Words, terms and phrases used in this chapter, unless
otherwise indicated, shall have the meaning set forth in the Standards
Dictionary of Electrical and Electronic Terms (ANSI/IEEE Standards No.
100-1988) adopted by reference in rule
62-814.300, F.A.C. In addition,
the following words or terms, when used in this chapter, shall have the
following indicated meanings:
(1)
"ANSI" means the American National Standards Institute.
(2) "Balanced Current" means currents in
three-phase electrical systems which are equal in amplitude and separated by a
phase angle of 120 degrees.
(3)
"Balanced Voltage" means voltages in a three-phase system which are equal in
amplitude and separated by a phase angle of 120 degrees.
(4) "Commence Construction" means, as applied
to the construction of a new transmission line, or new substation supplied by a
new transmission line, or new distribution line, that the facility owner has
begun a continuous program of actual on-site construction or physical
modification of the electrical facility, to be completed within a reasonable
period of time.
(5) "Department"
means the Florida Department of Environmental Protection.
(6) "Distribution Line" means a system of
conductors used to transport electrical energy at voltages of less than 69 kV
including service drops from transformers to residences or
businesses.
(7) "Electrical
Facility" means the components of an electrical transmission line, distribution
line or substation that produce or affect electric and magnetic
fields.
(8) "Facility Owner" means
an owner or operator of an electrical facility.
(9) "Gauss" means the unit of magnetic flux
density that will induce an electromotive force of 1 x 10 to the -8 volt in
each linear centimeter of a wire moving laterally with a speed of one
centimeter per second at right angles to the magnetic flux.
(10) "Hertz" means the unit of frequency of
an electrical facility equivalent to a cycle per second.
(11) "Highest Operating Voltage" means the
maximum voltage value set forth for a particular transmission line on Table 1,
ANSI C 84.1-1982, or ANSI C 92.2-1981, or the maximum operating voltage as
established by the facility owner.
(12) "IEEE" means the Institute of Electrical
and Electronic Engineers.
(13)
"Kilovolts/meter" means a unit of measurement of electric field strength
generally measured at a point one meter above the ground and expressed as
kV/m.
(14) "Maximum Current Rating"
or "MCR" means the maximum quantity of electric current, expressed in amperes,
that can be continuously carried on the conductors of an electrical circuit as
determined by the facility owner.
(15) "Maximum Electric Field Strength" means
the amplitude (Root Mean Square) of the electric field produced by an
electrical facility operating at the highest operating voltage expressed in
kV/m at a height of one meter above ground level.
(16) "Maximum Magnetic Field" means the
amplitude (Root Mean Square) of the magnetic flux density produced by an
electrical facility operating at MCR measured in Gauss one meter above the
earth's surface.
(17) "Minimum
Conductor Height" means the minimum vertical distance from the earth's surface
to the geometric center of the conductor or conductor bundle at MCR.
(18) "Modified" as it relates to electrical
facilities means a transmission line or substation that is altered or upgraded
to operate at a higher nominal voltage or current after March 21,
1989.
(19) "New Distribution Line"
means a distribution line that commenced construction after March 21,
1989.
(20) "New Electrical
Facility" means an electrical facility which commenced construction after March
21, 1989.
(21) "New Substation"
means a substation that commenced construction after March 21, 1989, that is
built to connect new transmission lines of 69 kV or larger with other
electrical facilities, or a substation into which a new transmission line is
built.
(22) "New Transmission Line"
means a transmission line upon which construction commenced after March 21,
1989, or an existing transmission line which commences construction for the
purpose of reinsulating to operate at a higher nominal voltage or
reconductoring to operate at a higher MCR after March 21, 1989. This does not
include transmission lines which are relocated or rebuilt unless such lines are
modified. This also does not include conductors used to connect existing
transmission lines to substations unless a new edge of right-of-way is created
on or immediately adjacent to private property.
(23) "NESC" means the National Electrical
Safety Code.
(24) "Nominal Voltage"
means the voltage classification as defined in Table 1, ANSI C 84.1-1982 or
ANSI C 92.2-1981.
(25)
"Residential, Commercial or Industrial Building" means a structure that persons
use for their residence, for commercial transactions, or for manufacturing a
product. It includes structures used by providers of private and governmental
services. It does not include buildings visited by people for short periods of
time on a non-daily basis.
(26)
"Right-of-Way" (ROW), as used herein, is a term intended to be used only for
purposes of determining the appropriate points for compliance with this rule,
and not for the purpose of determining a legal interest in property.
"Right-of-way" means the area between two edges of ROW. Each edge of the ROW
shall be identified as the farthermost point located by application of the
following methods:
(a) The boundary of land
where the facility owner has a property interest, such as, but not limited to,
an easement, prescriptive easement, or fee simple title, and which is used or
designated for construction, operation and maintenance of transmission
lines.
(b) In areas where the
facility owner does not have a property interest in the land where the
transmission line or distribution line will be located, the ROW will be assumed
to extend to the closer of:
1. The edge of the
nearest residential, commercial or industrial building in existence prior to
the date the electrical facility commenced construction or obtained a permit,
whichever is sooner, or
2. Fifty
feet from the point beneath the conductor closest to the edge of the ROW being
determined.
(c) In areas
where the transmission line or distribution line is adjacent to or within the
property boundary of a linear easement of a railroad, utility pipeline,
communication line, or public utility linear facility, or public road or canal,
the ROW will be assumed to extend to the closer of:
1. The farthermost edge of the linear
easement, or 50 feet from the point beneath the conductor closest to the edge
of the ROW being determined, whichever is farther, or
2. The edge of the nearest residential,
commercial or industrial building in existence prior to the date the electrical
facility commenced construction or obtained a permit, whichever is sooner.
OR
(d) In areas where the
transmission line or distribution line is adjacent to or within property owned
by federal, state, regional or local governmental agencies, the ROW will be
assumed to extend to the closer of:
1. The
edge of the nearest residential, commercial or industrial building in existence
prior to the date the electrical facility commenced construction or obtained a
permit, whichever is sooner, or
2.
Fifty feet from the point beneath the conductor closest to the edge of the ROW
being determined.
(27) "Secretary" means the Secretary of the
Department of Environmental Protection.
(28) "Substation" means the electrical
facility and related property used for the connection of transmission lines or
distribution lines to other such electrical facilities or electrical generating
plants.
(29) "Transmission Line"
means a system of conductors used to transport electrical energy at voltages of
69 kV or greater.