Ariz. Admin. Code § R20-5-413 - Safety and Safety Relief Valves
A. A valve shall not be placed between a
Safety Valve, Relief Valve, or a Safety Relief Valve and the Boiler, Lined Hot
Water Heater, or Pressure Vessel, or between a Safety Valve, Relief Valve, or a
Safety Relief Valve and the discharge pipe attached to the Boiler, Lined Hot
Water Heater, or Pressure Vessel.
B. When a Power Boiler is supplied with
feed-water directly from a water main without the use of a feeding apparatus,
Safety Valves shall not be set at a pressure greater than 94% of the lowest
pressure obtained in the water main feeding the Boiler;
C. Safety Valves, Safety Relief Valves, and
Relief Valves shall conform to the requirements of the 2019 ASME Boiler and
Pressure Vessel Code, Section I, IV or VIII, July, incorporated by reference
as applicable. This incorporation does not include any later amendments or
editions of the incorporated material. A copy of this referenced material is
available for review at the Industrial Commission of Arizona, 800 W. Washington
Street, Phoenix, AZ and may be obtained from ASME, Three Park Avenue, New York,
NY 10016-5990 or at http://www.asme.org/.
D. The resetting, repairing, and restamping
of Safety Valves, Relief Valves, and Safety Relief Valves shall be done by a
qualified valve repair organization holding a valid "VR" Certificate of
Authorization issued by the National Board of Boiler and Pressure Vessel
Inspectors. ASME valve manufacturers holding a valid "V," "HV," and "UV"
Certificate or Certificates of Authorization may also do this work provided
they also have a valid "VR" Certificate of Authorization issued by the National
Board of Boiler and Pressure Vessel Inspectors.
E. With jurisdictional approval, Owner,
Operators, and Users of Boilers, Lined Hot Water Heaters, and Pressure Vessels
may authorize external adjustments to bring installed Safety Valves, Relief
Valves, and Safety Relief Valves back to the stamped set pressure when
performed by the Owner's, Operator's, or User's trained, qualified, regular,
and full-time employees. Refer to Supplement 7.10 of the National Board
Inspection Code for guidelines regarding training, documentation, and the
implementation of a quality system for the Owner, Operator, or User employees.
All such external adjustments shall be resealed with a metal tag showing the
identification of the organization making the adjustments and the date. If any
valve repairs are required, they shall be done by a qualified "VR" certificate
holder.