
quarterly by using an air sample taken from the same outlet and in the same
manner as the respirator breathing air cylinders are filled or air line
respirators are connected.
(b) Meet
the requirements of either the 2003 edition of NFPA 1989, Standard on Breathing
Air Quality for Fire and Emergency Services Respiratory Protection or the 1997
edition of ANSI/CGA G7-1 - Commodity Specification for Air, with a minimum air
quality of grade D.
(c) Meet a
water vapor level of 24 ppm or less.
(7) Fit testing must be conducted in
accordance with this section and chapter
296-842 WAC, Respiratory protection.
(a) Each new member shall be tested by a
qualitative or quantitative method before being permitted to use SCBA's in a
hazardous atmosphere.
(b) Only
firefighters with a properly fitting facepiece must be permitted by the fire
department to function in a hazardous atmosphere with SCBA.
(c) Fit testing must be repeated:
(i) At least once every 12 months.
(ii) Whenever there are changes in the type
of SCBA or facepiece used.
(iii)
Whenever there are significant physical changes in the user. Example: Weight
change of 10 percent or more, scarring of face seal area, dental changes,
cosmetic surgery, or any other condition that may affect the fit of the
facepiece seal.
(d) The
fit testing is done only in a negative-pressure mode. If the facepiece is
modified for fit testing, the modification must not affect the normal fit of
the device. Such modified devices must only be used for fit testing.
(e) The fit test procedures and test
exercises described in WAC
296-842-15005 and
296-842-22010 must be followed
unless stated otherwise in this chapter.
(f) Respirator fit test records must include:
(i) Written guidelines for the respirator fit
testing program including pass/fail criteria;
(ii) Type of respirator tested including
manufacturer, model, and size;
(iii) Type of fit test and instrumentation or
equipment used;
(iv) Name or
identification of test operator;
(v) Name of person tested;
(vi) Date of test; and
(vii) Results of test.
|
Note:
|
Firefighters should be issued individual
facepieces.
|
(8) Facial hair, contact lenses, and eye and
face protective devices.
(a) A negative
pressure respirator, any self-contained breathing apparatus, or any respirator
which is used in an atmosphere immediately dangerous to life or health (IDLH)
equipped with a facepiece must not be worn if facial hair comes between the
sealing periphery of the facepiece and the face or if facial hair interferes
with the valve function.
(b) The
wearer of a respirator must not be allowed to wear contact lenses if the risk
of eye damage is increased by their use.
(c) If corrective lenses must be worn with a
facepiece, they must be worn so as to not adversely affect the seal of the
facepiece to the face. See WAC
296-842-18005(3).
(d) Straps or temple bars must not pass
between the seal or surface of the respirator and the user's face.
(9) At the end of suppression
activities (to include fire overhaul) and before returning to quarters:
(a) Gross/field decontamination must be
performed on firefighters prior to removal of their respirator whenever
firefighting activities resulted in exposure to a hazardous
substance.
(b) When exchanging air
supply bottles during suppression or overhaul activities, reasonable
precautions must be taken to maintain uncontaminated atmosphere to the
breathing zone and facepiece supply hose.
(10) Self-contained respiratory equipment
must be available and used by all firefighters who enter into hazardous
atmospheres during structural firefighting activities.
(11) Reserved.
(12) Respirators must be provided for, and
shall be used by, all personnel working in areas where:
(a) The atmosphere is hazardous;
(b) The atmosphere is suspected of being
hazardous; or
(c) The atmosphere
may rapidly become hazardous.
|
Reference:
|
See WAC
296-305-05002(13)
for additional requirements.
|
(13) Reserved.
(14) Firefighters using a properly
functioning SCBA must not compromise the protective integrity of the SCBA by
removing the facepiece for any reason in hazardous atmospheres or in
atmospheres where the quality of air is unknown.
(15) Firefighters must receive training for
each type and manufacturer of respiratory equipment available for their use,
the step-by-step procedure for donning the respirator and checking it for
proper function. Required training must include:
(a) Recognizing hazards that may be
encountered;
(b) Understanding the
components of the respirator;
(c)
Understanding the safety features and limitations of the respirator;
and
(d) Donning and doffing the
respirator.
(16) After
completing such training, each firefighter must practice at least quarterly,
for each type and manufacture of respirator available for use, the step-by-step
procedure for donning the respirator and checking it for proper
function.
(17) Members must be
tested at least annually on the knowledge of respiratory protection equipment
operation, safety, organizational policies and procedures, and facepiece seals,
to the fire department's standard. Such records must remain part of the member
training file.
(18) Members must be
allowed to use only the make, model, and size respirator for which they have
passed a fit test within the last 12 months.
(19) In cases where there is a reported
failure of a respirator, it must be removed from service, tagged and recorded
as such, and tested before being returned to service.
(20) Firefighters must be thoroughly trained
in accordance with the manufacturer's instructions on emergency procedures such
as use of regulator bypass valve, corrective action for facepiece and breathing
tube damage, and breathing directly from the regulator (where
applicable).
(21)
Reserved.
(22) SCBA cylinders must
be hydrostatically tested within the periods specified by the manufacturer and
the applicable governmental agencies.