Wis. Admin. Code Public Service Commission § PSC 135.181 - Distribution line valves addition [49 CFR 192.181]
Current through March 28, 2022
After 49 CFR 192.181(b), insert:
(bw) The distance between the valve and the
regulator or regulators shall be sufficient to permit the operation of the
valve during an emergency such as a large gas leak or a fire in the station.
These valves shall be in accessible locations neither closer than 25 feet nor
more than 1,500 feet distant from each regulator station.