Wash. Admin. Code § 296-800-30020 - Inspect and test all portable fire extinguishers
Make sure that portable fire extinguishers or hose systems (used instead of fire extinguishers) are visually inspected monthly.
Exemption: Most stored pressure extinguishers do not require an internal examination. Examples of those that do require an internal examination are those containing a loaded stream agent.
Exemption:
* Dry chemical extinguishers that have nonrefillable disposable containers are exempt from this requirement.
* Manually pressurized pumptanks are exempt from this requirement.
|
Note: |
Specific rules regarding conducting hydrostatic tests are covered in WAC 296-24-59212. |
When recharging or hydrostatic testing is performed, the 6-year requirement begins from that date
Hydrostatic Test Table
| Type of Extinguisher | Test Interval (Years) |
| Stored pressure water and/or antifreeze | 5 |
| Wetting agent | 5 |
| Foam (stainless steel shell) | 5 |
| Aqueous film forming form (AFFF) | 5 |
| Loaded stream | 5 |
| Dry chemical with stainless steel | 5 |
| Carbon dioxide | 5 |
| Dry chemical, stored pressure, with mild steel, brazed brass or aluminum shells | 12 |
| Halon 1211 | 12 |
| Halon 1301 | 12 |
| Dry powder, cartridge or cylinder operated, with mild steel shell | 12 |
|
Note: Due to a manufacturer's recall, stored pressure water extinguishers with fiberglass shell (pre-1976) are prohibited from hydrostatic testing. |
|
Notes
Statutory Authority: RCW 49.17.010, [49.17].040, and[49.17].050 . 01-23-060, § 296-800-30020, filed 11/20/01, effective 12/1/01; 01-11-038, § 296-800-30020, filed 5/9/01, effective 9/1/01.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.