Ariz. Admin. Code § R4-30-302 - Electrical Plans
A. A
registrant shall prepare and submit drawings and specifications for a new
electrical system or an addition or modification to an existing electrical
system provided the service and associated electrical feeders exceeds 600
amperes 120/240 volts, single phase or 225 amperes 120/208 volts, three phase
and the fault current exceeds 10,000 amperes.
B. In all cases a registrant shall design:
1. Electrical installations in hospitals or
other buildings with surgical operating rooms regulated by Article 517 of the
National Electrical code (1990 edition) incorporated herein by reference and on
file with the Office of the Secretary of State.
2. Electrical installations in locations
classified as hazardous in Article 500 of the National Electrical Code (1990
edition) incorporated herein by reference and on file with the Office of the
Secretary of State.
3. Electrical
installations in locations classified as hazardous in Article 500 of the
National Electrical Code (1990 edition) with the exception of gasoline
dispensing or repair garages.
4. A
registrant shall design an alarm or signaling system that is required for life
safety or code compliance.