Ariz. Admin. Code § R18-12-211 - Installation Requirements for Partially Excluded UST Systems
A. Owners and
operators installing an UST system listed in
R18-12-210(C)(1),
(3), or (4) storing regulated substances,
whether of single-wall or double-wall construction, shall ensure that it meets
all of the following requirements:
1. The UST
system will prevent releases due to corrosion or structural failure for the
operational life of the UST system;
2. The UST system is cathodically protected
against corrosion, constructed of non-corrodible material, steel clad with a
non-corrodible material, or designed in a manner to prevent the release or
threatened release of any stored substance;
3. The UST system is constructed or lined
with material that is compatible with the stored substance.
B. Notwithstanding subsection (A),
an UST system without corrosion protection may be installed at a site that is
determined by a corrosion expert not to be corrosive enough to cause it to have
a release due to corrosion during its operational life. Owners and operators
shall maintain records that demonstrate compliance with the requirements of
this subsection for the remaining operational life of the UST system.
C. Compliance with the corrosion protection
provisions of this Section shall be determined in accordance with the codes of
practice set forth in
R18-12-281(A).