Fla. Admin. Code Ann. R. 61G15-32.003 - Common Requirements to All Fire Protection System Engineering Documents
(1) The Fire
Protection System Engineering Documents shall provide the engineering
requirements to be used in the preparation of the Fire Protection System Layout
Documents and to indicate the nature and scope of the work, and to describe,
detail, dimension, label and define the Fire Protection Components, System(s),
materials, assemblies, equipment and its structural and utility support
system(s), insofar as they involve the safeguarding of life, health or
property.
(2) The Fire Protection
System Engineering Documents shall specify the applicable requirements for the
acceptance testing of the fire protection system and components, which shall be
based upon applicable codes and standards, where available.
(3) The occupancy of the area or description
of a specific hazard being protected by the Fire Protection System(s) shall be
shown on the Fire Protection System Engineering Documents.
(4) The applicable code(s) and standard(s) to
be used in the preparation of the Fire Protection System Layout Documents shall
be shown on the Fire Protection System Engineering Documents. When codes and
standards are not available or applicable, and said layout documents are to be
based on engineering judgment, any reasons and assumptions made to develop the
fire protection concept shall be identified on the Fire Protection System
Engineering Documents.
(5)
Structural support and structural openings required by the Fire Protection
System shall be shown on the Fire Protection System Engineering Documents and
shall be referenced on structural engineering documents.
(6) When Fire Protection Layout Documents
contain material deviation from the Fire Protection System Engineering
Documents, such Layout Documents are not compliant unless they are accompanied
by revised Engineering Documents prepared, signed, dated and sealed by the
Engineer of Record for the Fire Protection System.
(7) Requirements for activation control
systems, sequence, operating parameters, interlocks, safety related devices,
indicators and alarms, shall be shown on the Fire Protection System Engineering
Documents, unless shown on other related documents.
(8) Any information deemed appropriate by the
Engineer of Record to assist the authority having jurisdiction in understanding
the owner's intended use and proposed protection of the building or facility
and to provide sufficient direction to the installation contractor or other
interested parties regarding the layout of the system(s), shall be included in
the Fire Protection System Engineering Documents.
(9) Fire Protection System Engineering
Documents shall additionally meet the requirements of rule
61G15-30.003, F.A.C.,
Engineering Documents.
Notes
Rulemaking Authority 471.008, 471.033(2) FS. Law Implemented 471.005(7), 471.033(2) FS.
New 5-19-93, Formerly 21H-32.003, Amended 4-2-00, 6-26-01, 3-26-09, 7-25-19.