7 Del. Admin. Code § 3100-9.0 - Minimum Required Equipment for Vessels Using State Waters (Formerly BR-9)
(Penalty Section 23Del.C.§ 2125)
9.1 General.
9.1.1 Applicability.
9.1.1.1 This regulation does not apply to:
9.1.1.1.1 Military or public vessels of the
United States, other than recreational-type public vessels; and
9.1.1.1.2 A vessel used exclusively as a
ship's lifeboat.
9.1.1.2
9.2.1 of this regulation prescribes general provisions applicable to all
vessels covered by this regulation. Section 9.3 prescribes minimum required
equipment for recreational vessels used on the waters of this State. Section
9.4 prescribes minimum required equipment for vessels other than recreational
vessels that are not required to be documented.
9.2 Provisions Applicable to All Vessels
Covered by this Regulation.
9.2.1
Fire-Extinguishing Equipment.
9.2.1.1 All hand
portable fire extinguishers, semiportable fire extinguishing systems, and fixed
fire extinguishing systems shall be Coast Guard approved pursuant to
46 CFR §
25.30-5.
9.2.1.2 All required hand portable fire
extinguishers and semiportable fire extinguishing systems shall be of the "B"
type; i.e., suitable for extinguishing fires involving flammable liquids such
as gasoline, oil, etc., where a blanketing or smothering effect is essential.
The number designations for size will start with "I" for the smallest to "V"
for the largest. For the purpose of this regulation, only sizes I through III
will be considered. Sizes I and II are considered hand portable fire
extinguishers and sizes III, IV, and V are considered semiportable fire
extinguishing systems which shall be fitted with suitable hose and nozzle or
other practicable means so that all portions of the space concerned may be
covered. Examples of size graduations for some of the typical hand portable
fire extinguishers and semiportable fire extinguishing systems are set forth in
the following table:
Table 1:
Type | Size | FOAM (Gallons) | CO2 (Pounds) | DRY CHEMICAL (POUNDS) | HALON (Pounds) |
B | I | 11/4 | 4 | 2 | 21/2 |
B | II | 21/2 | 15 | 10 | 10 |
B | III | 12 | 35 | 20 | - |
9.2.1.3 All hand portable fire extinguishers
and semiportable fire extinguishing systems shall have permanently attached
thereto a metallic name plate giving the name of the item, the rated capacity
in gallons, quarts, or pounds, the name and address of the person or firm for
whom approved, and the identifying mark of the actual manufacturer.
9.2.1.4 Vaporizing-liquid type fire
extinguishers containing carbon tetrachloride or chlorobromomethane or other
toxic vaporing liquids are not acceptable as equipment required by this
part.
9.2.1.5 Hand portable or
semiportable extinguishers which are required on their name plates to be
protected from freezing shall not be located where freezing temperatures may be
expected.
9.2.1.6 The use of dry
chemical, stored pressure, fire extinguishers not fitted with pressure gauges
or indicating devices, manufactured prior to January 1, 1965, may be permitted
on motorboats and other vessels so long as such extinguishers are maintained in
good and serviceable condition. The following maintenance and inspections are
required for such extinguishers:
9.2.1.6.1
When the date on the inspection record tag on the extinguisher shows that 6
months have elapsed since last weight check ashore, then such extinguisher is
no longer accepted as meeting required maintenance conditions until reweighed
ashore and found to be in a serviceable condition and within required weight
conditions;
9.2.1.6.2 If the weight
of the container is 1/4 ounce less than that stamped on the container, it shall
be serviced;
9.2.1.6.3 If the outer
seal or seals (which indicate tampering or use when broken) are not intact, an
enforcement officer may inspect such extinguisher to see that the frangible
disc in the neck of the container is intact; and if such disc is not intact,
the container shall be serviced; and
9.2.1.6.4 If there is evidence of damage,
use, or leakage, such as dry chemical powder observed in the nozzle or
elsewhere on the extinguisher, the container shall be replaced with a new one
and the extinguisher shall be properly serviced or the extinguisher shall be
replaced with another approved extinguisher.
9.2.1.7 Fire extinguishers shall be at all
times kept in a condition for immediate and effective use, and shall be so
placed as to be readily accessible.
9.2.2 Backfire Flame Control.
9.2.2.1 Applicability. - This section applies
to every gasoline engine installed in a motorboat or motor vessel after April
25, 1940, except outboard motors.
9.2.2.2 Installations made before November
19, 1952, need not meet the detailed requirements of this section and may be
continued in use as long as they are serviceable and in good condition.
Replacements shall meet the applicable requirements of this section.
9.2.2.3 Installations consisting of backfire
flame arrestors or engine air and fuel induction systems bearing basic
Approval. Nos. 162.015 or 162.041 or engine air and fuel induction systems
bearing basic Approval Nos. 162.015 or 162.042, may be continued in use as long
as they are serviceable and in good condition. New installations or
replacements shall meet the applicable requirements of this section.
9.2.2.4 No person may use a vessel to which
this section applies unless each engine is provided with an acceptable means of
backfire flame control. The following are acceptable means of backfire flame
control:
9.2.2.4.1 A backfire flame arrestor
complying with Society of Automotive Engineers (SAE) Standard J-1928 or
Underwriters Laboratories (UL) Standard 1111 and marked accordingly. The flame
arrestor shall be suitably secured to the air intake with a flame tight
connection;
9.2.2.4.2 An engine air
and fuel induction system which provides adequate protection from propagation
of backfire flame to the atmosphere equivalent to that provided by an approved
backfire flame arrestor. A gasoline engine utilizing an air and fuel induction
system, and operated without an approved backfire flame arrestor, shall either
include a reed valve assembly or be installed in accordance with SAE Standard
J-1928; and
9.2.2.4.3 An
arrangement of the carburetor or engine air induction system that will disperse
any flames caused by engine backfire. The flames must be dispersed to the
atmosphere outside the vessel in such a manner that the flames will not
endanger the vessel, persons on board, or nearby vessels and structures. Flame
dispersion may be achieved by attachments to the carburetor or location of the
engine air induction system. All attachments shall be of metallic construction
with flametight connections and firmly secured to withstand vibration, shock,
and engine backfire.
9.2.2.5 No person may use a vessel to which
this section applies unless the backfire flame arrestor is serviceable and in
good condition.
9.2.3
Ventilation.
9.2.3.1 Applicability. - This
section applies to motorboats, motor vessels, and boats used on the waters of
this State and subject to this regulation.
9.2.3.2 No person shall operate a motorboat
or motor vessel, except an open boat, built after April 25, 1940, and before
August 1, 1980, which uses fuel having a flash point of 110°F, or less,
without every engine and fuel tank compartment being equipped with a natural
ventilation system. A natural ventilation system consists of:
9.2.3.2.1 At least two ventilator ducts,
fitted with cowls or their equivalent, for the efficient removal of explosive
or flammable gases from the bilges of every engine and fuel tank
compartment;
9.2.3.2.2 At least one
exhaust duct installed so as to extend from the open atmosphere to the lower
portion of the bilge and at least one intake duct that is installed to extend
to a point at least midway to the bilge or at least below the level of the
carburetor air intake; and
9.2.3.2.3 The cowls shall be located and
trimmed for maximum effectiveness and in such a manner so as to prevent
displaced fumes from being recirculated.
9.2.3.3 Boats built after July 31, 1978,
shall be exempt from the requirements of 9.2.3.1 of this section for fuel tank
compartments that:
9.2.3.3.1 Contain a
permanently installed fuel tank if each electrical component is ignition
protected in accordance with 33 CFR§
183.410(a); and
9.4.1.3.2 Contain fuel tanks that vent to the
outside of the motorboat or motor vessel.
9.2.3.4 Boats built after July 31, 1980, or
which are in compliance with the Coast Guard Ventilation Standard, a
manufacturer requirement (33
CFR §§
183.610 and
183.620), shall be exempt from the
requirements of 9.2.3.2 and 9.2.3.4 of this section.
9.2.3.5 No person shall operate a boat after
July 31, 1980, that has a gasoline engine for electrical generation, mechanical
power or propulsion unless it is equipped with an operable ventilation system
that meets the requirements of
33 CFR §§
183.610(a), (b), (d), (e) and
(f) and 183.6209(a).
9.2.3.6 Boat owners shall maintain their
boats' ventilation systems in good operating condition (regardless of the
boat's date of manufacture).
9.2.4 Whistles and Bells.
9.2.4.1 A vessel of 12 meters (39.4 ft.) or
more in length shall be equipped with a whistle and a bell. The whistle and
bell shall comply with the specifications in Annex III to the Inland Navigation
Rules ( 33 CFR Part 86). The bell may be replaced by other equipment having the
same respective sound characteristics, provided that manual sounding of the
prescribed signals shall always be possible.
9.2.4.2 A vessel of less than 12 meters (39.4
ft.) in length shall be equipped with a whistle or horn, or some other sounding
device capable of making an efficient sound signal.
9.2.5 Visual Distress Signals.
9.2.5.1 Applicability. - This section applies
to all boats operated on the coastal waters of this State and those waters
connected directly to them (i.e., bays, sounds, harbors, rivers, inlets, etc.)
where any entrance exceeds 2 nautical miles between opposite shorelines to the
first point where the largest distance between shorelines narrows to 2
miles.
9.2.5.2 Prohibition. -
Unless exempted by subsection 4.2.3 of this section, no person may use a boat
to which this section applies unless visual distress signals, approved by the
Commandant of the Coast Guard under 46 CFR Part 160 or certified by the
manufacturer under 46 CFR Parts 160 and 161, in the number required, are on
board. Devices suitable for day use and devices suitable for night use, or
devices suitable for both day and night use, shall be carried.
9.2.5.3 Exemptions. - The following boats
shall be exempt from the carriage requirements of 9.2.5.2 of this section
between sunrise and sunset, but between sunset and sunrise, visual distress
signals suitable for night use, in the number required, shall be on board:
9.2.5.3.1 Boats less than 16 feet in
length;
9.2.5.3.2 Boats
participating in organized events such as races, regattas, or marine
parades;
9.2.5.3.3 Open sailboats
less than 26 feet in length not equipped with propulsion machinery;
and
9.2.5.3.4 Manually propelled
boats.
9.2.5.4 Launchers.
- When a visual distress signal carried to meet the requirements of this
section requires a launcher to activate, then a launcher approved by the Coast
Guard under 46 CFR § 160.028 shall also be carried. Launchers manufactured
before January 1, 1981, which do not have approval numbers are acceptable for
use with meteor or parachute signals as long as they remain in serviceable
condition.
9.2.5.5 Visual distress
signals accepted. - Any of the following signals when carried in the number
required, can be used to meet the requirements of this section:
9.2.5.5.1 An electric distress light meeting
the standards of 46 CFR § 161.013 . One is required to meet the night only
requirement;
9.2.5.5.2 An orange
flag meeting the standards of 46 CFR § 160.072 . One is required to meet
the day only requirement;
9.2.5.6 Pyrotechnics meeting the standards
noted in the following table:
1 Must have manufacture date of October 1980 or later.
2 These signals require use in combination with a suitable launching device.
3 These devices may be either meteor or parachute assisted type. Some of these signals may require use in combination with a suitable launching device.
9.2.5.7 Any combination of signal devices
selected from the types noted in paragraphs 9.2.5.5.1, 9.2.5.5.2 and 9.2.5.5.3
of this section, when carried in the number required, may be used to meet both
day and night requirements. (The following illustrates the variety and
combination of devices which can be carried to meet both day and night
requirements: three hand-held red flares; one hand-held red flare and two
parachute flares; or three hand-held orange smoke signals with one electric
distress light.)
9.2.5.8 Stowage,
serviceability, approval and marking. - No person may use a boat unless the
visual distress signals required by this section are:
9.2.5.8.1 Readily accessible;
9.2.5.8.2 In serviceable condition and the
service life of the signal, if indicated by a date marked on the signal, has
not expired;
9.2.5.8.3 Legibly
marked with the approval number or certification statement as specified in 46
CFR Parts 160 and 161; and
9.2.5.8.4 In sufficient quantity as required
by the Coast Guard.
9.2.5.9 Prohibited use. - No person in a boat
shall display a visual distress signal on waters to which this section applies
under any circumstance except a situation where assistance is needed because of
immediate or potential danger to the persons on
board.
9.3
Minimum Required Equipment for Recreational-Type Vessels.
9.3.1 Personal Flotation Devices.
9.3.1.1 Except as provided in 9.3.2 of this
part, no person may use a recreational vessel unless at least one PFD of the
following types is on board for each person:
9.3.1.1.1 Type I PFD;
9.3.1.1.2 Type II PFD; or
9.3.1.1.3 Type III PFD.
9.3.1.2 No person may use a recreational
vessel 16 feet or more in length unless one Type IV PFD is on board in addition
to the total number of PFDs required in 9.3.1.1 of this section.
9.3.1.3 A Type V PFD may be carried in lieu
of any PFD required under 9.3.1.1 and 9.3.1.2 of this section, provided:
9.3.1.3.1 The approval label on the Type V
PFD indicates that the device is approved:
9.3.1.3.1.1 For the activity in which the
vessel is being used; or
9.3.1.3.1.2 As a substitute for a PFD of the
Type required in the vessel in use;
9.3.1.3.2 The PFD is used in accordance with
any requirements on the approval label; and
9.3.1.3.3 The PFD is used in accordance with
requirements in its owner's manual, if the approval label makes reference to
such a manual.
9.3.1.4 A
Type V hybrid PFD may satisfy the carriage requirements provided it is worn
except when the boat is not underway or when the user is below
deck.
9.3.2 Exceptions
9.3.2.1 Canoes and kayaks 16 feet in length
and over are exempted from the requirements for carriage of the additional Type
IV PFD required under 9.3.1.2 of this part.
9.3.2.2 Racing shells, rowing sculls, racing
canoes and racing kayaks are exempted from the requirements for carriage of any
Type PFD required under 9.3.1 of this part.
9.3.2.3 Sailboards are exempted from the
requirements for carriage of any Type PFD required under 9.3.1 of this
part.
9.3.3 Stowage,
Condition, and Marking of PFDs.
9.3.3.1 No
person may use a recreational vessel unless each Type I, II, or III PFD
required by 9.3.1.1 of this part, or equivalent Type allowed by 9.3.1.3 of this
part, is readily accessible.
9.3.3.2 No person may use a recreational
vessel unless each Type IV PFD required by 9.3.1.2 of this part, or equivalent
Type allowed by 9.3.1.3 of this part, is immediately available.
9.3.3.3 No person may use a recreational
vessel unless each PFD required by 9.3.2.3 of this part or allowed by 9.3.1.2
of this part is:
9.3.3.3.1 In serviceable
condition, as defined by 33
CFR §
175.23;
9.3.3.3.2 Of an appropriate size and fit for
the intended wearer, as marked on the approval label; and
9.3.3.3.3 Legibly marked with its Coast Guard
approval number, as specified in 46 CFR Part 160.
9.3.4 Fire-Extinguishing Equipment Required.
9.3.4.1 Motorboats less than 26 feet in
length with no fixed fire extinguishing system installed in machinery spaces
shall carry at least one Type B-I approved hand portable fire extinguisher.
When an approved fixed fire extinguishing system is installed in machinery
spaces, a portable extinguisher is not required. If the construction of the
motorboat does not permit the entrapment of explosive or flammable gases or
vapors, no fire extinguisher is required.
9.3.4.2 Motorboats 26 feet to less than 40
feet in length shall carry at least two Type B-I approved hand portable fire
extinguishers or at least one Type B-II approved portable fire extinguisher.
When an approved fixed fire extinguishing system is installed, one less Type
B-I extinguisher is required.
9.3.4.3 Motorboats 40 feet to not more than
65 feet in length shall carry at least three Type B-I approved hand portable
fire extinguishers or at least one Type B-I and one Type B-II approved portable
fire extinguisher. When an approved fixed fire extinguishing system is
installed, one less Type B-I extinguisher is required.
9.3.4.4 Motorboats 65 feet and over used for
recreational purposes shall carry fire extinguishing equipment as prescribed
under 9.4.3.2 of this regulation.
9.3.4.5 Motorboats are required to carry fire
extinguishers if any one of the following conditions exist:
9.3.4.5.1 Inboard engines;
9.3.4.5.2 Closed compartments and
compartments under seats wherein portable fuel tanks may be stored;
9.3.4.5.3 Double bottoms not sealed to the
hull or which are not completely filled with flotation material;
9.3.4.5.4 Closed living spaces;
9.3.4.5.5 Closed stowage compartments in
which combustible or flammable materials are stowed; or
9.3.4.5.6 Permanently installed fuel tanks.
(Fuel tanks secured so they cannot be moved in case of fire or other emergency
are considered permanently installed.)
9.3.4.6 Motorboats contracted for prior to
November 19, 1952, shall meet the applicable provisions of this section insofar
as the number and general type of equipment is concerned. Existing items of
equipment and installations previously approved but not meeting the applicable
requirements for type approval may be continued in service so long as they are
in good condition. All new installations and replacements shall meet the
requirements of this section.
9.4 Life-Saving Equipment for Commercial
Vessels not Documented.
9.4.1 Applicability.
This part applies to each vessel to which this regulation applies except:
9.4.1.1 Vessels used for noncommercial
use;
9.4.1.2 Vessels leased,
rented, or charted to another for the latter's noncommercial use; or
9.4.1.3 Commercial vessels propelled by sail
not carrying passengers for hire; or
9.4.1.4 Commercial barges not carrying
passengers for hire.
9.4.2 Life Preservers and Other Life-Saving
Equipment Required.
9.4.2.1 No person may
operate a vessel to which Section 9.4.1 of this part applies unless it meets
the requirements of this section.
9.4.2.2 Each vessel not carrying passengers
for hire, less than 40 feet in length, shall have at least one life preserver
(Type I PFD), buoyant vest (Type II PFD), or marine buoyant device intended to
be worn (Type III PFD), of a suitable size for each person on board. Kapok and
fibrous glass life preservers which do not have plastic-covered pad inserts as
required by 46 CFR §§ 160.062 and 160.005 are not acceptable as
equipment required by this subsection.
9.4.2.3 Each vessel carrying passengers for
hire and each vessel 40 feet in length or longer not carrying passengers for
hire shall have at least one life preserver (Type I PFD) of a suitable size for
each person on board. Kapok and fibrous glass life preservers which do not have
plastic-covered pad inserts as required by 46 CFR §§ 160.062 and
160.005 are not acceptable as equipment required by this subsection.
9.4.2.4 In addition to the equipment required
by 9.4.2.2 or 9.4.2.3 of this section, each vessel 26 feet in length or longer
shall have at least one Coast Guard approved ring life buoy.
9.4.2.5 Each vessel not carrying passengers
for hire may substitute an exposure suit (or immersion suit) for a life
preserver, buoyant vest, or marine buoyant device required under 9.4.2.2 or
9.4.2.3 of this section. Each exposure suit carried in accordance with this
paragraph shall be Coast Guard approved.
9.4.2.6 On each vessel, regardless of length
and regardless of whether carrying passengers for hire, a commercial hybrid PFD
may be substituted for a life preserver, buoyant vest, or marine buoyant device
required under 9.4.2.2 or 9.4.2.3 of this section if it is:
9.4.2.6.1 In the case of a Type V commercial
hybrid PFD, worn when the vessel is underway and the intended wearer is not
within an enclosed space;
9.4.2.6.2
Used in accordance with the conditions marked on the PFD and in the owner's
manual; and
9.4.2.6.3 Labeled for
use on uninspected commercial vessels.
9.4.2.7 The life-saving equipment required by
this section shall be legibly marked.
9.4.2.8 The life-saving equipment designed to
be worn required in 9.4.2.2, 9.4.2.3, and 9.4.2.4 of this section shall be
readily accessible.
9.4.2.8 The
life-saving equipment designed to be thrown required by 9.4.2.4 of this section
shall be immediately available.
9.4.2.9 The life-saving equipment required by
this section shall be in serviceable condition.
9.4.3 Fire-Extinguishing Equipment Required.
9.4.3.1 Motorboats.
9.4.3.1.1 Motorboats less than 26 feet in
length shall abide by 9.4.3.1 of this regulation.
9.4.3.1.2 Motorboats 26 feet in length to
less than 40 feet in length shall abide by 9.3.4.1 of this
regulation.
9.4.3.1.3 Motorboats 40
feet in length to less than 65 feet in length shall abide by 9.3.4.3 of this
regulation.
9.4.3.2 Motor
Vessels.
9.4.3.2.1 Motor vessels less than 50
gross tonnage shall carry one Type B-II approved hand portable fire
extinguisher.
9.4.3.2.2 Motor
vessels 50 and not over 100 gross tonnage shall carry two Type B-II approved
hand portable fire extinguishers.
9.4.3.2.3 Motor vessels 100 and not over 500
gross tonnage shall carry three Type B-II approved hand portable fire
extinguishers.
9.4.3.2.4 Motor
vessels 500 but not over 1,000 gross tonnage shall carry six Type B-II approved
hand portable fire extinguishers.
9.4.3.2.5 Motor vessels over 1,000 gross
tonnage shall carry eight Type B-II approved hand portable fire
extinguishers.
9.4.3.3 In
addition to the hand portable fire extinguishers required by 9.4.3.2 of this
section, the following fire-extinguishing equipment shall be fitted in the
machinery space:
9.4.3.3.1 One Type B-II hand
portable fire extinguisher shall be carried for each 1,000 B. H. P. of the main
engines or fraction thereof. However, not more than six such extinguishers need
be carried.
9.4.3.3.2 On motor
vessels over 300 gross tons, either one Type B-III semiportable
fire-extinguishing system shall be fitted, or alternatively, a fixed
fire-extinguishing system shall be fitted in the machinery
space.
9.4.3.4 Barges
carrying passengers.
9.4.3.4.1 Every barge 65
feet in length or less while carrying passengers when towed or pushed by a
motorboat, motor vessel or steam vessel shall be fitted with hand portable fire
extinguishers as required by this 9.3.4 of this regulation, depending upon the
length of the barge.
9.4.3.4.2
Every barge over 65 feet in length while carrying passengers when towed or
pushed by a motorboat, motor vessel or steam vessel shall be fitted with hand
portable fire extinguishers as required by this section, depending upon the
gross tonnage of the barge.
Notes
2 DE Reg. 1880 (4/1/99)
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.