Ariz. Admin. Code § R20-5-412 - Automatic Low-water Fuel Cutoff Devices or Combined Water Feeding and Fuel Cutoff Devices
A. An
Owner, Operator, or User shall ensure that low-water fuel cutoff devices or
combined water feeding and fuel cutoff devices do not interfere with an
Operator's or Authorized Inspector's ability to safely clean, repair, or
inspect a Boiler, Lined Hot Water Heater, or Pressure Vessel.
B. A low-water fuel cutoff device shall have
a pressure rating not less than the set pressure of the Safety Valve or Safety
Relief Valve.
C. In addition to the
requirements of subsections (A) and (B), all low-water fuel cutoffs and flow
sensing devices shall be constructed and installed in accordance with
applicable ASME Code and standards for Boilers and Direct Fired Jacketed Steam
Kettle in R20-5-404(A).