Wis. Admin. Code Public Service Commission § PSC 135.747 - Valve maintenance: distribution systems addition [49 CFR 192.747]
Current through March 28, 2022
After the text in 49 CFR 192.747(a), insert:
(1w) Inspection shall include checking of
alignment to permit use of a key or wrench and clearing from the valve box or
vault any debris which would interfere or delay the operation of the valve.
Records shall be maintained to show specific valve location and the records
shall be made continuously accessible to authorized personnel for use under
emergency conditions.
(2w) Existing
connections in the form of inline valves between low pressure gas distribution
systems and high pressure gas distribution systems shall be physically severed
by January 1, 1974.
(3w) The
by-pass valves in district regulator stations supplying gas to a low pressure
distribution system shall be sealed, locked or otherwise be rendered incapable
of operation, except by authorized personnel.