Fla. Admin. Code Ann. R. 69A-46.041 - Inspection Requirements for Fire Protection Systems
(1) A Fire Protection Contractor, contracting
to perform inspecting, testing, and maintenance (ITM) service on a fire
protection system must comply with the requirements of Chapter 633, F.S., and
the applicable standards in NFPA 25, Standard for the Inspection, Testing, and
Maintenance of Water-Based Fire Protection Systems, which is incorporated by
reference in Rule 69A-3.012, F.A.C. When an
inspection/test is required to be performed at a specified frequency, up to and
including annually, by NFPA 25, all inspection/tests required more frequently
than the specified frequency are also required to be performed, e.g.,
performance of an annual inspection/test would include the inspection/test
required on a daily, weekly, monthly, quarterly and semi-annual
frequency.
(2) Each system that has
been inspected, tested, or maintained by a Fire Protection Contractor, or his
or her permitted Water-Based Fire Protection Inspector, must have a record tag
of durable and weather resistant material placed on the system's main water
control valve.
(a) For sprinkler systems,
including water spray fixed systems and foam-water sprinkler systems, the main
water control valve is defined as the valve upstream of the water flow alarm
device that controls the entire system.
(b) For standpipe system risers or
combination standpipes in a single building, one record tag can be located for
all such systems at the main water control valve at the base of the standpipe
that is supplying water to all such systems.
(c) For private fire service mains, the main
water control valve shall be the first indicating gate valve downstream of the
connection to the water source.
(d)
Each fire hydrant on a private fire service main shall have a record tag
affixed to the hydrant in a manner not to impede operation of the
hydrant.
(e) For fire pumps, the
main water control valve is defined as the first indicating gate valve
downstream of the connection to the water prior to the pump. For multiple fire
pumps, one record tag shall be placed at each indicating gate valve prior to
each individual fire pump.
(f) For
water storage tanks, the main water control valve is defined as the tank
discharge valve. For multiple water storage tanks one record tag shall be
placed at each tank discharge valve.
(g) For water mist systems, the main water
control valve is defined as the first control valve upstream of the water mist
system. For multiple water mist systems, one record tag shall be placed at each
control valve upstream of each individual system.
(3) Inspection Tags.
(a) After inspection and testing, an
inspection tag shall be completed indicating all work that has been done, and
then attached to the system's main water control valve in such a position as to
permit convenient inspection and not hamper activation or operation. A new
inspection tag must be attached to the system's main water control valve each
time an inspection and test service is performed.
(b) Inspection tags must be a minimum
dimension of 133 mm (5 1/4 inches) in height and 89 mm (3 1/2 inches) in width,
and a maximum dimension of 178 mm (7 inches) in height and 102 mm (4 inches) in
width.
(c) Inspection tags must
bear the following information in an easy-to-read format:
1. 'DO NOT REMOVE BY ORDER OF THE STATE FIRE
MARSHAL.' This particular information must be in a minimum of 10-point type and
in all capital letters;
2. The
licensed Fire Protection System Contractor I or II's name and licensed physical
address;
3. The license number of
the Fire Protection System Contractor I or II;
4. The permit number of the Water-Based Fire
Protection Inspector;
5. The
permitted Water-Based Fire Protection Inspector's signature;
6. The day, month and year (to be punched);
and,
7. The facility name and
address.
8. Affixing this tag shall
not be construed to invalidate the owner's responsibility to maintain the
system as provided in Section
633.312, F.S.
9. The reverse of the RED or YELLOW tag must
include at least four separate boxes for the listing of repair work as follows:
a. Date of Repair;
b. Repaired by (Signature);
c. Print Name;
d. Type of Repair;
e. Permit Number (if repair is made by a
Water Based Fire Protection Inspector, Permit Number must be
noted.).
(d)
Inspection tags may be printed and established for a five-year period of
time.
(e) An inspection tag shall
only be removed by the Fire Protection System Contractor or his or her
permitted Water-Based Fire Protection Inspector.
(f) Compliance and Non-compliance Tags that
are greater than 1-year old shall be removed from the system except those tags
used for 3 and 5-year inspection/tests. The Compliance and Non-compliance Tags
shall remain on the system until replaced with the next 3 or 5-year
inspection/test tag. Water Based Fire Protection Inspectors shall not remove
Compliance and Non-compliance Tags from the system when the tags are less than
1-year old.
(g) A fire protection
system that has been repaired to correct a noted deficiency or impairment
documented during an inspection and test service is not required to be
reinspected by a Water Based Fire Protection Inspector until the next
inspection and test scheduled in accordance with NFPA 25. The repair must be
documented on the reverse side of the RED or YELLOW tag and a retagging of the
system is not required.
(4) Compliance and Non-compliance Tag.
(a) If a fire protection system is found to
be in compliance with the applicable NFPA ITM standards, a GREEN Compliance Tag
must be attached to the main water control valve in such a manner as to be
plainly visible and not more than 60 inches above the finished floor. GREEN
tags shall not be placed on a system if deficiencies or impairments still exist
from a previous inspection.
(b) If
a fire protection system is found to have noncritical deficiencies and is not
in compliance with the applicable NFPA ITM standards, a completed YELLOW
Non-compliance Tag must be attached to the main water control valve of the
system to indicate that corrective action is necessary. The building owner or
authorized representative must be notified by copy of the NFPA 25 inspection
report within 30 days of the inspection. If the building owner or authorized
representative has not contracted with the inspecting contractor so that the
noncritical deficiencies are corrected within 90 days from the date of the
inspection, or the inspecting contractor has not received confirmation from the
building owner or authorized representative that the corrections have been
performed by another licensed contractor, the inspecting contractor must notify
the local authority having jurisdiction (AHJ).
(c) If the system has critical deficiencies
or is found to be impaired, a completed RED Non-Compliance Tag must be attached
to the main water control valve of the system, and the contractor or inspector
must notify the building owner or authorized representative within 24 hours of
the time of the inspection. If the building owner or authorized representative
has not contracted with the inspecting contractor so that the critical
deficiencies are corrected within 30 days from the date of the inspection, or
the inspecting contractor has not received confirmation from the building owner
or authorized representative that the corrections have been performed by
another licensed contractor, the inspecting contractor must notify the local
AHJ. If a system is found to be impaired, the inspecting contractor must notify
the local AHJ within 72 hours of the time of the inspection if the impairment
has not been corrected within 72 hours of the finding.
(d) If a system is found to have noncritical
deficiencies or critical deficiencies, and the building tenant(s) is different
from the building owner, the building owner must notify the tenant(s) within 30
days of receipt of the NFPA 25 inspection report.
(e) If a system is found to have impairments,
and the building tenant(s) is different from the building owner, the building
owner must notify the tenant(s) within 72 hours of receiving notification of
the impairment.
(5) The
contractor shall maintain all records of any fire protection system having been
inspected, serviced and maintained as per the applicable NFPA ITM standards.
Inspection reports shall be maintained by the contractor for at least 10
years.
(6) These records shall be
made available to the State Fire Marshal upon request in the records storage
format utilized by the contractor.
(7) Form DFS-K3-2015, Uniform Inspection,
Testing, and Maintenance (ITM) Report (Eff. 03/2021) must be provided to the
local AHJ by the contractor, as mutually agreed between the contractor and the
local AHJ, using one of the following means:
(a) by United States mail;
(b) by hand delivery;
(c) by electronic submission; or
(d) through a third-party vendor that
collects the reports on behalf of the local AHJ. Form DFS-K3-2015 is hereby
incorporated by reference and is available on the following link:
http://www.flrules.org/Gateway/reference.asp?No=Ref-13339;
or on the Division's website at: myfloridacfo.com/Division/SFM; or by
contacting the Regulatory Licensing Section, Bureau of Fire Prevention,
Division of State Fire Marshal, 200 E. Gaines Street, Tallahassee, Florida
32399-0342, Phone: (850)413-3610.
(8) The contractor or his or her permitted
Water-Based Fire Protection Inspector must complete the inspection reports as
required in NFPA 25, which is incorporated by reference in Rule
69A-3.012, F.A.C., that outlines
all points of the inspection, test, and maintenance as required by the
applicable NFPA ITM standards. A copy of the NFPA 25 inspection report must be
provided to the owner at the completion of each inspection performed.
(9) The NFPA 25 inspection report must
include a detailed explanation of every deficiency, and indicate if the
inspection is a weekly, monthly, quarterly or annual inspection. The NFPA 25
inspection report must include the name of the permitted Water-Based Fire
Protection Inspector, the inspector permit number, the inspector's signature,
the date and time of the inspection, and the signature of the owner or the
owner's representative.
(10)
Pursuant to the provisions of Section
633.312, F.S., it is the owner's
responsibility to maintain the fire protection system and notify the tenant(s)
of deficiencies and impairments in accordance with this rule. Affixing an
inspection tag as required herein does not eliminate responsibility nor will a
transfer of risk be construed.
(11)
A contractor or licensee that performs ITM services in accordance with the
applicable NFPA ITM standards and this rule will be deemed to have performed to
the required standard of care in performing such services.
Notes
Rulemaking Authority 633.104, 633.308, 633.312 FS. Law Implemented 633.306, 633.308, 633.312, 633.338 FS.
New 10-20-93, Amended 11-21-01, Formerly 4A-46.041, Amended 5-18-08, 7-19-16, 9-1-21.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.