Fla. Admin. Code Ann. R. 62-600.735 - Operation and Maintenance Performance Report
(1) All applications to renew permits for
treatment, reuse, or disposal facilities as required by Form
62-620.910(2)
shall include a detailed operation and maintenance performance report. This
report will be used, in part, to establish reasonable assurances that these
facilities will meet permit limitations during the period for which the permit
is requested.
(2) The report shall
be jointly prepared by staff responsible for operation of these facilities, by
the permittee or the permittee's delegated representative, and by a
professional engineer registered in Florida.
(3) The report shall evaluate the capability
of treatment, reuse, and disposal facilities to function as intended during the
period for which the permit is requested.
(4) The report shall:
(a) Evaluate the physical condition of each
treatment unit, the treatment efficiencies of each treatment process, the
overall treatment efficiency of the treatment plant, performance trends, and
the operation and maintenance program.
(b) Identify physical, capacity, performance,
and operation and maintenance problems and deficiencies which need immediate
attention and areas which are potential problems. The report shall identify the
consequences if these problems and deficiencies are not corrected in a timely
fashion.
(c) Provide
recommendations and schedules for corrective actions.
(d) Evaluate the following components,
systems, and processes, if included in the facilities being considered for
permit renewal:
1. Pumping facilities (raw
wastewater, intermediate, recirculation, biosolids, effluent, or reclaimed
water pump stations).
2.
Preliminary treatment (screens, grit chambers, comminutors).
3. Primary, intermediate, and final
clarifiers (structures, scum and biosolids removal equipment, baffles, weirs,
sand and grit accumulation).
4.
Activated sludge system (blowers, mechanical aerators, aeration system, return
sludge system, diffusers, sand and grit accumulation).
5. Trickling filters (wastewater distribution
system, media, filter bottom, blowers).
6. Rotating biological contactors (drive
mechanisms, media integrity).
7.
Filters (media, distribution equipment, filter bottoms, backwash
facilities).
8.
Coagulation/flocculation (mixers, motors, flocculators, drives).
9. Nutrient removal systems.
10. Disinfection (contact chambers,
chlorinators, ozonators, ultraviolet systems).
11. Biosolids treatment and handling
(thickeners, chemical conditioning, aerobic digesters, anaerobic digesters,
biosolids collection equipment, heat exchange facilities, gas collection
equipment).
12. Biosolids
dewatering (drying beds, filter presses, vacuum filters).
13. Chemical feed facilities.
14. Blowers and motors associated with
treatment processes.
15.
Instrumentation and monitoring equipment.
16. Sample collection and laboratory
analysis.
17. Effluent or reclaimed
water pumping and transmission facilities (pumps, motors, valves).
18. Outfalls.
19. Injection wells.
20. Reuse systems.
21. Wetlands systems.
All applications to revew permits for treatment, reuse, or disposal facilities as required by Form 62-620.910(2), F.A.C., shall:
(5) The collection system and the collection
system action plan shall be evaluated if treatment plant problems result from
the operation of collection and transmission facilities (such as excessive
infiltration/inflow, septic wastewater, introduction of toxic substances, or
lack of controls on industrial wastewater discharges to the collection
system).
(6) The report shall be
signed by the owner and the facility's lead operator and shall be signed and
sealed by a professional engineer registered in Florida.
Notes
Rulemaking Authority 403.051, 403.061, 403.086, 403.087, 403.088 FS. Law Implemented 403.021, 403.051, 403.061, 403.087, 403.088 FS.
New 1-30-91, Formerly 17-600.735, Amended 12-24-96, 2-8-16, 12-6-21.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.