|
Note:
|
When chapters of NFPA 1670, Standard on Operations
and Training for Technical Rescue Incidents, are required by the following
sections, internal references requiring compliance with further NFPAs or
additional resources are not included in these requirements.
|
(1) Structural
collapse. Fire departments choosing to operate at the operations or technician
level for structural collapse incidents must meet the requirements found in
chapter 5 of the 2009 edition of NFPA 1670, Standard on Operations and Training
for Technical Rescue Incidents.
(2)
Rope rescue.
(a) Fire departments choosing to
operate at the operations or technician level for rope rescue incidents must
meet the requirements of this section and the nonconflicting portions of
chapter 6 of the 2009 edition of NFPA 1670, Standard on Operations and Training
for Technical Rescue Incidents.
(b)
Fire departments performing rope rescue operations must make sure previously
purchased life safety ropes and equipment complies with the 2001 edition of
NFPA 1983, Standard on Fire Service Life Safety Rope and System Components.
Ropes and equipment purchased after the effective date of this rule must meet
the requirements of the 2006 edition of NFPA 1983, Standard on Life Safety Rope
and Equipment for Emergency Services.
(c) Life safety rope and rope rescue
equipment must be inspected after purchase and prior to placing in service,
after each use, and at least semiannually.
(d) Harnesses must be inspected for worn or
broken stitching, rivets worn out of holes, and damage from abrasion, cuts, or
chemicals.
(e) Descending/ascending
hardware must be inspected for wear, cracks, distortion, sharp edges, and ease
of operation.
(f) The
manufacturer's recommended shelf life of life safety ropes must be followed. If
no shelf life is specified, ropes greater than six years old must be taken out
of service as a life safety rope.
|
Note:
|
See WAC
296-305-02019,
Life safety ropes, harnesses, and hardware protection, for further
requirements. |
(3) Confined space rescue.
(a) Fire departments choosing to operate at
the operations or technician level for confined space rescue incidents must
meet the requirements of this section, chapter
296-809 WAC Table 1, and the
nonconflicting sections of chapter 7 of the 2009 edition of NFPA 1670, Standard
on Operations and Training for Technical Rescue Incidents.
(b) Fire departments must comply with chapter
296-809 WAC for their own confined spaces.
(c) Fire departments which will respond to
calls to perform rescue from a permit-required confined space are required to
have each member of a rescue team practice making permit space rescues at least
every twelve months by means of simulated rescue operations in which they
remove dummies, mannequins or actual persons from permit space. A permit is
required for the practice permit space entry.
(d) During an actual rescue response, written
or verbally recorded hazard sizeup will be allowed in lieu of the written
permit requirements in WAC
296-809-50004
and must be completed prior to any entry. This sizeup must include at a
minimum:
(i) Recognition and declaration of
the situation as a confined space incident.
(ii) Denial of entry to unprotected
persons.
(iii) Assessment of all
readily available confined space documentation, e.g., MSDSs, any existing
permit, plans or blueprints of the space.
(iv) Assessment of number of victim(s),
locations and injury conditions.
(v) Discussion with witnesses, supervisors,
and other sources of information.
(vi) Assessment of any current or potential
space hazards, in particular, any hazard(s) which lead to the necessary
rescue.
(vii) Determination and
declaration if the situation is a body recovery or a victim
rescue.
(e) At confined
space incidents, at least two people outside must be equipped with appropriate
breathing apparatus to act as the back-up team, which must remain free of the
contaminated area in order to rescue disabled firefighters.
(f) Written documentation of the rescue
team's training on the fire department's confined space operating procedures,
authorized entrant training, and the contracted host's confined space program
must be kept. A record of each of the hazard sizeups must be maintained for at
least one year.
(g) Anytime
firefighters are working inside a confined space, such persons must be provided
with SCBA or air line respirator with escape bottle, and must use the equipment
unless the safety of the atmosphere can be established by testing and
continuous monitoring.
(i) If the service
life of the auxiliary air supply is fifteen minutes or less it must not be used
for entry into an IDLH atmosphere but it may be used for escape purposes. The
auxiliary air supply may be used for entry into an IDLH atmosphere only when
the service life of the unit exceeds fifteen minutes and when not more than
twenty percent of the noted air supply will be used during entry.
(ii) The maximum length of hose for supplied
air respirators is three hundred feet (91 meters). Such hose must be heavy duty
nonkinking and NIOSH approved.
(4) Machinery rescue. Fire departments
choosing to operate at the operations or technician level for machinery rescue
incidents must meet the requirements of this section and the nonconflicting
portions of chapter 12 of the 2009 edition of NFPA 1670, Standard on Operations
and Training for Technical Rescue Incidents.
(5) Water rescue.
(a) Fire departments choosing to operate at
the operations or technician level for water rescue incidents must meet the
requirements of this section and the nonconflicting portions of chapter 9 of
the 2009 edition of NFPA 1670, Standard on Operations and Training for
Technical Rescue Incidents.
(b)
Organizations choosing to operate at the operations or technician level for
dive rescue incidents must meet the requirements found in chapter 9 of the 2009
edition of NFPA 1670, Standard on Operations and Training for Technical Rescue
Incidents.
(c) Fire departments
choosing to operate at the operations or technician level for dive recovery
incidents must meet the requirements found in chapter
296-37 WAC, Standards for
commercial diving operations, and the nonconflicting parts of chapter 9 of the
2009 edition of NFPA 1670, Standard on Operations and Training for Technical
Rescue Incidents.
(d) If a
manufacturer's specifications are such that an engineer is required for the
operation of a vessel, one must be provided.
(e) When fire boats perform rescue activities
they must have two dedicated personnel. Any member not specifically required to
operate the vessel, e.g., an operator (pilot) or engineer (if required by the
manufacturer's specification) may be used as a deck hand. This may include the
boat officer if their duties do not include operating the fire boat.
(f) Watercraft load capabilities must not
exceed the manufacturer's specifications.
(g) Each fire department must determine the
function of their watercraft; firefighting, rescue, or both.
(h) Watercraft operating within navigable
waters of the state of Washington (as defined by the United States Coast Guard)
must comply with all of the rules of the United States Coast Guard.
(i) Fire boats operating within navigable
waters of the state of Washington (as defined by the United States Coast Guard)
must have a fully dedicated pilot.
(j) The operator (pilot) of the watercraft is
responsible for its safe operation.
(k) Training for all personnel must cover the
physical characteristics of the vessel involved and must be included in the
employer's accident prevention program.
(i)
All assigned personnel must be trained in safe operation of watercraft and the
operations the craft is intended to perform.
(ii) All employees involved in water rescue
must be trained in water rescue techniques and use Coast Guard approved
personal flotation devices, Type III, minimum.
|
Exception:
|
Employees working below deck or in enclosed
cabins or when working above, on or alongside still water where flotation would
not be achieved, are exempt from this requirement. |
(l) All employers operating watercraft in
nonnavigable waters must be responsible for training all employees to local
hazards.
(6) Trench and
excavation rescue.
(a) Fire departments
choosing to operate at the operations or technician level for trench and
excavation rescue incidents must meet the requirements of this section and
non-conflicting portions of chapter 11 of the 2009 edition of NFPA 1670,
Standard on Operations and Training for Technical Rescue Incidents.
(b) Employees that directly engage in trench
rescue operations must be under the direct supervision of per-son(s) with
adequate training in trench and excavation hazard recognition, equipment use
and operational techniques.
(c)
Each employee in an excavation must be protected from cave-ins by an adequate
protective system except when:
(i) Excavations
are made entirely in stable rock; or
(ii) Excavations are less than four feet
(1.22 meters) in depth and examination of the ground by a competent person
provides no indication of a potential cave-in.
(7) Mine and tunnel rescue.
(a) Fire departments choosing to operate at
the operations or technician level for mine and tunnel rescue incidents must
meet the requirements of this section and the nonconflicting portions of
chapter 14 (Mine and Tunnel Search and Rescue) of the 2009 edition of NFPA
1670, Standard on Operations and Training for Technical Rescue
Incidents.
(b) The requirements of
this section apply to agencies that provide varying degrees of response to
tunnels under construction or other underground excavations formerly classified
as mines or tunnels.
(c) The
requirements of this section do not apply to operating mines, tourist mines,
basements, or subterranean structures that are complete and in use or that meet
the definition of a confined space.
(d) Emergency services that are the
designated primary provider of rescue services for operational mines and
tunnels under construction are required to comply with the nonconflicting
portions of chapter
296-155 WAC Part Q, Underground construction.
(e) Members who regularly enter a tunnel
under construction as part of their regular duties must receive training
meeting the requirements of the safety instruction required by WAC
296-155-730(3).
(f) Regardless of whether an atmospheric
hazard is detected, any entrant into a tunnel under construction, mine or any
related shaft or excavation must have a means of emergency egress respiratory
protection with no less than a thirty minute rated service life immediately
available. There must be at least one unit immediately available for each
member in the tunnel.
MSHA or NIOSH approved "Self Rescuer" or "Self Contained Self
Rescuer" devices fulfill this requirement provided the user has been trained in
its use and the device is suitable for the type of potential hazards that may
be encountered.
(g) A
rescue service entry team must have the ability at a minimum to continuously
monitor the air for oxygen, carbon monoxide, hydrogen sulfide, and combustible
gasses as well as any other atmospheric contaminants that are known or
suspected.
(h) The rescue service
entry team must have at least two methods of communication with the surface,
one of which must be voice communication.
This requirement may be satisfied by using both the "direct"
and "trunked" features of the same radio systems provided adequate equipment is
available to the entry team to provide constant simultaneous communication
using both methods.
(i)
Rescue service entry teams that enter a mine or tunnel with a known atmospheric
hazard must have a clearly defined "turnaround" benchmark to ensure adequate
egress to an area of refuge or safety.
(j) Each rescue service entry team that
enters a mine or tunnel with a known or suspected atmospheric hazard must have
at least one source of breathable air independent of each wearer's SCBA to be
used in the event of an SCBA failure or "out of air" emergency. This source of
air is to be independent of any device brought in for the use of
victims.
(k) A backup team with
similar size and capabilities as the rescue service entry team must be
immediately available to enter the space.
(l) Each member of the organization who is
designated as part of the technician level rescue service must practice making
mine or tunnel rescues as part of a rescue team no less than once every twelve
months. This may be accomplished by means of simulated rescue operations in
which the team removes dummies, mannequins, or persons from actual mines and
tunnels or from representative mines and tunnels.
Representative mine and tunnels should, with respect to opening
size, configuration, and accessibility, simulate the types of mines and tunnels
from which rescue is to be performed.