Fla. Admin. Code Ann. R. 62-610.621 - Setback Distances
(1) The
permittee shall maintain setback distances between the wetted site area subject
to land application and surface waters and potable water supply wells to ensure
compliance with water quality and drinking water standards, and to protect the
public health, safety and welfare. All systems shall be designed to minimize
adverse effects resulting from noise, lighting, aerosol drift, and odors.
Adequate site area shall be provided for operation and maintenance, and for
controlling emergency discharges.
(2) Overland flow land application systems
shall maintain a distance of 100 feet from the edge of the wetted area of the
land application area to buildings that are not part of the treatment
facilities, utilities system, or municipal operations; or to the site property
line, and to potable water supply wells, which are not potable water wells, as
described in Rule 62-521.200, F.A.C., that are
existing or have been approved by the Department or by the Department of Health
(but not yet constructed).
(3) A
setback distance of 500 feet shall be provided from the edge of the wetted area
to Class I surface waters; or Class II surface waters, or to potable water
wells, as described in Rule
62-521.200, F.A.C., that are
existing or have been approved by the Department or by the Department of Health
(but not yet constructed). Setback distance requirements apply to all Class II
waters, regardless of Department classification (such as open, closed,
approved, conditionally approved, restricted, conditionally restricted,
prohibited, or unclassified).
(4) A
100-foot setback distance shall be provided from a reclaimed water transmission
facility to a public water supply well and surface water intakes for a potable
water supply. No setback distance is required to other potable water supply
wells or to nonpotable water supply wells.
(5) Setback distances to potable water supply
wells shall be applied only for new or expanded overland flow systems. Setback
distances shall not be applied when considering a permit renewal.
(6) Unless specifically stated otherwise, all
setback distances shall be measured horizontally.
Notes
Rulemaking Authority 403.051, 403.061, 403.087 FS. Law Implemented 403.021, 403.051, 403.061, 403.062, 403.085, 403.086, 403.087, 403.088 FS.
New 4-4-89, Amended 4-2-90, Formerly 17-610.621, Amended 1-9-96, 8-8-99, 4-1-21.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.