Wash. Admin. Code § 296-800-28025 - Maintain electrical fittings, boxes, cabinets and outlets in good condition
You must do the following when using covers and openings:
(1) When conductors enter
boxes, cabinets, or fittings:
(a) Protect the
conductor (wires) from abrasion.
(b) Effectively close the openings where
conductors enter.
(c) Effectively
close all unused openings.
(2) Provide pull boxes, junction boxes, and
fittings with covers approved for the purpose.
(3) Make sure each outlet box has a cover,
faceplate, or fixture canopy in completed installations.
(4) Make sure covers for outlet boxes with
openings for flexible cord pendants have bushings to protect the cord, or have
a smooth and well rounded surface where the cord touches the opening.
(5) Ground metal covers.
Notes
Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060, and chapter 49.17 RCW. 12-16-064, § 296-800-28025, filed 7/31/12, effective 9/1/12. Statutory Authority: RCW 49.17.010, [49.17].040, and [49.17].050. 01-23-060, § 296-800-28025, filed 11/20/01, effective 12/1/01; 01-11-038, § 296-800-28025, filed 5/9/01, effective 9/1/01.