Fla. Admin. Code Ann. R. 69A-48.008 - Monitoring
(1) Monitored fire
alarm systems shall be installed and operate in accordance with the applicable
NFPA standards incorporated by reference in Rule
69A-3.012, F.A.C.
(2) Any person currently providing or
proposing to provide fire alarm monitoring services to protected premises
(service provider) shall notify the authority having jurisdiction in writing at
least 10 days prior to offering the service. The service provider shall notify
the authority having jurisdiction verbally within 24 hours of discontinuing
monitoring services to a protected premise. The verbal notification shall be
confirmed by the service provider submitting written notification to the
authority having jurisdiction within 10 days of the discontinuance of
monitoring services.
(3) If there
is a change in service provider for an existing fire alarm monitoring service,
the new service provider shall, within 48 hours of the service transfer, submit
to the authority having jurisdiction a completed and fully executed Form
DFS-K3-2016, Report of Change of Alarm System Service Provider, effective
09/21, http://www.flrules.org/Gateway/reference.asp?No=Ref-13440
which is incorporated by reference herein. A copy of this form may be obtained
by writing to the Bureau of Fire Prevention, Division of State Fire Marshal,
Department of Financial Services, 200 East Gaines Street, Tallahassee, Florida
32399-0345, or by downloading the document from the Bureau's website,
https://www.myfloridacfo.com/division/sfm/bfp/.
(4) Managed Facilities-based Voice Network
(MFVN) is a physical facilities-based communication network that:
(a) Is managed and maintained by the service
provider to ensure service quality and reliability from the service subscriber
location to the point at which a call is transferred or handed off to another
MFVN peer network such as the public switched telephone network (PSTN), defined
as a single or an interconnected collection of local, long distance and
international phone companies;
(b)
Conforms to all relevant PSTN standards with respect to:
1. Dialing;
2. Dial plan;
3. Call completion;
4. Carriage of alarm signals and protocols;
and
5. Loop voltage
treatment.
(c) Provides
real-time transmission of voice and real-time transmission of signals that
carry alarm industry standard alarm formats unchanged;
(d) Preserves primary line seizure for alarm
signal transmission;
(e) Provides a
method of electrical power backup such as a battery that provides a minimum of
8 hours of continued uninterrupted voice service availability to the attached
alarm system; and
(f) Provides
disaster recovery plans to address individual customer outages and network
power restoration procedures. The plans shall be provided to the authority
having jurisdiction upon request.
(5) The service provider must demonstrate
that the network is a MFVN, as described in this rule by submitting to the
authority having jurisdiction an attestation that the service provider's
network meets the criteria in paragraphs (4)(a) through (4)(f),
above.