Ariz. Admin. Code § R7-6-212 - Classroom Lighting

A. Each general, science, and art classroom shall have a light system capable of maintaining at least:

1. Fifty foot-candles of light if the light is provided by incandescent, halogen, or fluorescent bulbs; or
2. Thirty foot-candles of light if the light is provided by LED (light emitting diode) bulbs;

B. The light level shall be measured at a work surface located in the approximate center of the classroom, between clean light fixtures under normal operating conditions.

C. A random sample of 10 percent of the general, science, and art classrooms in each building shall be measured to determine the classroom light level for the school facility.

D. For purposes of this Section, all portable or modular buildings located at a school facility that were manufactured in the same year and installed at the school facility at the same time are considered a single building.

Notes

Ariz. Admin. Code § R7-6-212
New Section made by exempt rulemaking at 8 A.A.R. 287, effective June 7, 2001 (Supp. 01-4). Amended by final expedited rulemaking at 26 A.A.R. 2963, effective 11/3/2020.