Ariz. Admin. Code § R18-2-C1302 - Limits on SO[2] Emissions from the Miami Smelter
A. Applicability.
1. This Section applies to the owner or
operator of the Miami Smelter It establishes limits on
SO2 emissions from the Miami Smelter and monitoring,
recordkeeping and reporting requirements for those limits.
2. Effective date. Except as otherwise
provided, the provisions of this Section shall take effect on the later of the
effective date of the Administrator's action approving it as part of the state
implementation plan or January 1, 2018.
B. Definitions. In addition to general
definitions contained in
R18-2-101, the following
definitions apply to this rule.
1. "Capture
system" means the collection of components used to capture gases and fumes
released from one or more emission points, and to convey the captured gases and
fumes to one or more control devices. A capture system may include, but is not
limited to, the following components as applicable to a given capture system
design: duct intake devices, hoods, enclosures, ductwork, dampers, manifolds,
plenums, and fans.
2. "Electric
furnace" means a furnace in which copper matte and slag are heated by
electrical resistance without the mechanical introduction of air or
oxygen.
3.
"IsaSmelt® furnace" means a furnace in which
air, oxygen, and fuel are injected through a top-submerged lance into a molten
slag bath to produce slag and copper matte.
4. "Miami Smelter" means the primary copper
smelter located near Miami, Gila County, Arizona at latitude 33º24'50"N
and longitude 110º51'25"W.
5.
"Out of control period" means the time that begins with the completion of the
fifth, consecutive, daily calibration drift check with a calibration drift in
excess of two times the allowable limit, or the time corresponding to the
completion of the daily calibration drift check preceding the daily calibration
drift check that results in a calibration drift in excess of four times the
allowable limit, and the time that ends with the completion of the calibration
check following corrective action that results in the calibration drifts at
both the zero (or low-level) and high-level measurement points being within the
corresponding allowable calibration drift limit.
6. "Operating day" means any calendar day in
which any of the following occurs:
a.
Concentrate is smelted in th e Electric furnace or
IsaSmelt® furnace;
b. Copper or sulfur bearing materials are
processed in the converters
c.
Blister or scrap copper is processed in the anode furnaces or mold ;
vessel;
d. Molten metal, including
slag, matte or blister copper, is transferred between vessels;
e. Molten metal is cast into molds, anodes,
or other intermediate or final products
f Power is provided to the electric furnace
to make or maintain a molten bath; or
g The anode furnace is heated to make or maintain a molten
bath.
C. Sulfu
g. Dioxide Emission Limitations. Combined SO2 emissions
from the tail gas stack, vent fume stack, aisle scrubber stack, bypass stack,
and smelter roofline fugitives shall not exceed 142.45 pounds per hour on a
30-day rolling average basis.
D.
Operational Standards.
1. Process Equipment
and control device operations. At all times, including periods of startup,
shutdown, and malfunction, the owner or operator shall, to the extent
practicable, maintain and operate smelter processes and associated emission
control devices in a manner consistent with good air pollution control
practices for minimizmg SO2 emissions from the process
gases associated with the IsaSmelt® furnace
electric furnace, and converters at least to the levels required by subsection
(C). Determination of whether acceptable operating and maintenance procedures
are being used will be based on information available to the Director and EPA
Region IX, which may include, but is not limited to, monitoring results, review
of operating and maintenance procedures and records, and inspection of the
relevant equipment.
2. Capture
system and control device operations and maintenance plan. The owner or
operator shall develop and implement an operations and maintenance plan for
each capture system and control device used to ventilate or control process gas
or emissions associated with the IsaSmelt®
furnace, electric furnace, and converters. The owner or operator shall submit
the initial plan to the Department and EPA Region IX for review and approval by
July 1, 2017.
a. The operations and
maintenance plan must address the following requirements as applicable to each
capture system and control device:
i.
Monitoring devices. The plan shall provide for installation, operation,
calibration, and maintenance of appropriate monitoring devices to measure and
record operating limit or range values at all times the required system is
operating. Dampers that are manually set and remain in the same position while
the capture system is operating are exempt from these monitoring requirements.
ii. Operational limits and ranges.
The owner or operator shall establish operating limits and ranges in the plan
for each capture system and control device that are representative and reliable
indicators of capture system performance and control device operation. If
selected as an operational limit or range, capture system damper position
settings shall be specified in the plan.
iii. Preventative maintenance. The owner or operator must perform
preventative maintenance for each capture system and control device according
to written procedures in the plan. The procedures must include a preventative
maintenance schedule that is consistent with the manufacturer's or engineer's
instructions and specified frequency for routine and long-term
maintenance.
iv. Inspections. The
owner or operator must perform inspections in accordance with written
procedures in the plan for each capture system and control device, including
position verification of any manual damper settings specified in the plan, that
are consistent with the manufacturer's or engineer's instructions for each
system and device
b. The
owner or operator shall operate and maintain each capture system and each
control device in accordance with the plan required by subsection (D)(2) and as
approved by the Department and EPA Region IX, except as provided herein. Until
receiving initial approval of the plan, the owner or operator shall operate and
maintain each capture system and each control device in accordance with the
plan as initially submitted pursuant to subsection (D)(2). The owner or
operator shall submit plan revisions for review by the Department and EPA
Region IX. At any time, the Department and/or EPA Region IX may require the
owner or operator to revise the plan if determined to be inconsistent with
subsection (D)(2a). Within 60 days of receiving written notification from the
Department or EPA Region IX specifying such inconsistency)( the owner or
operator shall submit a proposal to the Department and EPA Region IX that
addresses the inconsistency. The owner or operator shall maintain a current
copy of the plan onsite and available for review and inspection upon request.
E.
Monitoring.
1. To determine compliance with
subsection (C), the owner or operator shall install, calibrate, maintain, and
operate contuous monitoring systems to monitor and record
SO2 concentrations and stack gas volumetric flow rates
at the following locations.
a. The acid plant
tail gas stack;
b. The vent fume
stack;
c. The aisle scrubber
stack; and
d. The bypass
stack.
2. To determine
compliance with the emission limit in subsection (C), the owner or operator
shall install, calibrate, maintain, and operate a continuous monitoring system
to monitor and record fugitive SO2 a concentrations at
the Miami Smelter roofline.
3.
Except during periods of continuous monitoring system breakdown, repairs,
maintenance, out-of-control periods, calibration checks, and zero and span
adjustments, the owner or operator shall continuously monitor
SO2 concentrations and stack gas volumetric flow rates
at each location specified in subsection (E)(1) and use the monitored
concentrations and volumetric flow rates when demonstrating compliance with the
SO2 or emission limit in subsection (C) in accordance
with subsection (F).
4. Except
during periods of continuous monitoring system breakdown, repairs, maintenance,
out-of-control periods, calibration checks and zero and span adjustments, the
owner or operator shall continuously monitor fugitive
SO2 emissions at the Miami Smelter roofline and use the
monitored concentrations and volumetric flow rates when demonstrating
compliance with the SO2 emission limit in subsection (C)
in accordance with subsection (F).
5. For purposes of subsections (E)(3) and
(E)(4), continuous monitoring means the taking and recording of at least one
measurement of SO2 concentration and stack gas flow rate
reading from the effluent of each affected stack, outlet, or other approved
measurement location in each 15-minute period when the associated process units
are operating. Fifteen-minute periods start at beginning of each clock hour,
and run consecutively. All continuous monitoring systems required by subsection
(E)(1) shall complete at least one cycle of operation (sampling, analyzing, and
data recording) for each successive 15-minute period.
6. If the owner or operator can demonstrate
to the Director and EPA Region IX that measurement of stack gas volumetric flow
rate in the outlet of any particular piece of SO2
control equipment would yield inaccurate results or would be technologically
infeasible, then the Director and EPA Region IX may allow measurement of the
flow rate at an alternative sampling point.
7. The owner or operator shall demonstrate
that the continuous monitoring systems required by subsection (E)(1) meet all
of the following requirements:
a. Each
SO2 continuous monitoring system shall meet the
specifications under 40 CFR 60, Appendix B, Performance Specification
6.
b. Each
SO2 continuous monitoring system installed and operated
under this Section shall also meet the quality assurance requirements of 40 CFR
60, Appendix F, Procedure 1.
c. The
owner or operator shall notify the Director in writing at least 30 days in
advance of the start of the relative accuracy test audit (RATA) procedures
performed on each continuous monitoring system.
d. The Director shall approve the location of
all sampling points for monitoring SO2 concentrations
and stack gas volumetric flow rates in writing before installation and
operation of measurement instruments.
e. The span of each continuous monitoring
system for the acid plant tail stack, vent fume stack, and aisle scrubber stack
shall be set at a SO2 concentration of zero to 0.20
percent by volume.
f. The span of
the continuous monitoring system for the bypass stack shall be set at a
SO2 concentration of zero to 20 percent by
volume.
g. The zero (or low-level
value between 0 and 20 percent of the span value) and span (50 to 100 percent
of span value) calibration drifts shall be checked at least once each operating
day in accordance with a written procedure. The zero and span must, at a
minimum, be adjusted whenever either the 24-hour zero drift or the 24-hour span
drift exceeds two times the limit in 40 CFR Part 60, Appendix B, Performance
Specification 2. The system must allow the amount of the excess zero and span
drift to be recorded and quantified.
h. The owner or operator shall maintain on
hand and ready for immediate installation sufficient spare parts or duplicate
systems for the continuous monitoring system equipment required by this Section
to allow for the replacement within six hours of any monitoring system
equipment part that fails or malfunctions during operation.
8. The owner or operator
shall develop and implement a roofline fugitive emissions monitoring plan for
the continuous monitoring system required by subsection (E)(2). The owner or
operator shall submit the initial plan to the Department and EPA Region IX for
review and approval by July 1, 2017.
a. The
roofline fugitive emissions monitoring plan must address the following
requirements:
i. The continuous monitoring
system required by subsection (E)(2) must include measurement of fugitive
emissions from, at a minimum, the Converter, Electric Furnace, Anode Furnace,
and IsaSmelt® systems that is representative of
total fugitive emissions.
ii. Each
measurement system shall include at least one SO2
analyzer and sufficient sampling locations that ensure collection of a
representative sample along the roof monitor for each monitor system. The
number of sample probes and their locations for each monitoring system shall
account for the physical configuration of the vent, the locations of emitting
activities relative to the vent, and heat generated by the equipment served by
the vent.
iii. Each measurement
system shall include validation of adequate velocity for flow measurements and
sufficient flow and temperature sensors to ensure calculation of representative
exhaust flows through each vent. The number of such sensors and their locations
for each monitoring system shall account for the physical configuration of the
vent, the locations of emitting activities relative to the vent, and heat
generated by the equipment served by the vent.
iv. Each measurement system shall include an
on-site data collection system that continuously logs and stores the measured
SO2 concentration, the measured flow velocity, and the
measured temperature.
v. An
appropriate range for zero-span drift shall be established for all
SO2 analyzers to ensure proper calibration and
operation. Unless otherwise provided in the roofline fugitive emissions
monitoring plan required by subsection (E)(8), the zero (or low-level) value
determination shall be made using a gas containing between zero to 20 percent
of the span value for SO2 and the span (or high-level)
value determination shall be made using a certified gas with a value between 50
and 100 percent of the span value for SO2. For each
SO2 analyzer, a daily zero-span check shall be performed
by introducing zero gas and a known concentration of span gas to the analyzer.
If the zero or span drift for an analyzer is greater than five percent of the
span gas concentration for five consecutive days or greater than 10 percent of
the span gas concentration for one day, the analyzer shall be found to be
operating improperly and appropriate measures shall be taken to return the
analyzer to proper operation. The zero-span check shall be repeated after any
such corrective action is taken.
vi. All SO2 analyzers
shall be inspected quarterly by the owner or operator and inspected annually by
an independent auditor. The inspections shall be conducted in accordance with
the data accuracy assessment requirements of 40 CFR 60, Appendix F, Procedure
1,Section 5 or as otherwise provided in the roofline fugitive emissions
monitoring plan required by subsection (E)(8). The quarterly inspections
consist of two certified concentrations of SO2 to each
sample probe system and comparing the known concentrations to the
concentrations logged by the corresponding on-site data collection system to
generate a relative error for each system.
vii. The flow and temperature data shall be
checked daily for proper operation of flow and temperature sensors in
accordance with the roofline fugitive emissions monitoring plan required by
subsection (E)(8). If a flow or temperature sensor is found to be operating
improperly, appropriate measures shall be taken to return the sensor to proper
operation.
viii. All temperature
sensors shall be inspected annually. The inspection shall be conducted
according to the manufacturer's specification. A temperature sensor tolerance
range representative of proper sensor operation shall be established in the
roofline fugitive emissions monitoring plan required by subsection (E)(8). If a
temperature sensor is found to measure outside of an established tolerance
range, the sensor shall be found to be operating improperly and appropriate
measures shall be taken to return the sensor to proper operation.
ix. All flow sensors shall be calibrated
semi-annually with calibration tools according to the manufacturer's
specifications. A calibration tool range representative of proper sensor
operation shall be established in the roofline fugitive emissions monitoring
plan required by subsection (E)(8). If a flow sensor is found to measure
outside of an established range, the sensor shall be found to be operating
improperly and appropriate measures shall be taken to return the sensor to
proper operation.
b. The
owner or operator shall operate and maintain the continuous monitoring system
required by subsection (E)(2) in accordance with the roofline fugitive
emissions monitoring plan required by subsection (E)(2) and as approved by the
Department and EPA Region IX, except as provided herein. Until receiving
initial approval of the plan, the owner or operator shall operate and maintain
the continuous monitoring system required by subsection (E)(2) in accordance
with the plan as initially submitted pursuant to subsection (E)(2). The owner
or operator shall keep the plan current and consistent with subsection
(E)(8)(a). The owner or operator shall maintain a current copy of the plan
onsite and available for review and inspection upon request. The Department
and/or EPA Region IX may require the owner or operator to revise the plan if
determined to be inconsistent with subsection (E)(8)(a). Within 60 days of
receiving written notification from the Department or EPA Region IX specifying
such inconsistency, the owner or operator shall submit a proposal to the
Department and EPA Region IX that addresses the
inconsistency.
F. Compliance Demonstration Requirements.
1. Within 180 days of the effective date set
forth in subsection (A)(2), the owner or operator shall demonstrate compliance
with the emission limit in subsection (C) by calculating
SO2 emissions for each operating day as follows:
a. Sum the hourly pounds of
SO2 measured by the continuous monitoring systems
required by subsection (E)(1) and (E)(2) for the current operating day and the
preceding 29 operating days to calculate the total pounds of
SO2 emissions over the 30-operating day averaging
period.
b. Multiply the operating
days occurring during a 30-day averaging period by 24 to calculate the total
operating hours over the most recent 30-operating day period.
c. Divide the total amount of
SO2 emissions calculated from subsection (F)(1)(a) by
the total operating hours calculated from subsection (F)(1)(b) to calculate the
30-day rolling hourly average SO2 emissions.
2. For the continuous monitoring
systems required by subsections (E)(1) and (E)(2), hourly emissions shall be
computed as follows:
a. Except as provided
under subsection (F)(2)(c), for a full operating hour (any clock hour with 60
minutes of unit operation), at least four valid data points are required to
calculate the hourly average, i.e., one data point in each of the 15-minute
quadrants of the hour.
b. Except as
provided under subsection (F)(2)(c), for a partial operating hour (any clock
hour with less than 60 minutes of unit operation), at least one valid data
point in each 15-minute quadrant of the hour in which the unit operates is
required to calculate the hourly average.
c. For any operating hour in which required
maintenance or quality-assurance activities are performed:
i. If the unit operates in two or more
quadrants of the hour, a minimum of two valid data points, separated by at
least 15 minutes, is required to calculate the hourly average; or
ii. If the unit operates in only one quadrant
of the hour, at least one valid data point is required to calculate the hourly
average.
d. If a daily
calibration error check is failed during any operating hour, all data for that
hour shall be invalidated, unless a subsequent calibration error test is passed
in the same hour and the requirements of subsection (F)(2)(c) are met, based
solely on valid data recorded after the successful calibration.
e. For each full or partial operating hour,
all valid data points shall be used to calculate the hourly average.
f. Data recorded during periods of continuous
monitoring system breakdown, repair, maintenance, out of control periods,
calibration checks, and zero and span adjustments shall not be included in the
data averages computed under subsection (F)(3).
g. Either arithmetic or integrated averaging
of all data may be used to calculate the hourly average. The data may be
recorded in reduced or non-reduced form.
3. When no valid hour or hours of data have
been recorded by a continuous monitoring system required by subsections (E)(1)
and (E)(2) and the associated process unit is operating, the owner or operator
shall calculate substitute data for each such period according to the following
procedures:
a. For a missing data period less
than or equal to 24 hours, substitute the average of the hourly
SO2 concentrations recorded by the system for the hour
before and the hour after the missing data period.
b. For a missing data period greater than 24
hours, substitute the greater of:
i. The 90th
percentile hourly SO2 concentrations recorded by the
system during the previous 720 quality-assured monitor operating hours;
or
ii. The average of the hourly
SO2 concentrations recorded by the system for the hour
before and the hour after the missing data period.
4. The owner or operator shall
include periods of startup, shutdown, malfunction, or other upset conditions
when determining compliance with the emission limit in subsection
(C).
G. Recordkeeping.
1. The owner or operator shall maintain
records as specified in the capture system and control device operations and
maintenance plan required under subsection (D)(2) and the roofline fugitive
emissions monitoring plan required under subsection (E)(8).
2. The owner or operator shall maintain the
following records for at least five years:
a.
All measurements from the continuous monitoring systems required by subsection
(E)(1) and (E)(2); including the date, place, and time of sampling or
measurement, parameters sampled or measured, and results.
b. All records of all compliance calculations
required by subsection (F).
c. All
records of quality assurance and quality control activities conducted on the
continuous monitoring systems required by subsection (E)(1) and
(E)(2).
d. All records of
continuous monitoring system breakdowns, repairs, maintenance, out of control
periods, calibration checks, and zero and span adjustments for the continuous
monitoring systems required by subsection (E)(1) and (E)(2).
e. All records of the occurrence and duration
of any startup, shutdown, or malfunction in the operation of Smelter processes;
any malfunction of the associated air pollution control equipment; or any
periods during which a continuous monitoring system or monitoring device
required by subsection (E)(1) and (E)(2) is inoperative.
f. All records of all major maintenance
activities conducted on emission units, capture system, air pollution control
equipment, and continuous monitoring systems; including those set forth in the
operations and maintenance plan required by subsection (D)(2).
g. All records of reports and notifications
required by subsection (H).
H. Reporting
1. Within 30 days after the end of each
calendar quarter, the owner or operator shall submit a data assessment report
to the Director in accordance with 40 CFR Part 60, Appendix F, Procedure 1 for
the continuous monitoring systems required by subsection (E).
2. The owner or operator shall submit an
excess emissions and monitoring systems performance report and-or summary
report form in accordance with
40 CFR §
60.7(c) to the Director
semiannually for the continuous monitoring systems required by subsection
(E)(1) and (E)(2). All reports shall be postmarked by the 30th day following
the end of each six-month period.
3. The owner or operator shall provide the
following to the Director:
a. Notification of
commencement of construction of the project improvements and equipment
authorized by Significant Permit Revision No. 53592 to comply with the
operational or emission limits in this Section no later than 30 days after such
date.
b. Semiannual progress
reports on construction of any such improvements and equipment on January 1 and
July 1 of each calendar year until construction is complete.
c. Notification of initial startup of any
such improvements and equipment within 15 days after such date.
I. Preconstruction
review. This Section is determined to be Reasonably Available Control
Technology (RACT) for SO2 emissions from the operations
subject to subsection (C) for purposes of minor source NSR requirements
addressed in
R18-2-334.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.