Fla. Admin. Code Ann. R. 62-257.200 - Definitions
The following definitions are used to implement Chapter 62-257, F.A.C. Definitions that reference 40 C.F.R. Part 61, Subpart M, are adopted and incorporated by reference in Rule 62-204.800, F.A.C.
(1) "Asbestos" means the asbestiform
varieties of serpentinite (chrysotile), riebeckite (crocidolite),
cummingtonite-grunerite, anthophyllite, and actinolite-tremolite and includes
trade acronyms products such as amosite.
(2) "Asbestos Consultant" means a person
licensed as an asbestos consultant in the state of Florida, who offers to,
undertakes to, submits a bid to, or does, individually or by employing others,
conduct surveys for asbestos-containing materials, develop operation and
maintenance plans, monitor and evaluate asbestos abatement, prepare asbestos
abatement specifications, or perform related tasks.
(3) "Asbestos Contractor" means a person
licensed as an asbestos contractor in the state of Florida who is qualified and
responsible for the contracted project and who offers to, undertakes to,
submits a bid to, or does, individually or by employing others, remove,
encapsulate, or enclose asbestos-containing materials or dispose of
asbestos-containing waste in the course of activities including, but not
limited to, construction, renovation, maintenance, or demolition.
(4) "Asbestos-containing materials" means
Regulated Asbestos-Containing Material, Category I Nonfriable
Asbestos-Containing Material, or Category II Nonfriable Asbestos-Containing
Material.
(5) "Asbestos removal
project" means a renovation or demolition operation in a facility that involves
the removal of a threshold amount of regulated asbestos-containing
material.
(6) "Category I
Nonfriable Asbestos-Containing Material (ACM)" means asbestos-containing
packings, gaskets, resilient floor covering, and asphalt roofing products
containing more than 1 percent asbestos as determined using the method
specified in Appendix A, Subpart E, 40 C.F.R. Part 763, Section 1, Polarized
Light Microscopy.
(7) "Category II
Nonfriable ACM" means any material, excluding Category I Nonfriable ACM,
containing more than 1 percent asbestos as determined using the methods
specified in Appendix A, Subpart E, 40 C.F.R. Part 763, Section 1, Polarized
Light Microscopy, that, when dry, cannot be crumbled, pulverized, or reduced to
powder by hand pressure.
(8)
"Department" means the Florida Department of Environmental
Protection.
(9) "Demolition" means
the wrecking or taking out of any load-supporting structural member of a
facility together with any related handling operations or the intentional
burning of any facility.
(10)
"Emergency renovation operation" means a renovation operation that was not
planned but results from a sudden, unexpected event that, if not immediately
attended to, presents a safety or public health hazard, is necessary to protect
equipment from damage, or is necessary to avoid imposing an unreasonable
financial burden. This term includes operations necessitated by nonroutine
failures of equipment.
(11)
"Facility" means any institutional, commercial, public, industrial, or
residential structure, installation, or building (including any structure,
installation, or building containing condominiums or individual dwelling units
operated as a residential cooperative, but excluding residential buildings
having four or fewer dwelling units); any ship; and any active or inactive
waste disposal site. For purposes of this definition, any building, structure,
or installation that contains a loft used as a dwelling is not considered a
residential structure, installation, or building. Any structure, installation
or building that was previously subject to 40 C.F.R. 61, Subpart M, is not
excluded, regardless of its current use or function.
(12) "Facility component" means any part of a
facility including equipment.
(13)
"Friable Asbestos Material" means any material containing more than 1 percent
asbestos as determined using the method specified in Appendix A, Subpart E, 40
C.F.R. Part 763 Section 1, Polarized Light Microscopy that, when dry, can be
crumbled, pulverized, or reduced to powder by hand pressure. If the asbestos
content is less than 10 percent as determined by a method other than point
counting by Polarized Light Microscopy (PLM), verify the asbestos content by
point counting using PLM.
(14)
"Installation" means any building or structure or any group of buildings or
structures at a single demolition or renovation site that are under the control
of the same owner or operator (or owner or operator under common
control).
(15) "Local Air Program,"
for purposes of Chapter 62-257, F.A.C., only, means a county air pollution
control program which meets the criteria of Section 403.182(1), F.S.
(16) "Nonscheduled renovation operation"
means a renovation operation necessitated by the routine failure of equipment,
which is expected to occur within a given period based on past operating
experience, but for which an exact date cannot be predicted.
(17) "Notification" or Notice" means Notice
of Renovation or Demolition Form, DEP Form Number 62-257.900(1) as adopted and
incorporated in Rule 62-257.301, F.A.C.
(18) "Ordered demolition" means a demolition
under an order of a State or local government agency, issued because the
facility is structurally unsound and in danger of imminent collapse.
(19) "Owner or operator" means any person or
entity who owns, leases, operates, controls, or supervises either the
renovation or demolition operation or the site of the renovation or demolition
operation.
(20) "Planned renovation
operation" means a renovation operation, or a number of such operations, in
which regulated asbestos-containing material will be removed or stripped within
a given period of time and that can be predicted. Individual nonscheduled
operations are included if a number of such operations can be predicted to
occur during a given period of time based on operating experience.
(21) "Renovation" means the alteration in any
way of a facility or of one or more facility components. Operations in which
load-supporting structural members are wrecked or taken out are
demolitions.
(22) "Regulated
Asbestos-Containing Material (RACM)" means:
(a) Friable asbestos material;
(b) Category I nonfriable ACM that has become
friable;
(c) Category I nonfriable
ACM that will be or has been subjected to sanding, grinding, cutting, or
abrading, or
(d) Category II
nonfriable ACM that has become crumbled, pulverized, or reduced to powder or
has a high probability of becoming crumbled, pulverized, or reduced to powder
by the forces expected to act on the material in the course of demolition or
renovation operations regulated by 40 C.F.R. Part 61, Subpart M, as adopted in
Rule 62-204.800, F.A.C.
(23) "Residential exemption" means an
asbestos removal, renovation, or demolition project exempt from the survey and
notification requirements of this chapter. This exemption applies to a
residential building having no more than four dwelling units. This exemption
does not apply to
(a) any institutional,
commercial, public, or industrial structure;
(b) any installation;
(c) any structure or building (including a
residential building) demolished as part of a larger project;
(d) any structure or building used partly for
residential purposes and partly for commercial, public, or industrial
use;
(e) any structure or building
containing condominiums or individual dwelling units operated as a residential
cooperative (since this meets the definition of "facility"); or
(f) any structure or building that previously
met the definition of a "facility," regardless of its present use.
(24) "Resilient floor covering"
means asbestos-containing floor tile, including asphalt and vinyl floor tile,
and sheet vinyl floor covering containing more than 1 percent asbestos as
determined using polarized light microscopy (PLM) according to the method
specified in Appendix E, Subpart E, 40 CFR part 763, section 1, Polarized Light
Microscopy.
(25) "State Asbestos
Coordinator" means the person designated by the Director of the Department's
Division of Air Resources Management to serve as the statewide coordinator for
the asbestos program.
(26) "Survey"
means the process of inspecting a facility or installation for the presence of
asbestos-containing materials to determine the amount, location, and condition
of asbestos-containing materials prior to transfer of property, renovation,
demolition, or maintenance projects which may disturb asbestos-containing
materials.
(27) "Threshold amount
of regulated asbestos-containing material" means at least 260 linear feet (80
linear meters) on pipes, or at least 160 square feet (15 square meters) on
other facility components, or at least 35 cubic feet (1 cubic meter) of
facility components where the length or area could not be measured
previously.
(28) "Working day"
means Monday through Friday and includes holidays that fall on any of the days
Monday through Friday.
Notes
Rulemaking Authority 376.60, 403.061 FS. Law Implemented 376.60, 403.061 FS.
New 3-31-94, Formerly 17-257.200, Amended 11-23-94, 2-9-99.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.