W. Va. Code R. § 64-77-9 - Finished Water Storage
9.1.
General. -- The materials and designs used for finished water storage
structures shall provide stability and durability as well as protect the
quality of the stored water. Steel structures shall follow the current AWWA
standards concerning steel tanks, standpipes, reservoirs, and elevated tanks
wherever they are applicable. Other materials of construction are acceptable
when properly designed to meet the requirements of this section.
9.1.a. Sizing. -- Storage facilities shall
have sufficient capacity, as determined from engineering studies, to meet
domestic, commercial and industrial demands, and where fire protection is
provided, fire flow demands.
9.1.a.1. Fire
flow requirements established by the ISO shall be satisfied where fire
protection is provided.
9.1.a.2.
The minimum storage capacity (or equivalent capacity) for systems providing
fire protection shall be equal to twice the average daily demand of one hundred
fifty (150) gallons per customer per day plus fire flow unless it can be
demonstrated that the supply capacity of the system is sufficient to warrant
less. This requirement may be reduced when the source and treatment facilities
have sufficient capacity with standby power to supplement peak demands of the
system.
9.1.a.3. A recommended
storage capacity for community and non-community, non-transient public water
systems not providing fire protection shall be equal to twice the average daily
demand of one hundred fifty (150) gallons per customer per day.
9.1.b. Location of ground-level
reservoirs. -- The bottom of reservoirs and standpipes shall be placed at the
normal ground surface and shall be above the one hundred (100) year flood
level. When the bottom is below normal ground surface, it shall be placed above
the groundwater table. At least fifty per cent (50%) of the water depth of the
reservoir may be above grade. Sewers, drains, standing water, and similar
sources of possible contamination shall be kept at least fifty (50) feet from
the reservoir. A water main pipe, pressure tested in place to fifty (50) pounds
per square inch without leakage, may be located from twenty (20) to fifty (50)
feet from a sewer, but under no circumstances shall it be located within twenty
(20) feet of a sewer.
The top of a partially buried storage structure shall be at least two (2) feet above normal ground surface. Clearwells constructed under filters may be excepted from this requirement when the design provides adequate protection from contamination.
9.1.c. Protection. -- All finished water
storage structures shall have suitable watertight roofs and screened vents that
exclude birds, animals, insects, and excessive dust. The installation of
appurtenances, such as antenna, shall be done in a manner that ensures no
damage to the tank, coatings or water quality.
9.1.d. Protection from trespassers. --
Fencing, locks on access manholes, and other necessary precautions shall be
provided to prevent trespassing, vandalism and sabotage, including the
installation of high strength locks or lock covers to prevent direct cutting of
a lock, if possible.
9.1.e. Drains.
-- No drain on a water storage structure may have a direct connection to a
sewer or storm drain. The design shall allow draining the storage facility for
cleaning or maintenance without causing loss of pressure in the distribution
system.
9.1.f. Overflow. -- All
water storage structures shall be provided with an overflow that is brought
down to an elevation between twelve (12) and twenty-four (24) inches above the
ground surface and that discharges over a drainage inlet structure or a splash
plate. No overflow may be connected directly to a sewer or a storm drain. All
overflow pipes shall be located so that any discharge is visible.
9.1.f.1. When an internal overflow pipe is
used on elevated tanks, it shall be located in the access tube. For vertical
drops on other types of storage facilities, the overflow pipe shall be located
on the outside of the structure.
9.1.f.2. The overflow of a ground-level
structure shall open downward and be screened with twenty-four (24) mesh
non-corrodible screen installed within the pipe at a location least susceptible
to damage by vandalism.
9.1.f.3.
The overflow pipe shall be of sufficient diameter to permit waste of water in
excess of the filling rate.
9.1.g. Access. -- Finished water storage
structures shall be designed with reasonably convenient access to the interior
for cleaning and maintenance. Manholes above the water line: shall be framed at
least four (4) inches, and preferably (6) six inches, above the surface of the
roof at the opening; on ground-level structures, shall be elevated twenty-four
(24) to thirty-six (36) inches above the top or covering sod; shall be fitted
with a solid watertight cover that overlaps the framed opening and extends down
around the frame at least two (2) inches; shall be hinged at one (1) side; and
shall have a locking device.
9.1.h.
Vents. -- Finished water storage structures shall be vented. Overflows shall
not be considered as vents. Open construction between the sidewall and roof is
not permissible. Vents shall prevent the entrance of surface water and
rainwater and shall exclude birds, animals and insects, as much as this
function can be made compatible with effective venting. For elevated tanks and
standpipes, four (4) mesh non-corrodible screen may be used. On ground-level
structures, standpipes shall terminate in an inverted U construction with the
opening twenty-four (24) to thirty-six (36) inches above the roof or sod and be
covered with twenty-four (24) mesh non-corrodible screen installed within the
pipe at a location least susceptible to vandalism.
9.1.i. Roof and sidewall. -- The roof and
sidewalls of all structures shall be watertight with no openings except
properly constructed vents, manholes, overflows, risers, drains, pump
mountings, control ports and piping for inflow and outflow.
9.1.i.1. Any pipes running through the roof
or sidewall of a finished water storage structure shall be welded, or properly
gasketed in metal tanks. In concrete tanks, these pipes shall be connected to
standard wall castings that were poured in place during the forming of the
concrete. These wall castings shall have seepage rings imbedded in the
concrete.
9.1.i.2. Openings in a
storage structure roof or top, designed to accommodate control apparatus or
pump columns, shall be curbed and sleeved with proper additional shielding to
prevent the access of surface or floor drainage water into the
structure.
9.1.i.3. Valves and
controls shall be located outside the storage structure so that the valve stems
and similar projections do not pass through the roof or top of the
reservoir.
9.1.i.4. The roof of
concrete reservoirs with an earthen cover shall be sloped to facilitate
drainage. Consideration shall be given to installation of an impermeable
membrane roof covering.
9.1.i.5.
Locks shall be provided on valve vaults where applicable.
9.1.j. Drainage of roof. -- The roof of the
storage structure shall be well drained. Downspout pipes shall not enter or
pass through the reservoir. Parapets, or similar construction that would tend
to hold water and snow on the roof, shall not be approved by the BPH unless
adequate waterproofing and drainage are provided.
9.1.k. Safety. -- The safety of employees
shall be considered in the design of the storage structure. As a minimum,
employee safety matters shall conform to pertinent laws and rules.
9.1.k.1. Ladders, ladder guards, balcony
railings, and safely located entrance hatches shall be provided where
applicable. Elevated tanks with riser pipes more than eight inches in diameter
shall have protective bars over the riser openings inside the tank. Railings or
handholds shall be provided on elevated tanks where persons transfer from the
access tube to the water compartment. Confined space entry requirements shall
be considered.
9.1.l.
Freezing. -- All finished water storage structures and their appurtenances,
especially the riser pipes, overflows, and vents, shall be designed to prevent
freezing that interferes with proper functioning. Equipment used for freeze
protection that comes into contact with the potable water shall meet ANSI/NSF
Standard 61 or be approved by the BPH. If a water circulation system is used,
it is recommended that the circulation pipe be located separately from the
riser pipe.
9.1.m. Internal
catwalk. -- Every catwalk over finished water in a storage structure shall have
a solid floor with raised edges designed so that shoe scrapings and dirt do not
fall into the water.
9.1.n. Silt
stop. -- The discharge pipes from all reservoirs shall be located in a manner
that prevents the flow of sediment into the distribution system. Removable silt
stops shall be provided.
9.1.o.
Grading. -- The area surrounding a ground-level structure shall be graded in a
manner that prevents surface water from standing within fifty (50)
feet.
9.1.p. Painting and cathodic
protection. -- Proper protection shall be given to metal surfaces by paints or
other protective coatings, by cathodic protective devices, or by both. Paint
systems shall be certified to conform to ANSI/NSF Standard 61: Drinking Water
System Components - Health Effects. Interior paint shall be properly applied
and cured. After curing, the coating shall not transfer any substance to the
water that is toxic or cause tastes or odors. Prior to placing in service, an
analysis for volatile organic compounds is advisable to establish that the
coating is properly cured. Consideration shall be given to 100% solids
coatings. Wax coatings for the tank interior shall not be used on new tanks.
Recoating with a wax system is not allowed. Old wax coating shall be completely
removed before using another coating. Cathodic protection shall be installed on
below grade steel reservoirs and shall be designed and installed by competent
technical personnel; a maintenance contract shall be provided.
9.1.q. Disinfection. -- Finished water
storage structures shall be disinfected in accordance with current AWWA
Standard C652. Two (2) or more successive sets of samples, taken at twenty-four
(24) hour intervals, shall be microbiologically satisfactory before the
facility is placed into operation. Disposal of heavily chlorinated water from
the tank disinfection process shall be in accordance with the requirements of
the WVDEP. The disinfection procedure (AWWA C652 chlorination method 3,
subsection 4.3.) that allows use of the chlorinated water held in the storage
tank for disinfection purposes is not recommended. When that procedure is used,
it is recommended that the initial heavily chlorinated water be properly
disposed in order to prevent the release of water that may contain various
chlorinated organic compounds into the distribution system.
9.1.r. Provisions of Sampling. --
Smooth-nosed sampling taps shall be provided to facilitate collection of water
samples for both bacteriologic and chemical analysis. The sampling tap(s) shall
be easily accessible.
9.2. Plant Storage. -- The applicable design
standards for finished water storage shall be followed for plant storage.
9.2.a. Filter Washwater tanks. -- Filter
washwater tanks shall be sized, in conjunction with available pump units and
finished water storage, to provide the backwash water required. Consideration
shall be given to the backwashing of several filters in rapid
succession.
9.2.b. Clearwell. --
Clearwell storage shall be sized, in conjunction with distribution system
storage, to relieve the filters from having to follow fluctuations in water use
and meet peak demands, including filter backwash water. When finished water
storage is used to provide contact time for chlorine, special attention shall
be given to size and baffling. To ensure adequate chlorine contact time in
accordance with the West Virginia Bureau for Public Health rule, Public Water
Systems, 64CSR3, sizing of the clearwell shall include extra volume to
accommodate depletion of storage during the nighttime for intermittently
operated filtration plants with automatic high service pumping from the
clearwell during non-treatment hours. An overflow and vent shall be provided. A
minimum of two (2) clearwell compartments shall be provided.
9.2.c. Adjacent compartments. -- Finished
water shall not be stored or conveyed in a compartment adjacent to untreated or
partially treated water when the two compartments are separated by a single
wall.
9.2.d. Other treatment plant
storage tanks. -- Receiving basins, detention basins, backwash reclaim tanks
and pump wet wells for finished water shall be designed as finished water
storage structures.
9.3.
Hydropneumatic Tanks. -- Hydropneumatic (pressure) tanks serving community and
non-community, non-transient public water systems, when provided as the only
storage facility, are acceptable only in very small service areas. Systems
serving more than 150 living units shall have ground or elevated storage.
Hydropneumatic tank storage is not permitted for fire protection purposes.
Pressure tanks shall meet ASME code requirements or an equivalent requirement
of state or local laws and rules of construction and installation of unfired
pressure vessels. Non-ASME, factory-built hydropneumatic tanks may be allowed
if approved by the BPH.
9.3.a. Location. --
The tank shall be located above normal ground surface and be completely
housed.
9.3.b. Sizing. -- The
capacity of the pumps in a hydropneumatic system shall be at least ten (10)
times the average daily consumption rate. The gross volume of the
hydropneumatic tank, in gallons, shall be at least ten (10) times the capacity
of the largest pump, rated in gallons per minute. For example, a two hundred
fifty (250) gallon per minute pump shall have a two thousand five hundred
(2,500) gallon pressure tank, unless other measures, such as variable speed
drives in conjunction with the pump motors are provided to meet the maximum
demand. Sizing of hydropneumatic storage tanks shall consider the need for
chlorine detention time, as applicable, independent of the storage
requirements. If hydropneumatic tanks are considered for chlorine contact,
separate inlet and outlet connectors at top and bottom of the tank are
required.
9.3.c. Piping. -- The
hydropneumatic tank shall have bypass piping to permit operation of the system
while it is being repaired or painted.
9.3.d. Appurtenances. -- Each hydropneumatic
tank shall have an access manhole, a drain and control equipment consisting of
pressure gauge, water sight glass, automatic or manual air blow-off, a means
for adding air, and pressure operated start-stop controls for the pumps. A
pressure relief valve shall be installed and be capable of handling the full
pumpage rate of flow at the pressure vessel design limit. Where practical the
access manhole shall be twenty-four (24) inches in diameter.
9.3.e. Coatings. -- The interior coating of
all tanks shall meet ANSI/NSF Standard 61: Drinking Water System Components -
Health Effects.
9.4.
Distribution Storage. -- The applicable design standards of subsection 9.1. of
this rule shall be followed for distribution system storage. The minimum
storage capacity (or equivalent capacity) for systems providing fire protection
shall be equal to twice the average daily demand of one hundred fifty (150)
gallons per customer per day plus fire flow unless it can be demonstrated that
the supply capacity of the system is sufficient to warrant less. All tanks
shall be controlled to provide an adequate turn-over of at least twenty percent
(20%) of the total volume each twenty-four (24) hour period. The BPH may allow
a variance to the minimum twenty percent (20%) turn-over requirement, if
adequate justification is provided such as no distribution water quality
violations, booster chlorination, etc. This may require a main line altitude
valve or externally controlled valves.
9.4.a.
Pressures. -- The maximum variation between high and low levels in standpipes
or elevated storage structures providing pressure to a distribution system
shall not exceed thirty (30) feet (thirteen (13) pounds per square inch). The
minimum pressure in the distribution system shall be thirty (30) pounds per
square inch under static conditions and twenty (20) pounds per square inch
under all flow conditions. The normal working pressures of the distribution
mains shall be designed based upon the pipe manufacturer's recommendations and
the applicable AWWA standards for the type of pipe. Pressure
regulating/pressure reducing valves shall be used to protect the distribution
mains from excessive pressures. When static pressures in the distribution mains
exceed one hundred thirty five (135) pounds per square inch, the utility shall
have the option of installing pressure reducing valves on service lines or
requiring (or recommending) the customer install and maintain a pressure
reducing valve on the customer's service line.
9.4.b. Drainage. -- Storage structures that
provide pressure directly to the distribution system shall be designed so they
can be isolated from the distribution system and drained for cleaning or
maintenance without necessitating loss of pressure in the distribution system.
The drain shall discharge to the ground surface with no direct connection to a
sewer or storm drain.
9.4.c. Level
controls. -- Commercially available control systems shall be provided to
maintain levels in distribution system storage structures for community and
non-community, non-transient public water systems. Level indicating devices
shall be provided at a central location. Pumps shall be controlled from tank
levels with the signal transmitted by telemetering equipment when any
appreciable head loss occurs in the distribution system between the source and
the storage structure. Altitude valves or equivalent controls may be required
for additional structures on the system. Overflow and low-level warnings or
alarms shall be located at places in the community where they are under
responsible surveillance twenty-four (24) hours a day.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.