46 CFR 169.672 - Wiring for power and lighting circuits.

§ 169.672 Wiring for power and lighting circuits.

(a) Wiring for power and lighting circuits must have copper conductors, of 14 AWG or larger, and -

(1) Meet Article 310-8 and Table 310-13 of the National Electrical Code;

(2) Be listed as “50 volt boat cable”; or

(3) Meet subpart 111.60 of this chapter.

(b) Wiring for power and lighting circuits on new vessels must have stranded conductors.

(c) Conductors must be sized so that -

(1) They are adequate for the loads carried; and

(2) The voltage drop at the load terminals is not more than 10 percent.

This is a list of United States Code sections, Statutes at Large, Public Laws, and Presidential Documents, which provide rulemaking authority for this CFR Part.

This list is taken from the Parallel Table of Authorities and Rules provided by GPO [Government Printing Office].

It is not guaranteed to be accurate or up-to-date, though we do refresh the database weekly. More limitations on accuracy are described at the GPO site.


United States Code
U.S. Code: Title 33 - NAVIGATION AND NAVIGABLE WATERS
U.S. Code: Title 46 - SHIPPING
Statutes at Large

Title 46 published on 09-May-2017 04:27

The following are ALL rules, proposed rules, and notices (chronologically) published in the Federal Register relating to 46 CFR Part 169 after this date.

  • 2016-07-22; vol. 81 # 141 - Friday, July 22, 2016
    1. 81 FR 48220 - Harmonization of Standards for Fire Protection, Detection, and Extinguishing Equipment
      GPO FDSys XML | Text
      DEPARTMENT OF HOMELAND SECURITY, Coast Guard
      Final rule.
      This final rule is effective August 22, 2016. The incorporation by reference of certain publications listed in the rule is approved by the Director of the Federal Register on August 22, 2016.
      33 CFR Parts 140, 145, 148, and 149
The section you are viewing is cited by the following CFR sections.