Ariz. Admin. Code § R18-4-215 - Backflow Prevention
A. A public
water system shall protect its system from contamination caused by backflow
through unprotected cross-connections by requiring the installation and
periodic testing of backflow-prevention assemblies. Required
backflow-prevention assemblies shall be installed as close as practicable to
the service connection.
B. A public
water system shall ensure that a backflow-prevention assembly is installed
whenever any of the following occur:
1. A
substance harmful to human health is handled in a manner that could permit its
entry into the public water system. These substances include chemicals,
chemical or biological process waters, water from public water supplies that
has deteriorated in sanitary quality, and water that has entered a fire
sprinkler system. A Class 1 or Class 2 fire sprinkler system is exempt from the
requirements of this Section;
2. A
source of water supply exists on the user's premises that is not accepted as an
additional source by the public water system or is not approved by the
Department;
3. An unprotected
cross-connection exists or a cross-connection problem has previously occurred
within a user's premises; or
4.
There is a significant possibility that a cross-connection problem will occur
and entry to the premises is restricted to the extent that cross-connection
inspections cannot be made with sufficient frequency or on sufficiently short
notice to ensure that unprotected cross-connections do not exist.
C. Unless a cross-connection
problem is specifically identified, or as otherwise provided in this Section,
the requirements of this Section shall not apply to single-family residences
used solely for residential purposes.
D. A backflow-prevention assembly required by
this Section shall comply with the following:
1. If equipped with test cocks, it shall have
been issued a certificate of approval by:
a.
The University of Southern California Foundation for Cross-Connection Control
and Hydraulic Research (USC-FCCCHR), or
b. A third-party certifying entity that is
unrelated to the product's manufacturer or vendor, and is approved by the
Department.
2. If not
equipped with test cocks, it shall be approved by a third-party certifying
entity that is unrelated to the product's manufacturer or vendor and is
approved by the Department.
E. The minimum level of backflow protection
that is provided to protect a public water system shall be the level
recommended in Section 7.2 of the Manual of Cross-Connection Control, Ninth
Edition, USC-FCCCHR, KAP-200 University Park MC-2531, Los Angeles, CA,
90089-2531, December 1993, (and no future editions or amendments), incorporated
by reference and on file with the Department. The types of backflow prevention
that may be required, listed in decreasing order according to the level of
protection they provide, include: an air-gap separation (AG), a reduced
pressure principle backflow prevention (RP) assembly, a pressure vacuum breaker
(PVB) assembly, and a double check valve (DC) assembly. Nothing contained in
this Section shall prevent a public water system from requiring the use of a
higher level of protection than the level required by this subsection.
1. A public water system may make
installation of a required backflow-prevention assembly a condition of service.
A user's failure to comply with this requirement shall be sufficient cause for
the public water system to terminate water service.
2. Specific installation requirements for
backflow prevention include the following:
a.
Any backflow prevention required by this Section shall be installed in
accordance with the manufacturer's specifications.
b. For an AG installation, all piping between
the user's connection and the receiving tank shall be entirely visible unless
otherwise approved in writing by the public water system.
c. An RP assembly shall not be installed in a
meter box, pit, or vault unless adequate drainage is provided.
d. A PVB assembly may be installed for use on
a landscape water irrigation system if the irrigation system conforms to all of
the criteria listed below. An RP assembly is required whenever any of the
criteria are not met.
i. The water use beyond
the assembly is for irrigation purposes only;
ii. The PVB is installed in accordance with
the manufacturer's specifications;
iii. The irrigation system is designed and
constructed to be incapable of inducing backpressure; and
iv. The injection of chemical pesticides and
fertilizers, chemigation, is not used or provided in the irrigation
system.
F. Each backflow-prevention assembly required
by this Section shall be tested at least annually, or more frequently if
directed by the public water system or the Department. Each assembly shall also
be tested after installation, relocation, or repair. An assembly shall not be
placed in service unless it has been tested and is functioning as designed. The
following provisions shall apply to the testing of backflow-prevention
assemblies:
1. Testing shall be in accordance
with procedures described in Section 9 of the Manual of Cross-Connection
Control. The public water system shall notify the water user when testing of
backflow-prevention assemblies is needed. The notice shall specify the date by
which the testing must be completed and the results forwarded to the public
water system.
2. Testing shall be
performed by a person who is currently certified as a "general" tester by the
California-Nevada Section of the American Water Works Association (CA-NV
Section, AWWA), the Arizona State Environmental Technical Training (ASETT)
Center, or other certifying authority approved by the Department.
3. When a backflow-prevention assembly is
tested and found to be defective, it shall be repaired or replaced in
accordance with the provisions of this Section.
G. A public water system shall maintain
records of backflow-prevention assembly installations and tests performed on
backflow-prevention assemblies in its service area. Records shall be retained
by the public water system for at least three years and shall be made available
for review by the Department upon request. These records shall include an
inventory of backflow-prevention assemblies required by this Section and, for
each assembly, all of the following information:
1. Assembly identification number and
description,
2. Location,
3. Date of tests,
4. Description of repairs and recommendations
for repairs made by the tester, and
5. The tester's name and certificate
number.
H. A public
water system shall submit a written cross-connection incident report to the
Department and the local health authority within five business days after a
cross-connection problem occurs that results in contamination of the public
water system. The report shall address all of the following:
1. Date and time of discovery of the
unprotected cross-connection,
2.
Nature of the cross-connection problem,
3. Affected area,
4. Cause of the cross-connection
problem,
5. Public health
impact,
6. Date and text of any
public health advisory issued,
7.
Each corrective action taken, and
8. Date of completion of each corrective
action.
I. An individual
with direct responsibility for implementing a backflow prevention program for a
water system serving more than 50,000 persons, or an individual with direct
responsibility for implementing a backflow prevention program for a for a water
system serving 50,000 or fewer persons if the Department has determined that
such a need exists, shall be licensed as a "cross-connection control program
specialist" by the CA-NV Section, AWWA, the ASETT Center, or another certifying
authority approved by the Department.