(a) Unless the
department has approved a lesser minimum separation distance, a person who
installs, modifies, or operates a source of drinking water associated with a
private water system must meet the following minimum separation distances to a
potential source of contamination:
(1) at
least 100 horizontal feet, measured nearest edge to nearest edge, to a
wastewater treatment works, sewer line, sewer line cleanout, manhole, lift
station, septic tank, wastewater holding tank, soil absorption system, disposal
system, disposal sewer, pit privy, sanitary landfill, or other potential source
of contamination such as animal byproducts, manure or waste, agricultural
waste, sewage solids disposal sites, or biosolids storage areas;
(2) at least 25 horizontal feet, measured
nearest edge to nearest edge, to a private sewer line, sewer service line, or
sump contained within a building;
(3) at least 25 horizontal feet, measured
nearest edge to nearest edge, to a land surface discharge or subsurface
disposal area associated with drinking water treatment waste; in this
paragraph, "drinking water treatment waste" includes reject water from reverse
osmosis units and backwash water from filters and water softeners;
and
(4) at least 25 horizontal
feet, measured nearest edge to nearest edge, to a fuel storage tank or line;
the minimum separation distance to a fuel storage tank or line does not apply
to
(A) a tank or line that contains propane
or natural gas; or
(B) an
above-ground storage tank or drum that, in the aggregate, has a storage
capacity equal to or less than 500 gallons of petroleum
products.
(b)
Unless the department has approved a lesser separation distance, a person who
installs, modifies, or operates a water holding tank associated with a private
water system or a private water line must meet the following minimum separation
distances to potential sources of contamination:
(1) at least 10 horizontal feet, measured
nearest edge to nearest edge, to a fuel storage tank or line; the minimum
separation distance for a fuel storage tank or line does not apply to
(A) a tank or line that contains propane or
natural gas; or
(B) an above-ground
storage tank or drum that, in the aggregate, has a storage capacity of equal to
or less than 500 gallons of petroleum products;
(2) at least five horizontal feet, measured
nearest edge to nearest edge, to a septic tank, treatment tank, holding tank,
lift station, community sewer line, land surface discharge, or subsurface
disposal area;
(3) at least 12
horizontal inches, measured nearest edge to nearest edge, to a private sewer
line;
(4) at locations where a
private water line must cross a private or community sewer line,
(A) at least 12 vertical inches, measured
nearest edge to nearest edge, with the private or community sewer line located
below the private water line; and
(B) at least nine feet, measured nearest edge
to nearest edge, from the private water line joints to the private or community
sewer line joints.
(c) A person who drills, installs, modifies,
or operates a well serving a private water system must use a method equivalent
to well protection or source water protection contained in 18 AAC 80 or the
publicly identified approved best management practice as protective of a public
water systems.
(d) A person who
owns or is responsible for a well shall maintain it in accordance with
18 AAC 80.015(d)
or decommission it in accordance with
18 AAC