Fla. Admin. Code Ann. R. 69AER24-3 - Means of Egress
(1) Doors.
(a) All doors in fire rated or smoke proof
corridors shall be self-closing doors.
(b) Opposite swinging smoke stop doors in
smoke partitions within the corridor shall comply with the requirements of
section 8.4.3 of the edition of NFPA 101, as adopted in rule
69A-3.012, F.A.C.
(c) Darkroom doors.
1. In darkrooms with a capacity of 10 or more
persons, a revolving darkroom door, if used, shall:
a. Have a pop-out safety feature;
and,
b. Be equipped with a remotely
located side-hinged door for secondary egress.
2. In darkrooms with a capacity of fewer than
10 people, a revolving darkroom door with a pop-out safety feature is permitted
to be used as the primary means of egress.
3. Revolving darkroom doors with a pop-out
safety feature shall be conspicuously labeled.
4. In buildings designed on or after October
18, 1994, the requirements of this section apply to darkrooms with an occupancy
of 6 or more.
(d) Exit
doors shall swing in the direction of exit travel.
(e) All egress doors and gates, regardless of
use or location serving spaces designed to be occupied by 6 or more students,
shall swing in the direction of exit travel.
(2) Existing smoke stop doors shall meet the
requirements of subdivision 8.3.4 of NFPA 101, the edition as adopted in rule
69A-3.012, F.A.C.
(a) Smoke stop doors may be used to create a
secondary means of egress from interior instructional spaces.
(b) When a pair of smoke stop doors is
located within a corridor, each leaf shall be designed to swing in a direction
opposite from the other and each leaf in the pair of doors shall swing in a
right-hand direction.
(c) Door
stops shall be provided at the head and sides of smoke stop door
frames.
(d) Smoke stop door frames
shall be free of center mullions.
(e) Smoke stop doors shall be free of locking
devices and may be held in the open position only in accordance with section
7.2.1.8 of NFPA 101.
(3)
Special Function Doors.
(a) Special function
doors such as revolving doors, power operated doors, or horizontal sliding
doors shall not be used as a means of egress.
(b) Revolving doors shall have a side-hinged
exit door within 10 feet and within the same wall.
(c) Turnstiles shall comply with subdivision
7.2.1.11 of NFPA 101, the edition as adopted in rule
69A-3.012,
F.A.C.
(4) Folding Doors
and Folding Partitions. Where permanently mounted folding or movable partitions
are used to divide a room into smaller spaces capable of being occupied by 6 or
more persons, a separate exit from each space or a permanent full height 5'
foot wide opening between the spaces shall be provided. This requirement
applies to spaces occupied by 10 or more persons in buildings occupied prior to
October 18, 1994.
(5) Gates used to
secure buildings or used for egress shall be side-hinged and shall allow egress
at all times without assistance from the side from which egress is to be
made.
(6) Screen and storm doors on
exits shall be hinged on the same side as the exit door and swing in the
direction of exit travel.
(7) Doors
and gates shall be equipped with hardware which allows egress at all
times.
(8) All fire-rated doors and
solid core doors in partitions rated at 1/2 hour or more, or installed in
smoketight partitions, shall be self-closing.
(9) Emergency Rescue (Escape) Openings
(Secondary Means of Egress).
(a) In existing
non-sprinklered buildings, every instructional space, and other spaces normally
subject to student occupancy of 10 or more, shall have at least one (1) window,
panel, or door leading to the exterior or to a separate atmosphere.
(b) For buildings designed after October 18,
1994, the emergency rescue (escape) opening shall be provided in rooms over 250
square feet used for classroom or other educational purposes or normally
subject to student occupancy of 6 or more.
(c) Windows and panels shall be operable from
the inside by a single operation and without the use of tools.
(d) A security screen or grill installed on a
window or panel shall be operable from the inside by the same single operation
as the window or panel and without the use of tools. The release device shall
be readily identifiable and accessible.
(10) Interior instructional spaces shall be
provided with side-hinged or double acting communicating doors providing
secondary means of egress and emergency rescue (escape). The door shall provide
direct access to:
(a) A separated exit
corridor;
(b) A separate
atmosphere;
(c) At least one
enclosed exit stair; or
(d) Another
classroom which has a minimum of two doors that open to separate
atmospheres.
(11)
Specialties and Signage.
(a) Emergency rescue
openings shall be marked with a sign that reads: "EMERGENCY RESCUE - KEEP AREA
CLEAR."
(b) Secondary means of
egress and emergency escape openings shall be marked with a sign that reads:
"EMERGENCY ESCAPE" or "EMERGENCY EGRESS - KEEP AREA CLEAR."
(c) Where manual pull stations are located
inside student-occupied spaces, a permanently affixed sign reading "FIRE ALARM
PULL STATION INSIDE" shall be placed outside that space and adjacent to the
door.
(d) A graphic diagram of
primary and secondary evacuation routes shall be posted adjacent to the primary
exit door from each student-occupied space. The diagram shall clearly indicate,
by contrasting color and number, the primary and secondary route of evacuation.
Exception: When an exit door from a self-contained classroom opens directly to the exterior.
(12) Open Plan Schools.
(a) Each space designed to be occupied by 50
persons or more shall have 2 or more means of egress.
(b) Open plan assembly areas shall have exits
leading directly to the exterior and shall be separated from other required
exits of the open plan.
(13) Maximum travel distances.
(a) Exits shall be maintained so that the
maximum length of travel from any point in the building or space (including
places of assembly) to an exit shall not exceed 150' feet.
(b) In a building equipped with a fully
automatic fire sprinkler system, the travel distance to an exit may be
increased to 200 feet.
(c) Open
mezzanines shall be permitted to exit to the exterior from within the space
below.
(14) Corridors and
hallways.
(a) Corridors shall be arranged so
that each end leads to an exit and shall be without pockets or dead ends more
than 20' feet in length.
(b)
Hallway widths in office and service areas shall be a minimum of 44'' inches in
width.
(c) Child Care. Areas
designated for children's sleeping mats, cots, or cribs shall include a clearly
marked exit passageway.
(15) Interior Stairs, Exterior Stairs, and
Smoke-Proof Towers.
(a) The minimum clear
width of stairways serving as a required means of egress for student occupied
areas shall be 44'' inches.
(b) All
interior stairways shall open directly to the exterior, into a protected
vestibule or into a protected corridor that opens to the exterior.
(c) The areas above or below exit stairs and
ramps, whether interior or exterior, shall not be used as a closet for storage
of any kind, or for any other purpose.
(d) Interior corridors or stairwells shall be
free of piping systems designed for flammable liquids or
gases.
(16) Kilns.
(a) Kiln rooms and areas shall be provided
with adequate exhaust to dispel emitted heat to the exterior.
(b) Kilns shall be located away from paths of
egress or exits.
(c) Kilns shall be
located in separate rooms when serving students through grade three.
(d) Kiln rooms shall be provided with
automatic heat or smoke detection devices appropriate for the
environment.
(17) Boiler
Rooms.
(a) Boilers shall comply with chapter
554, F.S., and rule chapter 69A-51, F.A.C. A valid boiler inspection
certificate of compliance issued by the State Fire Marshal shall be displayed
and clearly visible, when required.
(b) Each boiler room door shall:
1. Open directly to the outside and, if
opening toward a building or path of egress, shall have opening protection in
accordance with section 8.3.4 of NFPA 101; or
2. When a door opens into the interior of the
building, the door shall swing into the boiler room and have opening protection
in accordance with section 8.3.4 of NFPA 101.
(c) All rooms housing a fuel-fired heat
producing appliance that does not meet the minimum thresholds of rule chapter
69A-51, F.A.C., and with an input capacity of 60,000 BRUs per hour or more, and
that is intended to supply hot water or steam, shall be equipped with heat
detectors connected to any required fire alarm system. Access room doors shall
have opening protection in accordance with section 8.3.4 of NFPA
101.
(18) Shade Houses or
Green Houses.
(a) A minimum of two remotely
located side hinged doors that swing in the direction of egress shall be
provided from each shade or green house.
(b) Fire alarm pull stations shall be located
within 200' feet of any shade or green house.
(c) Fire alarm horns shall be audible inside
the shade or green house.
(19) Stages and Platforms. Stages and
platforms, including props and equipment, shall conform to the specific
requirements of chapter 13 of NFPA 101, the edition as adopted in rule
69A-3.012, F.A.C.
(20) Electrical. Emergency lighting shall be
provided in all student-occupied areas and group toilets.
Notes
Rulemaking Authority 633.104(1), (7), 633.206, 1013.12(1) FS. Law Implemented 633.104(7), 633.206, 633.208, 1013.12, 1013.371, 1013.38 FS.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.