Ga. Comp. R. & Regs. R. 110-11-1-.24 - International Building Code (IBC), 2018 Edition with 2020, 2022, 2024 and 2025 Georgia State Amendments
Click here to view image
GEORGIA STATE MINIMUM STANDARD BUILDING CODE
(INTERNATIONAL BUILDING CODE WITH GEORGIA STATE AMENDMENTS)
The INTERNATIONAL BUILDING CODE, 2018 Edition, published by the International Code Council, when used in conjunction with these and any other Georgia State Amendments to the INTERNATIONAL BUILDING CODE, 2018 Edition, shall constitute the official Georgia State Minimum Standard Building Code.
GEORGIA STATE AMENDMENTS
CODE REFERENCE:
Note: By Georgia law, the International Existing Building Code is a permissive or optional State Minimum Standard Code. Consequently, the provisions contained in the International Existing Building Code are not mandatory or applicable unless specifically referenced in the adopting ordinance of local governments.
APPENDICES:
Appendices are not enforceable unless they are specifically referenced in the body of the code or adopted by the Department of Community Affairs or the authority having jurisdiction.
SCOPE:
The provisions of the Georgia State Minimum Standard Building Code shall apply to the construction, alteration, relocation, enlargement, replacement, repair, equipment, use and occupancy, location, maintenance, removal and demolition of every building or structure or any appurtenances connected or attached to such buildings or structures.
Exception #1: Detached one- and two-family dwellings and multiple single-family dwellings (townhouses separated by a 2-hour fire-resistance-rated wall assembly) not more than three stories above grade plane in height with a separate means of egress and their accessory structures shall comply with the Georgia State Minimum Standard One- and Two-Family Dwelling Code (International Residential Code for One- and Two-Family Dwellings with Georgia State Amendments).
Exception #2: The following table titled 'Codes Reference Guide' establishes specific primary and supplementary code applications and is to be applied by the authority having jurisdiction.
|
CODES REFERENCE GUIDE |
||
|
Area |
Primary |
Supplement |
|
Occupancy Classification |
LSC |
IBC |
|
Building Construction Types including allowable height, allowable building areas, and the requirements for sprinkler protection related to minimum building construction types. |
IBC |
LSC |
|
Means of Egress |
LSC |
NONE |
|
Standpipes |
IBC |
IFC |
|
Interior Finish |
LSC |
NONE |
|
HVAC Systems |
IMC |
NONE |
|
Vertical Openings |
LSC |
NONE |
|
Sprinkler Systems minimum construction standard |
LSC |
NONE |
|
Fire Alarm Systems |
LSC |
NONE |
|
Smoke Alarms and Smoke Detection Systems |
State Statute and LSC |
NONE |
|
Portable Fire Extinguishers |
IFC |
NONE |
|
Cooking Equipment |
LSC and NFPA 96 |
NONE |
|
Fuel Fired Appliances |
IFGC |
NFPA 54 |
|
Liquid Petroleum Gas |
NFPA 58 |
NFPA 54 |
|
Compressed Natural Gas |
NFPA 52 |
NONE |
*Revise the International Building Code, 2018 Edition, to read as follows:
APPENDIX P
TALL MASS TIMBER BUILDINGS
*Revise IBC Appendix P "Tall Mass Timber Buildings" Section 602.4 'Type IV' last paragraph to read as follows:
...
In buildings of Type IV-A, IV-B and IV-C, construction with an occupied floor located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access, up to and including 12 stories or 180 feet (54 864 mm) above grade plane, mass timber interior exit and elevator hoistway enclosures shall be protected in accordance with Section 602.4.1.2. In buildings greater than 12 stories or 180 feet (54 864 mm) above grade plane, interior exit and elevator hoistway enclosures shall be constructed of non-combustible materials.
(Effective January 1, 2025)
Click here to view image
GEORGIA STATE MINIMUM STANDARD BUILDING CODE
(INTERNATIONAL BUILDING CODE WITH GEORGIA STATE AMENDMENTS)
The INTERNATIONAL BUILDING CODE, 2018 Edition, published by the International Code Council, when used in conjunction with these and any other Georgia State Amendments to the INTERNATIONAL BUILDING CODE, 2018 Edition, shall constitute the official Georgia State Minimum Standard Building Code.
GEORGIA STATE AMENDMENTS
CODE REFERENCE:
Note: By Georgia law, the International Existing Building Code is a permissive or optional State Minimum Standard Code. Consequently, the provisions contained in the International Existing Building Code are not mandatory or applicable unless specifically referenced in the adopting ordinance of local governments.
APPENDICES:
Appendices are not enforceable unless they are specifically referenced in the body of the code or adopted by the Department of Community Affairs or the authority having jurisdiction.
SCOPE:
The provisions of the Georgia State Minimum Standard Building Code shall apply to the construction, alteration, relocation, enlargement, replacement, repair, equipment, use and occupancy, location, maintenance, removal and demolition of every building or structure or any appurtenances connected or attached to such buildings or structures.
Exception #1: Detached one- and two-family dwellings and multiple single-family dwellings (townhouses separated by a 2-hour fire-resistance-rated wall assembly) not more than three stories above grade plane in height with a separate means of egress and their accessory structures shall comply with the Georgia State Minimum Standard One- and Two-Family Dwelling Code (International Residential Code for One- and Two-Family Dwellings with Georgia State Amendments).
Exception #2: The following table titled 'Codes Reference Guide' establishes specific primary and supplementary code applications and is to be applied by the authority having jurisdiction.
|
CODES REFERENCE GUIDE |
||
|
Area |
Primary |
Supplement |
|
Occupancy Classification |
LSC |
IBC |
|
Building Construction Types including allowable height, allowable building areas, and the requirements for sprinkler protection related to minimum building construction types. |
IBC |
LSC |
|
Means of Egress |
LSC |
NONE |
|
Standpipes |
IBC |
IFC |
|
Interior Finish |
LSC |
NONE |
|
HVAC Systems |
IMC |
NONE |
|
Vertical Openings |
LSC |
NONE |
|
Sprinkler Systems minimum construction standard |
LSC |
NONE |
|
Fire Alarm Systems |
LSC |
NONE |
|
Smoke Alarms and Smoke Detection Systems |
State Statute and LSC |
NONE |
|
Portable Fire Extinguishers |
IFC |
NONE |
|
Cooking Equipment |
LSC and NFPA 96 |
NONE |
|
Fuel Fired Appliances |
IFGC |
NFPA 54 |
|
Liquid Petroleum Gas |
NFPA 58 |
NFPA 54 |
|
Compressed Natural Gas |
NFPA 52 |
NONE |
*Revise the International Building Code, 2018 Edition, to read as follows:
CHAPTER 2
DEFINITIONS
SECTION 202
DEFINITIONS
*Revise Section 202 'Definitions' to read as follows:
[F] FLAMMABLE GAS. A material which is a gas at 68°F (20°C) or less at 14.7 pounds per square inch atmosphere (psia) (101 kPa) of pressure [a material that has a boiling point of 68°F (20°C) or less at 14.7 psia (101 kPa)], subdivided as follows:
A gas which meets the flammability criteria for Category 1A, is not pyrophoric or chemically unstable, and meets one or more of the following:
The limits specified shall be determined at 14.7 psi (101 kPa) of pressure and a temperature of 68°F (20°C) in accordance with ASTM E681.
Where not otherwise specified, the term "flammable gas" includes both Category 1A and Category 1B.
(Effective January 1, 2024)
CHAPTER 4
SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY AND USE
SECTION 414
HAZARDOUS MATERIALS
*Revise Table 414.5.1 'Explosion Control Requirements' and add new footnote to read as follows:
TABLE 414.5.1 EXPLOSION CONTROL REQUIREMENTS
Portions of table not shown remain unchanged.
|
MATERIAL |
CLASS |
EXPLOSION CONTROL METHODS |
|
|
Barricade construction |
Explosion (deflagration) venting or explosion (deflagration) prevention systems |
||
|
Hazard Category |
|||
|
Flammable gas |
Gaseous |
Not required |
Requiredi |
|
Liquefied |
Not required |
Requiredi |
|
...
CHAPTER 15
ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
SECTION 1511
REROOFING
*Revise Section 1511.1 'General' to read as follows:
Materials and methods of application for recovering or replacing an existing roof covering shall comply with the requirements of Chapter 15.
Exception 1
Roof replacement or roof recover of existing low-slope roof coverings shall not be required to meet the minimum design slope requirement of one-quarter unit vertical in 12 units horizontal (2-percent slope) in Section 1507 for roofs that provide positive roof drainage and meet the requirements of Section 1608.3 and Section 1611.2.
Exception 2
Recovering or replacing an existing roof covering shall not be required to meet the requirement for secondary (emergency overflow) drains or scuppers in Section 1502.2 for roofs that provide for positive roof drainage and meet the requirements of Section 1608.3 and Section 1611.2. For the purposes of this exception, existing secondary drainage or scupper systems required in accordance with this code shall not be removed unless they are replaced by secondary drains or scuppers designed and installed in accordance with Section 1502.2.
Click here to view image
GEORGIA STATE MINIMUM STANDARD BUILDING CODE
(INTERNATIONAL BUILDING CODE WITH GEORGIA STATE AMENDMENTS)
The INTERNATIONAL BUILDING CODE, 2018 Edition, published by the International Code Council, when used in conjunction with these and any other Georgia State Amendments to the INTERNATIONAL BUILDING CODE, 2018 Edition, shall constitute the official Georgia State Minimum Standard Building Code.
GEORGIA STATE AMENDMENTS
CODE REFERENCE:
Note: By Georgia law, the International Existing Building Code is a permissive or optional State Minimum Standard Code. Consequently, the provisions contained in the International Existing Building Code are not mandatory or applicable unless specifically referenced in the adopting ordinance of local governments.
APPENDICES:
Appendices are not enforceable unless they are specifically referenced in the body of the code or adopted by the Department of Community Affairs or the authority having jurisdiction.
SCOPE:
The provisions of the Georgia State Minimum Standard Building Code shall apply to the construction, alteration, relocation, enlargement, replacement, repair, equipment, use and occupancy, location, maintenance, removal and demolition of every building or structure or any appurtenances connected or attached to such buildings or structures.
Exception #1: Detached one- and two-family dwellings and multiple single-family dwellings (townhouses separated by a 2-hour fire-resistance-rated wall assembly) not more than three stories above grade plane in height with a separate means of egress and their accessory structures shall comply with the Georgia State Minimum Standard One- and Two-Family Dwelling Code (International Residential Code for One- and Two-Family Dwellings with Georgia State Amendments).
Exception #2: The following table titled 'Codes Reference Guide' establishes specific primary and supplementary code applications and is to be applied by the authority having jurisdiction.
|
CODES REFERENCE GUIDE |
||
|
Area |
Primary |
Supplement |
|
Occupancy Classification |
LSC |
IBC |
|
Building Construction Types including allowable height, allowable building areas, and the requirements for sprinkler protection related to minimum building construction types. |
IBC |
LSC |
|
Means of Egress |
LSC |
NONE |
|
Standpipes |
IBC |
IFC |
|
Interior Finish |
LSC |
NONE |
|
HVAC Systems |
IMC |
NONE |
|
Vertical Openings |
LSC |
NONE |
|
Sprinkler Systems minimum construction standard |
LSC |
NONE |
|
Fire Alarm Systems |
LSC |
NONE |
|
Smoke Alarms and Smoke Detection Systems |
State Statute and LSC |
NONE |
|
Portable Fire Extinguishers |
IFC |
NONE |
|
Cooking Equipment |
LSC and NFPA 96 |
NONE |
|
Fuel Fired Appliances |
IFGC |
NFPA 54 |
|
Liquid Petroleum Gas |
NFPA 58 |
NFPA 54 |
|
Compressed Natural Gas |
NFPA 52 |
NONE |
*Revise the International Building Code, 2018 Edition, to read as follows:
CHAPTER 6
TYPES OF CONSTRUCTION
SECTION 602
CONSTRUCTION CLASSIFICATION
*Add new Section 602.1.2 'Alternative mass timber provisions (Appendix P)' to read as follows:
CHAPTER 17
SPECIAL INSPECTIONS AND TESTS
SECTION 1704
SPECIAL INSPECTIONS AND TESTS, CONTRACTOR RESPONSIBILITY AND STRUCTRUAL OBSERVATION
*Revise Table 1704.2 'Minimum Special Inspector Qualifications' to read as follows:
|
TABLE 1704.2 MINIMUM SPECIAL INSPECTOR QUALIFICATIONS |
|||
|
Category of Testing and Inspection |
Minimum Qualifications (refer to key at end of Table) |
||
|
Shop Testing or Inspection |
Field Testing or Inspection |
Review Testing, Certification & Lab Reports |
|
|
1704.2.5 Inspection of Fabricators |
|||
|
Pre-cast concrete |
A, C, E |
||
|
Structural steel construction |
C, F, G |
||
|
Wood construction |
A |
||
|
Cold formed metal construction |
A |
||
|
1705.2, 1705.10, 1705.11 & 1705.12 Steel Construction |
|||
|
Verification of welding consumables, filler metals, procedure specifications, procedure qualification records and personnel performance qualification records |
C, F |
||
|
Nondestructive testing of welding |
G |
G |
|
|
Inspection of welding |
C, F |
C, F |
|
|
Verification of fabricator and erector documents as listed in AISC 360, chapter N, paragraph 3.2 |
A, C |
||
|
Material verification of weld filler materials |
C, F |
||
|
Inspection of high strength bolting and steel frame joint details |
A, C |
||
|
Inspection of embedment |
A, C, F |
||
|
Inspection of steel elements of composite construction |
A, C, F |
||
|
Verification of reinforcing steel, cold formed steel deck and truss materials |
A, C, F |
||
|
Inspection of reinforcing steel, cold formed steel deck and trusses |
A, C |
||
|
1705.3 & 1705.12 Concrete Construction |
|||
|
Reinforcing placement, cast-in-place bolts, post installed anchors concrete and shotcrete placement and curing operations. Inspection of formwork for shape, location and dimensions |
A, C, H |
||
|
Pre-stressing steel installation |
A, C, D, E |
||
|
Erection of pre-cast concrete members |
A, C, H |
||
|
Concrete field sampling and field testing |
J |
||
|
Concrete strength testing |
P |
||
|
Review certified mill reports |
A, C |
||
|
Verify use of required design mix |
A, I, J, H, C |
||
|
Pre-stressed (pre-tensioned) concrete force application |
A, C, E |
||
|
Post-tensioned concrete force application |
A, C, D |
||
|
Review of in-situ concrete strength, prior to stressing of |
|||
Remainder of Table to remain unchanged.
(Effective January 1, 2022)
SECTION 1705
REQUIRED SPECIAL INSPECTIONS AND TESTS
*Revise Table 1705.3 'Required Special Inspections and Tests of Concrete Construction' to read as follows:
TABLE 1705.3
REQUIRED SPECIAL INSPECTIONS AND TESTS OF CONCRETE CONSTRUCTION
|
TYPE |
CONTINUOUS SPECIAL INSPECTION |
PERIODIC SPECIAL INSPECTION |
REFERENCE D STANDARDa |
IBC REFERENCE |
|
1. Inspect reinforcement, including prestressing tendons, and verify placement. |
X |
ACI 318: Ch. 20, 25.2, 25.3, 26.6.126.6.3 |
1908.4 |
|
|
2. Reinforcing bar welding: a. Verify weldability of reinforcing bars other than ASTM A706; b. Inspect single-pass fillet welds, maximum 5/16"; and c. Inspect all other welds. |
- |
X |
AWS D1.4 ACI 318: 26.6.4 |
- |
|
X |
||||
|
X |
||||
|
3. Inspect anchors cast in concrete. |
- |
X |
ACI 318: 17.8.2 |
- |
|
4. Inspect anchors post-installed in hardened concrete members.b a. Adhesive anchors installed in horizontally or upwardly inclined orientations to resist sustained tension loads. b. Mechanical anchors and adhesive anchors not defined in 4.a. |
X |
X |
ACI 318: 17.8.2.4 |
- |
|
ACI 318: 17.8.2 |
||||
|
5. Verify use of required design mix. |
- |
X |
ACI 318: Ch. 19, 26.4.3, 26.4.4 |
1904.1, 1904.2, 1908.2, 1908.3 |
|
6a. Prior to concrete placement, fabricate specimens for strength tests, perform slump or slump flow, air content tests, density and determine the temperature of the concrete with all results included in the test reports. |
X |
- |
ASTM C172 ASTM C31 ACI 318: 26.5, 26.12 |
1908.10 |
|
6b. Verify that concrete specimens for strength tests are maintained in the required initial curing and laboratory curing environment, and that the maximum and minimum temperatures during the initial curing period are reported. |
X |
- |
ACI 318 26.12 ASTM C31 |
- |
|
7. Inspect concrete and shotcrete placement for proper application techniques. |
X |
- |
ACI 318: 26.5 |
1908.6, 1908.7, 1908.8 |
|
8. Verify maintenance of specified curing temperature and techniques. |
- |
X |
ACI 318: 26.5.3-26.5.5 |
1908.9 |
|
9. Inspect prestressed concrete for: a. Application of prestressing forces; and b. Grouting of bonded prestressing tendons. |
X X |
- |
ACI 318: 26.10 |
- |
|
10. Inspect erection of precast concrete members. |
X |
ACI 318: 26.9 |
||
|
11. Verify in-situ concrete strength, prior to stressing of tendons in post-tensioned concrete and prior to removal of shores and forms from beams and structural slabs. |
X |
ACI 318: 26.11.2 |
||
|
12. Inspect formwork for shape, location and dimensions of the concrete member being formed. |
- |
X |
ACI 318: 26.11.1.2(b) |
- |
For SI: 1 inch = 25.4mm.
(Effective January 1, 2022)
*Add new Section 1705.3.3 'Testing agency' to read as follows:
(Effective January 1, 2022)
CHAPTER 35
REFERENCED STANDARDS
*Revise Chapter 35 'Referenced Standards' to add the following new reference standards to read as follows:
|
ASTM |
ASTM International 100 Barr Harbor Drive West Conshohocken, PA 19428-2859 |
|
|
Standard reference number |
Title |
Referenced in code section number |
|
c1077-17 |
Standard Practice for Agencies Testing concrete and Concrete Aggregates for Use in Construction and Criteria for Testing Agency Evaluation. |
1705.3.3, GA Amendments |
IBC APPENDIX P
TALL MASS TIMBER BUILDINGS
P101
GENERAL
P102
AMENDMENTS TO THE 2018 INTERNATIONAL BUILDING CODE
CHAPTER 1
SCOPE AND ADMINISTRATION
Add new text as follows:
CHAPTER 2
DEFINITIONS
Add new text as follows:
MASS TIMBER. Structural elements of Type IV construction primarily of solid, built-up, panelized or engineered wood products that meet minimum cross section dimensions of Type IV construction.
NONCOMBUSTIBLE PROTECTION (FOR MASS TIMBER). Noncombustible material, in accordance with Section 703.5, designed to increase the fire-resistance rating and delay the combustion of mass timber.
Revise as follows:
[BS] WALL, LOAD-BEARING. Any wall meeting either of the following classifications:
CHAPTER 4
SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY AND USE
Revise as follows:
Exception: Two connections to the same main shall be permitted provided that the main is valved such that an interruption can be isolated so that the water supply will continue without interruption through not fewer than one of the connections.
CHAPTER 5
GENERAL BUILDING HEIGHT AND AREAS
Revise as follows:
TABLE 504.3
ALLOWABLE BUILDING HEIGHT IN FEET ABOVE GRADE PLANEa
|
OCCUPANCY CLASSIFICATION |
TYPE OF CONSTRUCTION |
||||||||||||
|
SEE FOOTNOTES |
TYPE I |
TYPE II |
TYPE III |
TYPE IV |
TYPE V |
||||||||
|
A |
B |
A |
B |
A |
B |
A |
B |
C |
HT |
A |
B |
||
|
A, B, E, F, M, S, U |
NSb |
UL |
160 |
65 |
55 |
65 |
55 |
65 |
65 |
65 |
65 |
50 |
40 |
|
S |
UL |
180 |
85 |
75 |
85 |
75 |
270 |
180 |
85 |
85 |
70 |
60 |
|
|
H-1, H-2, H-3, H-5 |
NSc,d |
UL |
160 |
65 |
55 |
65 |
55 |
120 |
90 |
65 |
65 |
50 |
40 |
|
S |
|||||||||||||
|
H-4 |
NSc,d |
UL |
160 |
65 |
55 |
65 |
55 |
65 |
65 |
65 |
65 |
50 |
40 |
|
S |
UL |
180 |
85 |
75 |
85 |
75 |
140 |
100 |
85 |
85 |
70 |
60 |
|
|
I-1 Condition 1, I-3 |
NSd,e |
UL |
160 |
65 |
55 |
65 |
55 |
65 |
65 |
65 |
65 |
50 |
40 |
|
S |
UL |
180 |
85 |
75 |
85 |
75 |
180 |
120 |
85 |
85 |
70 |
60 |
|
|
I-1 Condition 2, I-2 |
NSd,e,f |
UL |
160 |
65 |
55 |
65 |
55 |
65 |
65 |
65 |
65 |
50 |
40 |
|
S |
UL |
180 |
85 |
||||||||||
|
I-4 |
NSd,g |
UL |
160 |
65 |
55 |
65 |
55 |
65 |
65 |
65 |
65 |
50 |
40 |
|
S |
UL |
180 |
85 |
75 |
85 |
75 |
180 |
120 |
85 |
85 |
70 |
60 |
|
|
Rh |
NSd |
UL |
160 |
65 |
55 |
65 |
55 |
65 |
65 |
65 |
65 |
50 |
40 |
|
S13D |
60 |
60 |
60 |
60 |
60 |
60 |
60 |
60 |
60 |
60 |
50 |
40 |
|
|
S13R |
60 |
60 |
60 |
60 |
60 |
60 |
60 |
60 |
60 |
60 |
60 |
60 |
|
|
S |
UL |
180 |
85 |
75 |
85 |
75 |
270 |
180 |
85 |
85 |
70 |
60 |
|
For SI: 1 foot = 304.8 mm
UL = Unlimited; NS = Buildings not equipped throughout with an automatic sprinkler system; S = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2; S13D = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.3.
Revise as follows:
TABLE 504.4
ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANEa, b
|
OCCUPANCY CLASSIFICATION |
TYPE OF CONSTRUCTION |
||||||||||||
|
SEE FOOTNOTES |
TYPE I |
TYPE II |
TYPE III |
TYPE IV |
TYPE V |
||||||||
|
A |
B |
A |
B |
A |
B |
A |
B |
C |
HT |
A |
B |
||
|
A-1 |
NS |
UL |
5 |
3 |
2 |
3 |
2 |
3 |
3 |
3 |
3 |
2 |
1 |
|
S |
UL |
6 |
4 |
3 |
4 |
3 |
9 |
6 |
4 |
4 |
3 |
2 |
|
|
A-2 |
NS |
UL |
11 |
3 |
2 |
3 |
2 |
3 |
3 |
3 |
3 |
2 |
1 |
|
S |
UL |
12 |
4 |
3 |
4 |
3 |
18 |
12 |
6 |
4 |
3 |
2 |
|
|
A-3 |
NS |
UL |
11 |
3 |
2 |
3 |
2 |
3 |
3 |
3 |
3 |
2 |
1 |
|
S |
UL |
12 |
4 |
3 |
4 |
3 |
18 |
12 |
6 |
4 |
3 |
2 |
|
|
A-4 |
NS |
UL |
11 |
3 |
2 |
3 |
2 |
3 |
3 |
3 |
3 |
2 |
1 |
|
S |
UL |
12 |
4 |
3 |
4 |
3 |
18 |
12 |
6 |
4 |
3 |
2 |
|
|
A-5 |
NS |
UL |
UL |
UL |
UL |
UL |
UL |
1 |
1 |
1 |
UL |
UL |
UL |
|
S |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
|
|
B |
NS |
UL |
11 |
5 |
3 |
5 |
3 |
5 |
5 |
5 |
5 |
3 |
2 |
|
S |
UL |
12 |
6 |
4 |
6 |
4 |
18 |
12 |
9 |
6 |
4 |
3 |
|
|
E |
NS |
UL |
5 |
3 |
2 |
3 |
2 |
3 |
3 |
3 |
3 |
1 |
1 |
|
S |
UL |
6 |
4 |
3 |
4 |
3 |
9 |
6 |
4 |
4 |
2 |
2 |
|
|
F-1 |
NS |
UL |
11 |
4 |
2 |
3 |
2 |
3 |
3 |
3 |
4 |
2 |
1 |
|
S |
UL |
12 |
5 |
3 |
4 |
3 |
10 |
7 |
5 |
5 |
3 |
2 |
|
|
F-2 |
NS |
UL |
11 |
5 |
3 |
4 |
3 |
5 |
5 |
5 |
5 |
3 |
2 |
|
S |
UL |
12 |
6 |
4 |
5 |
4 |
12 |
8 |
6 |
6 |
4 |
3 |
|
|
H-1 |
NSc,d |
1 |
1 |
1 |
1 |
1 |
1 |
NP |
NP |
NP |
1 |
1 |
NP |
|
S |
1 |
1 |
1 |
||||||||||
|
H-2 |
NSc,d |
UL |
3 |
2 |
1 |
2 |
1 |
1 |
1 |
1 |
2 |
1 |
1 |
|
S |
2 |
2 |
2 |
||||||||||
|
H-3 |
NSc,d |
UL |
6 |
4 |
2 |
4 |
2 |
3 |
3 |
3 |
4 |
2 |
1 |
|
S |
4 |
4 |
4 |
||||||||||
|
H-4 |
NSc,d |
UL |
7 |
5 |
3 |
5 |
3 |
5 |
5 |
5 |
5 |
3 |
2 |
|
S |
UL |
8 |
6 |
4 |
6 |
4 |
8 |
7 |
6 |
6 |
4 |
3 |
|
|
H-5 |
NSc,d |
4 |
4 |
3 |
3 |
3 |
3 |
2 |
2 |
2 |
3 |
3 |
2 |
|
S |
3 |
3 |
3 |
||||||||||
|
I-1 Condition 1 |
NSd,e |
UL |
9 |
4 |
3 |
4 |
3 |
4 |
4 |
4 |
4 |
3 |
2 |
|
S |
UL |
10 |
5 |
4 |
5 |
4 |
10 |
7 |
5 |
5 |
4 |
3 |
|
|
I-1 Condition 2 |
NSd,e |
NP |
NP |
NP |
NP |
NP |
NP |
NP |
NP |
NP |
NP |
NP |
NP |
|
Si |
UL |
10 |
3 |
2 |
2 |
1 |
7 |
4 |
1 |
2 |
2 |
1 |
|
|
I-2 |
NSd,f |
UL |
4 |
2 |
1 |
1 |
NP |
NP |
NP |
NP |
1 |
1 |
NP |
|
S |
UL |
5 |
3 |
7 |
5 |
1 |
|||||||
|
I-3 |
NSd,e |
UL |
4 |
2 |
1 |
2 |
1 |
2 |
2 |
2 |
2 |
2 |
1 |
|
S |
UL |
5 |
3 |
2 |
3 |
2 |
7 |
5 |
3 |
3 |
3 |
2 |
|
|
I-4 |
NSd,g |
UL |
5 |
3 |
2 |
3 |
2 |
3 |
3 |
3 |
3 |
1 |
1 |
|
S |
UL |
6 |
4 |
3 |
4 |
3 |
9 |
6 |
4 |
4 |
2 |
2 |
|
|
M |
NS |
UL |
11 |
4 |
2 |
4 |
2 |
4 |
4 |
4 |
4 |
3 |
1 |
|
S |
UL |
12 |
5 |
3 |
5 |
3 |
12 |
8 |
6 |
5 |
4 |
2 |
|
|
R-1h |
NSd |
UL |
11 |
4 |
4 |
4 |
4 |
4 |
4 |
4 |
4 |
3 |
2 |
|
S13R |
4 |
4 |
4 |
3 |
|||||||||
|
S |
UL |
12 |
5 |
5 |
5 |
5 |
18 |
12 |
8 |
5 |
4 |
3 |
|
|
R-2h |
NSd |
UL |
11 |
4 |
4 |
4 |
4 |
4 |
4 |
4 |
4 |
3 |
2 |
|
S13R |
4 |
4 |
4 |
4 |
3 |
||||||||
|
S |
UL |
12 |
5 |
5 |
5 |
5 |
18 |
12 |
8 |
5 |
4 |
3 |
|
|
R-3h |
NSd |
UL |
11 |
4 |
4 |
4 |
4 |
4 |
4 |
4 |
4 |
3 |
3 |
|
S13D |
4 |
4 |
3 |
3 |
|||||||||
|
S13R |
4 |
4 |
4 |
4 |
|||||||||
|
S |
UL |
12 |
5 |
5 |
5 |
5 |
18 |
12 |
5 |
5 |
4 |
4 |
|
|
R-4h |
NSd |
UL |
11 |
4 |
4 |
4 |
4 |
4 |
4 |
4 |
4 |
3 |
2 |
|
S13D |
4 |
4 |
3 |
2 |
|||||||||
|
S13R |
4 |
4 |
4 |
3 |
|||||||||
|
S |
UL |
12 |
5 |
5 |
5 |
5 |
18 |
12 |
5 |
5 |
4 |
3 |
|
|
S-1 |
NS |
UL |
11 |
4 |
2 |
3 |
2 |
4 |
4 |
4 |
4 |
3 |
1 |
|
S |
UL |
12 |
5 |
3 |
4 |
3 |
10 |
7 |
5 |
5 |
4 |
2 |
|
|
S-2 |
NS |
UL |
11 |
5 |
3 |
4 |
3 |
4 |
4 |
4 |
4 |
4 |
2 |
|
S |
UL |
12 |
6 |
4 |
5 |
4 |
12 |
8 |
5 |
5 |
5 |
3 |
|
|
U |
NS |
UL |
5 |
4 |
2 |
3 |
2 |
4 |
4 |
4 |
4 |
2 |
1 |
|
S |
UL |
6 |
5 |
3 |
4 |
3 |
9 |
6 |
5 |
5 |
3 |
2 |
|
UL = Unlimited; NP = Not Permitted; NS = Buildings not equipped throughout with an automatic sprinkler system; S = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2; S13D = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.3.
Revise as follows:
TABLE 506.2
ALLOWABLE AREA FACTOR (At= NS, S1, S13R, S13D OR SM, as applicable) IN SQUARE FEETa,b
|
OCCUPANCY CLASSIFICATION |
TYPE OF CONSTRUCTION |
||||||||||||
|
SEE FOOTNOTES |
TYPE I |
TYPE II |
TYPE III |
TYPE IV |
TYPE V |
||||||||
|
A |
B |
A |
B |
A |
B |
A |
B |
C |
HT |
A |
B |
||
|
A-1 |
NS |
UL |
UL |
15,500 |
8,500 |
14,000 |
8,500 |
45,000 |
30,000 |
18,750 |
15,000 |
11,500 |
5,500 |
|
S1 |
UL |
UL |
62,000 |
34,000 |
56,000 |
34,000 |
180,000 |
120,000 |
75,000 |
60,000 |
46,000 |
22,000 |
|
|
SM |
UL |
UL |
46,500 |
25,500 |
42,000 |
25,500 |
135,000 |
90,000 |
56,250 |
45,000 |
34,500 |
16,500 |
|
|
A-2 |
NS |
UL |
UL |
15,500 |
9,500 |
14,000 |
9,500 |
45,000 |
30,000 |
18,750 |
15,000 |
11,500 |
6,000 |
|
S1 |
UL |
UL |
62,000 |
38,000 |
56,000 |
38,000 |
180,000 |
120,000 |
75,000 |
60,000 |
46,000 |
24,000 |
|
|
SM |
UL |
UL |
46,500 |
28,500 |
42,000 |
28,500 |
135,000 |
90,000 |
56,250 |
45,000 |
34,500 |
18,000 |
|
|
A-3 |
NS |
UL |
UL |
15,500 |
9,500 |
14,000 |
9,500 |
45,000 |
30,000 |
18,750 |
15,000 |
11,500 |
6,000 |
|
S1 |
UL |
UL |
62,000 |
38,000 |
56,000 |
38,000 |
180,000 |
120,000 |
75,000 |
60,000 |
46,000 |
24,000 |
|
|
SM |
UL |
UL |
46,500 |
28,500 |
42,000 |
28,500 |
135,000 |
90,000 |
56,250 |
45,000 |
34,500 |
18,000 |
|
|
A-4 |
NS |
UL |
UL |
15,500 |
9,500 |
14,000 |
9,500 |
45,000 |
30,000 |
18,750 |
15,000 |
11,500 |
6,000 |
|
S1 |
UL |
UL |
62,000 |
38,000 |
56,000 |
38,000 |
180,000 |
120,000 |
75,000 |
60,000 |
46,000 |
24,000 |
|
|
SM |
UL |
UL |
46,500 |
28,500 |
42,000 |
28,500 |
135,000 |
90,000 |
56,250 |
45,000 |
34,500 |
18,000 |
|
|
A-5 |
NS |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
|
S1 |
|||||||||||||
|
SM |
|||||||||||||
|
B |
NS |
UL |
UL |
37,500 |
23,000 |
28,500 |
19,000 |
108,000 |
72,000 |
45,000 |
36,000 |
18,000 |
9,000 |
|
S1 |
UL |
UL |
150,000 |
92,000 |
114,000 |
76,000 |
432,000 |
288,000 |
180,000 |
144,000 |
72,000 |
36,000 |
|
|
SM |
UL |
UL |
112,500 |
69,000 |
85,500 |
57,000 |
324,000 |
216,000 |
135,000 |
108,000 |
54,000 |
27,000 |
|
|
E |
NS |
UL |
UL |
26,500 |
14,500 |
23,500 |
14,500 |
76,500 |
51,000 |
31,875 |
25,500 |
18,500 |
9,500 |
|
S1 |
UL |
UL |
106,000 |
58,000 |
94,000 |
58,000 |
306,000 |
204,000 |
127,500 |
102,000 |
74,000 |
38,000 |
|
|
SM |
UL |
UL |
79,500 |
43,500 |
70,500 |
43,500 |
229,500 |
153,000 |
95,625 |
76,500 |
55,500 |
28,500 |
|
|
F-1 |
NS |
UL |
UL |
25,000 |
15,500 |
19,000 |
12,000 |
100,500 |
67,000 |
41.875 |
33,500 |
14,000 |
8,500 |
|
S1 |
UL |
UL |
100,000 |
62,000 |
76,000 |
48,000 |
402,000 |
268,000 |
167,500 |
134,000 |
56,000 |
34,000 |
|
|
SM |
UL |
UL |
75,000 |
46,500 |
57,000 |
36,000 |
301,500 |
201,000 |
125,625 |
100,500 |
42,000 |
25,500 |
|
|
F-2 |
NS |
UL |
UL |
37,500 |
23,000 |
28,500 |
18,000 |
151,500 |
101,000 |
63,125 |
50,500 |
21,000 |
13,000 |
|
S1 |
UL |
UL |
150,000 |
92,000 |
114,000 |
72,000 |
606,000 |
404,000 |
252,500 |
202,000 |
84,000 |
52,000 |
|
|
SM |
UL |
UL |
112,500 |
69,000 |
85,500 |
54,000 |
454,500 |
303,000 |
189,375 |
151,500 |
63,000 |
39,000 |
|
|
H-1 |
NSc |
21,000 |
16,500 |
11,000 |
7,000 |
9,500 |
7,000 |
10,500 |
10,500 |
10,500 |
10,500 |
7,500 |
NP |
|
S1 |
|||||||||||||
|
H-2 |
NSc |
21,000 |
16,500 |
11,000 |
7,000 |
9,500 |
7,000 |
10,500 |
10,500 |
10,500 |
10,500 |
7,500 |
3,000 |
|
S1 |
|||||||||||||
|
SM |
|||||||||||||
|
H-3 |
NSc |
UL |
60,000 |
26,500 |
14,000 |
17,500 |
13,000 |
25,500 |
25,500 |
25,500 |
25,500 |
10,000 |
5,000 |
|
S1 |
|||||||||||||
|
SM |
|||||||||||||
|
H-4 |
NSc,d |
UL |
UL |
37,500 |
17,500 |
28,500 |
17,500 |
72,000 |
54,000 |
40,500 |
36,000 |
18,000 |
6,500 |
|
S1 |
UL |
UL |
150,000 |
70,000 |
114,000 |
70,000 |
288,000 |
216,000 |
162,000 |
144,000 |
72,000 |
26,000 |
|
|
SM |
UL |
UL |
112,500 |
52,500 |
85,500 |
52,500 |
216,000 |
162,000 |
121,500 |
108,000 |
54,000 |
19,500 |
|
|
H-5 |
NSc,d |
UL |
UL |
37,500 |
23,000 |
28,500 |
19,000 |
72,000 |
54,000 |
40,500 |
36,000 |
18,000 |
9,000 |
|
S1 |
UL |
UL |
150,000 |
92,000 |
114,000 |
76,000 |
288,000 |
216,000 |
162,000 |
144,000 |
72,000 |
36,000 |
|
|
SM |
UL |
UL |
112,500 |
69,000 |
85,500 |
57,000 |
216,000 |
162,000 |
121,500 |
108,000 |
54,000 |
27,000 |
|
|
I-1 |
NSd,e |
UL |
55,000 |
19,000 |
10,000 |
16,500 |
10,000 |
54,000 |
36,000 |
18,000 |
18,000 |
10,500 |
4,500 |
|
S1 |
UL |
220,000 |
76,000 |
40,000 |
66,000 |
40,000 |
216,000 |
144,000 |
72,000 |
72,000 |
42,000 |
18,000 |
|
|
SM |
UL |
165,000 |
57,000 |
30,000 |
49,500 |
30,000 |
162,000 |
108,000 |
54,000 |
54,000 |
31,500 |
13,500 |
|
|
I-2 |
NSd,f |
UL |
UL |
15,000 |
11,000 |
12,000 |
NP |
36,000 |
24,000 |
12,000 |
12,000 |
9,500 |
NP |
|
S1 |
UL |
UL |
60,000 |
44,000 |
48,000 |
NP |
144,000 |
96,000 |
48,000 |
48,000 |
38,000 |
NP |
|
|
SM |
UL |
UL |
45,000 |
33,000 |
36,000 |
NP |
108,000 |
72,000 |
36,000 |
36,000 |
28,500 |
NP |
|
|
I-3 |
NSd,e |
UL |
UL |
15,000 |
10,000 |
10,500 |
7,500 |
36,000 |
24,000 |
12,000 |
12,000 |
7,500 |
5,000 |
|
S1 |
UL |
UL |
45,000 |
40,000 |
42,000 |
30,000 |
144,000 |
96,000 |
48,000 |
48,000 |
30,000 |
20,000 |
|
|
SM |
UL |
UL |
45,000 |
30,000 |
31,500 |
22,500 |
108,000 |
72,000 |
36,000 |
36,000 |
22,500 |
15,000 |
|
|
I-4 |
NSd,g |
UL |
60,500 |
26,500 |
13,000 |
23,500 |
13,000 |
76,500 |
51,000 |
25,500 |
25,500 |
18,500 |
9,000 |
|
S1 |
UL |
121,000 |
106,000 |
52,000 |
94,000 |
52,000 |
306,000 |
204,000 |
102,000 |
102,000 |
74,000 |
36,000 |
|
|
SM |
UL |
181,500 |
79,500 |
39,000 |
70,500 |
39,000 |
229,500 |
153,000 |
76,500 |
76,500 |
55,500 |
27,000 |
|
|
M |
NS |
UL |
UL |
21,500 |
12,500 |
18,500 |
12,500 |
61,500 |
41,000 |
25,625 |
20,500 |
14,000 |
9,000 |
|
S1 |
UL |
UL |
86,000 |
50,000 |
74,000 |
50,000 |
246,000 |
164,000 |
102,500 |
82,000 |
56,000 |
36,000 |
|
|
SM |
UL |
UL |
64,500 |
37,500 |
55,500 |
37,500 |
184,500 |
123,000 |
76,875 |
61,500 |
42,000 |
27,000 |
|
|
R-1h |
NSd |
UL |
UL |
24,000 |
16,000 |
24,000 |
16,000 |
61,500 |
41,000 |
25,625 |
20,500 |
12,000 |
7,000 |
|
S13R |
|||||||||||||
|
S1 |
UL |
UL |
96,000 |
64,000 |
96,000 |
64,000 |
246,000 |
164,000 |
102,500 |
82,000 |
48,000 |
28,000 |
|
|
SM |
UL |
UL |
72,000 |
48,000 |
72,000 |
48,000 |
184,500 |
123,000 |
76,875 |
61,500 |
36,000 |
21,000 |
|
|
R-2h |
NSd |
UL |
UL |
24,000 |
16,000 |
24,000 |
16,000 |
61,500 |
41,000 |
25,625 |
20,500 |
12,000 |
7,000 |
|
S13R |
|||||||||||||
|
S1 |
UL |
UL |
96,000 |
64,000 |
96,000 |
64,000 |
246,000 |
164,000 |
102,500 |
82,000 |
48,000 |
28,000 |
|
|
SM |
UL |
UL |
72,000 |
48,000 |
72,000 |
48,000 |
184,500 |
123,000 |
76,875 |
61,500 |
36,000 |
21,000 |
|
|
R-3h |
NSd |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
UL |
|
S13D |
|||||||||||||
|
S13R |
|||||||||||||
|
S1 |
|||||||||||||
|
SM |
|||||||||||||
|
R-4h |
NSd |
UL |
UL |
24,000 |
16,000 |
24,000 |
16,000 |
61,500 |
41,000 |
25,625 |
20,500 |
12,000 |
7,000 |
|
S13D |
|||||||||||||
|
S13R |
|||||||||||||
|
S1 |
UL |
UL |
96,000 |
64,000 |
96,000 |
64,000 |
246,000 |
164,000 |
102,500 |
82,000 |
48,000 |
28,000 |
|
|
SM |
UL |
UL |
72,000 |
48,000 |
72,000 |
48,000 |
184,500 |
123,000 |
76,875 |
61,500 |
36,000 |
21,000 |
|
|
S-1 |
NS |
UL |
48,000 |
26,000 |
17,500 |
26,000 |
17,500 |
76,500 |
51,000 |
31,875 |
25,500 |
14,000 |
9,000 |
|
S1 |
UL |
192,000 |
104,000 |
70,000 |
104,000 |
70,000 |
306,000 |
204,000 |
127,500 |
102,000 |
56,000 |
36,000 |
|
|
SM |
UL |
144,000 |
78,000 |
52,500 |
78,000 |
52,500 |
229,500 |
153,000 |
95,625 |
76,500 |
42,000 |
27,000 |
|
|
S-2 |
NS |
UL |
79,000 |
39,000 |
26,000 |
39,000 |
26,000 |
115,500 |
77,000 |
48,125 |
38,500 |
21,000 |
13,500 |
|
S1 |
UL |
316,000 |
156,000 |
104,000 |
156,000 |
104,000 |
462,000 |
308,000 |
192,500 |
154,000 |
84,000 |
54,000 |
|
|
SM |
UL |
237,000 |
117,000 |
78,000 |
117,000 |
78,000 |
346,500 |
231,000 |
144,375 |
115,500 |
63,000 |
40,500 |
|
|
U |
NSi |
UL |
35,500 |
19,000 |
8,500 |
14,000 |
8,500 |
54,000 |
36,000 |
22,500 |
18,000 |
9,000 |
5,500 |
|
S1 |
UL |
142,000 |
76,000 |
34,000 |
56,000 |
34,000 |
216,000 |
144,000 |
90,000 |
72,000 |
36,000 |
22,000 |
|
|
SM |
UL |
106,500 |
57,000 |
25,500 |
42,000 |
25,500 |
162,000 |
108,000 |
67,500 |
54,000 |
27,000 |
16,500 |
|
For SI: 1 square foot = 0.0929 m2.
UL = Unlimited; NP = Not Permitted; NS = Buildings not equipped throughout with an automatic sprinkler system; S1 = Buildings a maximum of one story above grade plane equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; SM = Buildings two or more stories above grade plane equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2; S13D = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.3.
Revise as follows:
Add new text as follows:
CHAPTER 6
TYPES OF CONSTRUCTION
Revise as follows:
Type IV construction is that type of construction in which the building elements are mass timber or noncombustible materials and have fire resistance ratings in accordance with Table 601. Mass timber elements shall meet the fire resistance rating requirements of this section based on either the fire resistance rating of the noncombustible protection, the mass timber, or a combination of both and shall be determined in accordance with Section 703.2 or 703.3. The minimum dimensions and permitted materials for building elements shall comply with the provisions of this section and Section 2304.11. Mass timber elements of Type IV-A, IV-B and IV-C construction shall be protected with noncombustible protection applied directly to the mass timber in accordance with Sections 602.4.1 through 602.4.3. The time assigned to the noncombustible protection shall be determined in accordance with Section 703.8 and comply with Section 722.7.
Cross laminated timber shall be labeled as conforming to PRG 320-19 as reference in Section 2303.1.4.
Exterior load bearing walls and nonload-bearing walls shall be mass timber construction, or shall be of noncombustible construction.
Exception: Exterior load-bearing walls and nonload-bearing walls of Type IV-HT Construction in accordance with Section 602.4.4.
The interior building elements, including nonload-bearing walls and partitions, shall be of mass timber construction or of noncombustible construction.
Exception: Interior building elements and nonload-bearing walls and partitions of Type IV-HT Construction in accordance with Section 602.4.4.
Combustible concealed spaces are not permitted except as otherwise indicated in Sections 602.4.1 through 602.4.4. Combustible stud spaces within light frame walls of Type IV-HT construction shall not be considered concealed spaces, but shall comply with Section 718.
In buildings of Type IV-A, IV-B and IV-C, construction with an occupied floor located more than 75 feet (22 860 mm) above the lowest level of fire department access, up to and including 12 stories or 180 feet (54 864 mm) above grade plane, mass timber interior exit and elevator hoistway enclosures shall be protected in accordance with Section 602.4.1.2. In buildings greater than 12 stories or 180 feet (54 864 mm) above grade plane, interior exit and elevator hoistway enclosures shall be constructed of non-combustible materials.
Add new text as follows:
Exceptions: Unprotected portions of mass timber ceilings and walls complying with Section 602.4.2.2.4 and the following:
Click here to view image (Equation 6-1)
where:
Utc = Total unprotected mass timber ceiling areas
Uac = Allowable unprotected mass timber ceiling area conforming to Exception 1.1 of Section 602.4.2.2.2.
Utw = Total unprotected mass timber wall areas
Uaw = Allowable unprotected mass timber wall area conforming to Exception 1.2 of Section 602.4.2.2.2.
Renumber and Revise as follows:
602.4.1 to 602.4.4.1 Fire-retardant-treated wood in exterior walls. Fire-retardant-treated wood framing and sheathing complying with Section 2303.2 shall be permitted within exterior wall assemblies not less than 6 inches (152 mm) in thickness with a 2-hour rating or less.
602.4.2 to 602.4.4.2 Cross-laminated timber in exterior walls. Cross-laminated timber complying with Section 2303.1.4 shall be permitted within exterior wall assemblies not less than 6 inches (152 mm) in thickness with a 2-hour rating or less, provided the exterior surface of the cross-laminated timber is protected by one of the following:
602.4.3 to 602.4.4.3 Exterior structural members. Where a horizontal separation of 20 feet (6096 mm) or more is provided, wood columns and arches conforming to heavy timber sizes complying with Section 2304.11 shall be permitted to be used externally.
TABLE 601
FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (HOURS)
|
BUILDING ELEMENT |
TYPE I |
TYPE II |
TYPE III |
TYPE IV |
TYPE V |
|||||||
|
A |
B |
A |
B |
A |
B |
A |
B |
C |
HT |
A |
B |
|
|
Primary structural framef (see Section 202) |
3a,b |
2a,b |
1b |
0 |
1b |
0 |
3a |
2a |
2a |
HT |
1b |
0 |
|
Bearing walls Exteriore,f Interior |
3 3a |
2 2a |
1 1 |
0 0 |
2 1 |
2 0 |
3 3 |
2 2 |
2 2 |
2 1/HT |
1 1 |
0 0 |
|
Nonbearing walls and partitions Exterior |
See Table 602 |
|||||||||||
|
Nonbearing walls and partitions Interiord |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
See Section 2304.11. 2 |
0 |
0 |
|
Floor construction and associated secondary members (see Section 202) |
2 |
2 |
1 |
0 |
1 |
0 |
2 |
2 |
2 |
HT |
1 |
0 |
|
Roof construction and associated secondary members (see Section 202) |
1 ½b |
1b,c |
1b,c |
0c |
1b,c |
0 |
1 ½ |
1 |
1 |
HT |
1b,c |
0 |
For SI: 1 foot = 304.8 mm.
TABLE 602
FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCE a,d,g
|
FIRE SEPARATION DISTANCE = X (feet) |
TYPE OF CONSTRUCTION |
OCCUPANCY GROUP He |
OCCUPANCY GROUP F-1, M, S-1f |
OCCUPANCY GROUP A, B, E, F-2, I, Ri, S-2, Uh |
|
X 5b |
All |
3 |
2 |
1 |
|
5 <= X < 10 |
IA, IV-A Others |
3 2 |
2 1 |
1 1 |
|
10 <= X < 30 |
IA, IB, IV-A, IV-B IIB, VB Others |
2 1 1 |
1 0 1 |
1c 0 1c |
|
X >= 30 |
All |
0 |
0 |
0 |
For SI: 1 foot = 304.8 mm.
CHAPTER 7
FIRE AND SMOKE PROTECTION FEATURES
Add new text as follows:
The noncombustible protection time contribution shall be determined by subtracting the fire resistance time, in minutes, of Test Assembly 1 from the fire resistance time, in minutes, of Test Assembly 2.
Add new text as follows:
Sealants shall meet the requirements of ASTM C920. Adhesives shall meet the requirements of ASTM D3498.
Exception: Sealants or adhesives need not be provided where they are not a required component of a tested fire-resistance-rated assembly.
Revise as follows:
Exceptions:
Revise as follows:
Add new text as follows:
TABLE 722.7.1(1)
PROTECTION REQUIRED FROM NONCOMBUSTIBLE COVERING MATERIAL
|
REQUIRED FIRE-RESISTANCE RATING OF BUILDING ELEMENT PER TABLE 601 AND TABLE 602 (hours) |
MINIMUM PROTECTION REQUIRED FROM NONCOMBUSTIBLE PROTECTION (minutes) |
|
1 |
40 |
|
2 |
80 |
|
3 or more |
120 |
TABLE 722.7.1(2)
PROTECTION PROVIDED BY NONCOMBUSTIBLE COVERING MATERIAL
|
NONCOMBUSTIBLE PROTECTION |
PROTECTION CONTRIBUTION (minutes) |
|
½-inch Type X gypsum board |
25 |
|
5/8-inch Type X gypsum board |
40 |
Exception: The third layer, where determined necessary by Section 722.7, shall be permitted to be attached with 1-inch (25 mm) No. 6 Type S drywall screws to furring channels in accordance with AISI S220.
CHAPTER 14
EXTERIOR WALLS
Revise as follows:
CHAPTER 17
SPECIAL INSPECTIONS AND TESTS
Add new text as follows:
Add new table as follows:
TABLE 1705.5.3
REQUIRED SPECIAL INSPECTION OF MASS TIMBER CONSTRUCTION
|
TYPE |
CONTINUOUS SPECIAL INSPECTION |
PERIODIC SPECIAL INSPECTION |
||
|
1. |
Inspection of anchorage and connections of mass timber construction to timber deep foundation systems. |
- |
X |
|
|
2. |
Inspect erection of mass timber construction. |
- |
X |
|
|
3. |
Inspection of connections where installation methods are required to meet design loads. |
|||
|
Threaded fasteners |
Verify use of proper installation equipment. |
- |
X |
|
|
Verify use of pre-drilled holes where required. |
- |
X |
||
|
Inspect screws, including diameter, length, head type, spacing, installation angle and depth. |
- |
X |
||
|
Adhesive anchors installed in horizontal or upwardly inclined orientation to resist sustained tension loads. |
X |
- |
||
|
Adhesive anchors not defined in preceding cell. |
- |
X |
||
|
Bolted connections. |
- |
X |
||
|
Concealed connections. |
- |
X |
||
Add new text as follows:
CHAPTER 23
WOOD
Add new text as follows:
CHAPTER 31
SPECIAL CONSTRUCTION
Revise as follows:
Exception: Plastic less than 30 feet (9144 mm) above any floor used in greenhouses, where occupancy by the general public is not authorized, and for aquaculture pond covers is not required to meet the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701.
Revise as follows:
CHAPTER 35
REFERENCED STANDARDS
Revise as follows:
|
APA |
APA - Engineered Wood Association 7011 South 19th Street Tacoma WA 98466-7400 |
ANSI/APA PRG 320 "19: Standard for Performance-rated Cross-laminated Timber
602.4, 2303.1.4
Add new text as follows:
|
ASTM |
ASTM International 100 Barr Harbor Drive, P.O. Box C700 West Conshohocken PA 19428-2959 |
D3498-03(2011): Standard Specification for Adhesives for Field-Gluing Plywood to Lumber Framing for Floor Systems
703.9
|
AWC |
American Wood Council 222 Catoctin Circle SE, Suite 201 Leesburg, VA 20175 |
ANSI/AWC SDPWS-2021: Special Design Provisions for Wind and Seismic
202, 2305.1, 2305.2, 2305.3, 2306.1, 2306.2, 2306.3, Table 2306.3(1), Table 2306.3(3), 2307.1
|
AWC |
American Wood Council 222 Catoctin Circle SE, Suite 201 Leesburg, VA 20175 |
APPENDIX D
FIRE DISTRICTS
Revise Appendix D as follows:
Exceptions:
Click here to view image
GEORGIA STATE MINIMUM STANDARD BUILDING CODE
(INTERNATIONAL BUILDING CODE WITH GEORGIA STATE AMENDMENTS)
The INTERNATIONAL BUILDING CODE, 2018 Edition, published by the International Code Council, when used in conjunction with these Georgia State Amendments, shall constitute the official Georgia State Minimum Standard Building Code.
GEORGIA STATE AMENDMENTS
CODE REFERENCE:
Note: By Georgia law, the International Existing Building Code is a permissive or optional State Minimum Standard Code. Consequently, the provisions contained in the International Existing Building Code are not mandatory or applicable unless specifically referenced in the adopting ordinance of local governments.
APPENDICES:
Appendices are not enforceable unless they are specifically referenced in the body of the code or adopted by the Department of Community Affairs or the authority having jurisdiction.
SCOPE:
The provisions of the Georgia State Minimum Standard Building Code shall apply to the construction, alteration, relocation, enlargement, replacement, repair, equipment, use and occupancy, location, maintenance, removal and demolition of every building or structure or any appurtenances connected or attached to such buildings or structures.
Exception #1: Detached one- and two-family dwellings and multiple single-family dwellings (townhouses separated by a 2-hour fire-resistance-rated wall assembly) not more than three stories above grade plane in height with a separate means of egress and their accessory structures shall comply with the Georgia State Minimum Standard One and Two Family Dwelling Code (International Residential Code for One- and Two-Family Dwellings with Georgia State Amendments).
Exception #2: The following table titled 'Codes Reference Guide' establishes specific primary and supplementary code applications and is to be applied by the authority having jurisdiction.
|
CODES REFERENCE GUIDE |
||
|
Area |
Primary |
Supplement |
|
Occupancy Classification |
LSC |
IBC |
|
Building Construction Types including allowable height, allowable building areas, and the requirements for sprinkler protection related to minimum building construction types. |
IBC |
LSC |
|
Means of Egress |
LSC |
NONE |
|
Standpipes |
IBC |
IFC |
|
Interior Finish |
LSC |
NONE |
|
HVAC Systems |
IMC |
NONE |
|
Vertical Openings |
LSC |
NONE |
|
Sprinkler Systems minimum construction standard |
LSC |
NONE |
|
Fire Alarm Systems |
LSC |
NONE |
|
Smoke Alarms and Smoke Detection Systems |
State Statute and LSC |
NONE |
|
Portable Fire Extinguishers |
IFC |
NONE |
|
Cooking Equipment |
LSC and NFPA 96 |
NONE |
|
Fuel Fired Appliances |
IFGC |
NFPA 54 |
|
Liquid Petroleum Gas |
NFPA 58 |
NFPA 54 |
|
Compressed Natural Gas |
NFPA 52 |
NONE |
*Revise the International Building Code, 2018 Edition, to read as follows:
CHAPTER 1
SCOPE AND ADMINISTRATION
*Delete Chapter 1 'Scope and Administration' entirely without substitution. Chapter 1 to remain in the Code as a reference guide for local governments to use in development of their own Administrative Procedures.
(Effective January 1, 2020)
CHAPTER 2
DEFINITIONS
SECTION 202
DEFINITIONS
*Add definition of 'Elevator Door Opening Protective Device' to read as follows:
ELEVATOR DOOR OPENING PROTECTIVE DEVICE. Any device that either independently or in conjunction with the (elevator) door assembly allows the device(s) to meet the requirements of Sections 716.5.3 716, 716.2.2.1 and 3008.6.3.
(Effective January 1, 2020)
CHAPTER 3
OCCUPANCY AND USE CLASSIFICATION
SECTION 308
INSTITUTIONAL GROUP I
*Add a new Section 308.3.3 'Assisted living communities' to read as follows:
(Effective January 1, 2020)
CHAPTER 4
SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
SECTION 415
GROUPS H-1, H-2, H-3, H-4 AND H-5
*Revise Section [F] 415.9.2 'Liquefied petroleum gas facilities' to read as follows:
CHAPTER 5
GENERAL BUILDING HEIGHTS AND AREAS
SECTION 504
BUILDING HEIGHT AND NUMBER OF STORIES
*Revise Table 504.4 'Allowable Number of Stories Above Grade Planea,b' for the Occupancy Classification "I-1 Condition 2" as shown and add a new footnote "i" to read as follows:
TABLE 504.4
ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE a, b
|
OCCUPANCY CLASSIFICATION |
TYPE OF CONSTRUCTION |
|||||||||
|
SEE FOOTNOTES |
TYPE 1 |
TYPE II |
TYPE III |
TYPE IV |
TYPE V |
|||||
|
A |
B |
A |
B |
A |
B |
HT |
A |
B |
||
|
I-1 Condition 2 |
NSd,e |
NP |
NP |
NP |
NP |
NP |
NP |
NP |
NP |
NP |
|
S j |
UL |
10 |
3 |
2 |
2 |
1 |
2 |
2 |
1 |
|
(Remainder of table unchanged)
(Effective January 1, 2020)
CHAPTER 7
FIRE AND SMOKE PROTECTION FEATURES
SECTION 706
FIRE WALLS
*Revise Section 706.2 'Structural stability' to read as follows:
Exception: In Seismic Design Categories D through F, where double fire walls are used in accordance with NFPA 221, floor and roof sheathing not exceeding 3/4 inch (19.05 mm) thickness shall be permitted to be continuous through the wall assemblies of light frame construction.
(Effective January 1, 2020)
*Delete Exception to Section 706.3 'Materials' without substitution.
(Effective January 1, 2020)
SECTION 713
SHAFT ENCLOSURES
*Add new Section 713.14.1 'Designated floor lobbies for elevator return' to read as follows:
Exceptions:
(Effective January 1, 2020)
CHAPTER 9
FIRE PROTECTION AND LIFE SAFETY SYSTEMS
SECTION 903
AUTOMATIC SPRINKLER SYSTEMS
*Revise Section [F] 903.2.8 'Group R' to add exception to read as follows:
Exception: Group R-1 and R-2 occupancies which meet the exceptions allowed by the Rules and Regulations of the Safety Fire Commissioner Chapter 120-3-3 'Rules and Regulations for the State Minimum Fire Safety Standards' are exempt from this requirement.
(Effective January 1, 2020)
*Revise Section [F] 903.2.8.1 'Group R-3' to read as follows:
(Effective January 1, 2020)
*Revise Section [F] 903.2.8.2 'Group R-4, Condition 1' to read as follows:
(Effective January 1, 2020)
*Revise Section [F] 903.2.8.4 'Care facilities' to read as follows:
(Effective January 1, 2020)
*Revise Section [F] 903.3.1.3 'NFPA 13D sprinkler systems' to read as follows:
(Effective January 1, 2020)
SECTION 909
SMOKE CONTROL SYSTEMS
*Delete Section 909.21.1 'Pressurization requirements' entirely and substitute to read as follows:
Exception: In existing buildings, when testing existing elevator pressurization systems, they shall be certified to ensure a minimum positive pressure, subject to the approval of the authority having jurisdiction. This pressure shall be measured at the midpoint of each hoistway door, with all elevator cars at the floor of recall and all hoistway doors on the floor of recall open and all other hoistway doors closed. The opening and closing of hoistway doors at each level must be demonstrated during this test. The supply air intake shall be from an outside, uncontaminated source.
(Effective January 1, 2020)
CHAPTER 11
ACCESSIBILITY
*Delete Chapter 11 'Accessibility' entirely without substitution.
{Cross-reference in State law: Title 30, Chapter 3 of the Official Code of Georgia Annotated (O.C.G.A) and the Rules and Regulations of the Georgia Safety Fire Commissioner.}
(Effective January 1, 2020)
CHAPTER 14
EXTERIOR WALLS
SECTION 1404
INSTALLATION OF WALL COVERINGS
*Add new Section [BS] 1404.19 'Installation of wall coverings' to read as follows:
[BS] 1404.19 Installation of wall coverings. Except masonry veneer, wall cladding shall be installed a minimum of 6 inches above the finished earth grade, or a minimum of 2 inches above paved areas to provide a clear, visible inspection gap.
(Effective January 1, 2020)
CHAPTER 17
SPECIAL INSPECTIONS AND TESTS
SECTION 1701
GENERAL
*Add new Section 1701.2 'Construction documents' to read as follows:
"Special inspection reports and a final report in accordance with Section 1704.2.4 shall be submitted to the building official prior to the time that phase of the work is approved for occupancy."
(Effective January 1, 2020)
*Add new Section 1701.3 'Guidelines' to read as follows:
(Effective January 1, 2020)
SECTION 1704
SPECIAL INSPECTIONS AND TESTS, CONTRACTOR RESPONSIBILITY AND STRUCTURAL OBSERVATION
*Revise Section 1704.2 'Special inspections and tests' to read as follows:
Exceptions:
(Effective January 1, 2020)
*Revise Section 1704.2.1 'Special inspector qualifications' to read as follows:
The registered design professional in responsible charge and engineers of record involved in the design of the project are permitted to act as the approved agency and their personnel are permitted to act as the special inspector for the work designed by them, provided they qualify as special inspectors.
(Effective January 1, 2020)
*Add new Table 1704.2 'Minimum Special Inspector Qualifications' to read as follows:
|
TABLE 1704.2 MINIMUM SPECIAL INSPECTOR QUALIFICATIONS |
|||
|
Category of Testing and Inspection |
Minimum Qualifications (refer to key at end of Table) |
||
|
Shop Testing or Inspection |
Field Testing or Inspection |
Review Testing, Certification & Lab Reports |
|
|
1704.2.5 Inspection of Fabricators |
|||
|
Pre-cast concrete |
A, C, E |
||
|
Structural steel construction |
C, F, G |
||
|
Wood construction |
A |
||
|
Cold formed metal construction |
A |
||
|
1705.2, 1705.10, 1705.11 & 1705.12 Steel Construction |
|||
|
Verification of welding consumables, filler metals, procedure specifications, procedure qualification records and personnel performance qualification records |
C, F |
||
|
Nondestructive testing of welding |
G |
G |
|
|
Inspection of welding |
C, F |
C, F |
|
|
Verification of fabricator and erector documents as listed in AISC 360, chapter N, paragraph 3.2 |
A, C |
||
|
Material verification of weld filler materials |
C, F |
||
|
Inspection of high strength bolting and steel frame joint details |
A, C |
||
|
Inspection of embedment |
A, C, F |
||
|
Inspection of steel elements of composite construction |
A, C, F |
||
|
Verification of reinforcing steel, cold formed steel deck and truss materials |
A, C, F |
||
|
Inspection of reinforcing steel, cold formed steel deck and trusses |
A, C |
||
|
1705.3 & 1705.12 Concrete Construction |
|||
|
Reinforcing placement, cast-in-place bolts, post installed anchors concrete and shotcrete placement and curing operations. Inspection of formwork for shape, location and dimensions |
A, C, H |
||
|
Pre-stressing steel installation |
A, C, D, E |
||
|
Erection of pre-cast concrete members |
A, C, H |
||
|
Concrete field sampling and field testing |
A, J |
||
|
Concrete strength testing |
P |
||
|
Review certified mill reports |
A, C |
||
|
Verify use of required design mix |
A, I, J, H, C |
||
|
Pre-stressed (pre-tensioned) concrete force application |
A, C, E |
||
|
Post-tensioned concrete force application |
A, C, D |
||
|
Review of in-situ concrete strength, prior to stressing of tendons in post-tensioned concrete and prior to removal of shores and forms from beams and structural slabs |
A, C, D, H |
||
|
Reinforcing steel weldability, reinforcing welding, weld filler material |
C, F |
||
|
Testing of welding of reinforcing steel |
G |
||
|
1705.4 Masonry |
|||
|
Verification of f'm and f'AAC |
A, C, L, M |
||
|
Mortar joint construction, grout protection and placement, materials proportion, type/size/location of reinforcement, structural elements, anchorage, and connectors |
A, C, K |
||
|
Sampling/testing of grout/mortar specimens |
A, C, L, M |
||
|
Observe preparation of masonry prisms for testing of compressive strength of masonry, f'm and f'AAC |
A, C, K, L, M |
||
|
Inspection of welding of reinforcing steel |
C, F |
||
|
Testing of welding of reinforcing steel |
G |
||
|
1705.6 & 1804 Soils |
|||
|
Observe site preparation, fill placement testing of compaction for compliance with the construction documents for the project |
A, C, I, N |
||
|
Observe test bearing materials below shallow foundations for ability to achieve design bearing capacity |
A, C, N, I (Level III) |
||
|
Review compaction testing for compliance with the construction documents for the project |
A |
||
|
1705.5, 1705.10, 1705.11 & 1705.12 Wood Construction |
|||
|
Observe structural panel sheathing, size of framing members, nail or staple diameter and length, number of fastener lines, and spacing of fastener lines and fasteners for compliance with construction documents for the project |
A |
||
|
Observe temporary and permanent truss member restraint/bracing, field gluing of elements. Observe bolting, anchoring or other fastening of: shear walls, diaphragms, drag struts, braces and hold-downs |
A |
||
|
1705.7, 1705.8, 1705.9 & 1810 Pile and Pier Foundations |
|||
|
Observe installation |
A, N |
||
|
Observe load tests |
A |
||
|
1705.13 Sprayed Fire-Resistant Materials |
|||
|
Observe surface conditions, application, average thickness and density of applied material, and cohesive/adhesive bond |
A, C |
||
|
1705.14 Mastic and Intumescent Fire-Resistant Coatings |
|||
|
Observe application compliance with AWCI 12-B |
A, C |
||
|
1705.15 Exterior Insulation and Finish Systems |
|||
|
Inspect EIFS systems |
A, B, C, O |
||
|
1705.1 Special Cases |
|||
|
Work of unusual or special nature |
A, B, O |
||
|
1705.16 Fire-Resistant Penetrations and Joints |
See Requirements of IBC Sections 1705.16.1 and 1705.16.2 |
||
|
1705.17 Smoke Control |
See Requirements of IBC Section 1705.17.2 |
||
|
1705.10, 1705.11 & 1705.12 Seismic and Wind Resistance |
|||
|
Periodic inspection of fabrication, installation and/or anchorage of building systems and components |
A |
||
|
KEY: A. Georgia Professional Engineer (GA PE) competent in the specific task area or graduate of accredited engineering/engineering technology program under the direct supervision of a GA PE. B. Georgia Registered Architect (GA RA) or graduate of accredited architecture/architecture technology program under the direction of a GA RA. C. International Code Council (ICC) Special Inspector Certification specific to the particular material and testing methodology applicable to each Category of Testing and Inspection listed in the table. D. Post-tensioning Institute (PTI) Certification, Level 2, bonded or unbonded as applicable. E. Pre-stressed Concrete Institute (PCI) Certified Inspector. F. American Welding Society (AWS) Certified Welding Inspector (CWI) or AWS Certified Associate Welding Inspector working under the direct on-site supervision of a CWI. G. American Society for Nondestructive Testing (ASNT) Level II certification, or a Level III certification if previously certified as a Level II in the particular material and testing methodology applicable to each Category of Testing and Inspection listed in the table. H. American Concrete Institute (ACI) Concrete Construction Special Inspector. I. National Institute for Certification in Engineering Technologies (NICET) Level II or higher certification specific to the particular material and testing methodology applicable to each Category of Testing and Inspection listed in the table. J. ACI Concrete Field Testing Technician with Grade 1 certification. K. Georgia Concrete and Products Association (GC&PA) - Masonry Association of Georgia (MAG) Masonry Construction Inspector Certification. L. National Concrete Masonry Association (NCMA) Concrete Masonry Testing Procedures certification. M. GC&PA - MAG Masonry Testing Technician certification. N. NICET Certified Engineering Technologist (CT). O. Other Qualified Special Inspector as approved by the Building Official. P. American Concrete Institute (ACI) Strength Testing Technician. Notes: 1. The Special Inspector shall meet one of the minimum qualifications listed for the applicable Category of Testing and Inspection. 2. Materials testing shall be done by an Approved Testing Agency meeting the requirements of IBC Section 1703 and ASTM E 329. |
|||
(Effective January 1, 2020)
*Revise Section 1704.2.4 'Report requirement' to read as follows:
(Effective January 1, 2020)
CHAPTER 18
SOILS AND FOUNDATIONS
SECTION 1810
DEEP FOUNDATIONS
*Revise Section 1810.3.2.6 'Allowable stresses' title to read as follows:
(Effective January 1, 2020)
*Revise Table 1810.3.2.6 'Allowable Stresses for Materials Used in Deep Foundation Elements' title and item 4 'Other conditions' to read as follows:
TABLE 1810.3.2.6
ALLOWABLE AXIAL STRESSES FOR MATERIALS USED IN DEEP FOUNDATION ELEMENTS
|
MATERIAL TYPE AND CONDITION |
MAXIMUM ALLOWABLE AXIAL STRESSa |
|
4. Non-prestressed reinforcement in tension Within micropiles Other conditions For load combinations not including wind or seismic loads For load combinations including wind or seismic loads |
0.6 fy 0.5 fy <= 24,000 30,000 psi 0.5 fy <=40,000 psi |
Remainder of table and footnotes remain unchanged.
(Effective January 1, 2020)
CHAPTER 29
PLUMBING SYSTEMS
SECTION 2902
MINIMUM PLUMBING FACILITIES
*Delete the requirements for "service sinks" from Table [P] 2902.1 'Minimum Number of Required Plumbing Fixturesa' without substitution.
(Effective January 1, 2020)
CHAPTER 30
ELEVATORS AND CONVEYING SYSTEMS
SECTION 3001
GENERAL
*Revise Table 3001.3 'Elevators and Conveying Systems and Components' under 'STANDARDS' for Elevators, escalators, dumbwaiters, moving walks, material lifts to add the following new standards to read as follows:
TABLE 3001.3
ELEVATORS AND CONVEYING SYSTEMS AND COMPONENTS
|
TYPE |
STANDARDS |
|
Elevators, escalators, dumbwaiters, moving walks, material lifts |
ANSI/ASSE A10.4, ANSI/ASSE A10.5 |
(Effective January 1, 2020)
SECTION 3002
HOISTWAY ENCLOSURES
*Revise Section 3002.4 'Elevator car to accommodate ambulance stretcher' to add a new exception at the end of the section to read as follows:
Exception: Elevators with 50 feet or less of travel serving only one residence of a one- or two-family dwelling or townhouse shall be in compliance with ASME A17.1 as currently adopted and amended by the Georgia Office of Safety Fire Commissioner.
(Effective January 1, 2020)
SECTION 3005
MACHINE ROOMS
*Delete Section 3005.4 'Machine rooms, control rooms, machinery spaces and control spaces' and substitute to read as follows:
Exception: Where machine rooms and machinery spaces do not meet the required fire-resistance rating, they shall require sprinklers and shunt trip breaker in accordance with NFPA 72.
(Effective January 1, 2020)
*Revise Section 3005.5 'Shunt trip' to read as follows:
(Effective January 1, 2020)
CHAPTER 34
EXISTING STRUCTURES
*Revise the title of Chapter 34 'Reserved' to read as 'Existing Buildings' and carry forward all the provisions from Chapter 34 'Existing Buildings' of the 2012 International Building Code. (Effective January 1, 2020)
SECTION 3401
GENERAL
*Add new Section 3401.7 'Existing system conformance' to read as follows:
(Effective January 1, 2020)
SECTION 3408
CHANGE OF OCCUPANCY
*Add new Section 3408.2.1 'Assisted living communities' to read as follows:
(Effective January 1, 2020)
CHAPTER 35
REFERENCED STANDARDS
*Revise Chapter 35 'Referenced Standards' to add the following new reference standards to read as follows:
|
ACEC/GA |
American Council of Engineering Companies of Georgia Peachtree Center, Harris Tower, Suite 700 233 Peachtree Street Atlanta, GA 30303 |
|
|
Standard reference number |
Title |
Referenced in code section number |
|
ACEC/SEAOG SI GL 01-19 |
Georgia Special Inspections Guidelines (http://www.seaog.org/si.html) |
1704.2.1, GA Amendments |
|
ASTM |
ASTM International 100 Barr Harbor Drive West Conshohocken, PA 19428-2859 |
|
|
Standard reference number |
Title |
Referenced in code section number |
|
E 329-11c |
Standard Specification for Agencies Engaged in Construction Inspection, Testing, or Special Inspection |
1704.2.1, GA Amendments |
|
ANSI/ASSE |
American Society of Safety Engineers 520 N. Northwest Highway Park Ridge, IL 60068 |
|
|
Standard reference number |
Title |
Referenced in code section number |
|
A10.4-2016 A10.5-2013 |
Safety Requirements for Personnel Hoist and Employee Elevators on Construction and Demolition Sites Safety Requirements for Material Hoists |
Table 3001.3, GA Amendments Table 3001.3, GA Amendments |
Remainder of reference standards remain unchanged.
(Effective January 1, 2020)
APPENDIX O
DISASTER RESILIENT CONSTRUCTION
*The Department of Community Affairs hereby adopts Appendix O 'Disaster Resilient Construction' as optional. This document can be downloaded at https://dca.ga.gov/local-government-assistance/construction-codes-industrialized-buildings/construction-codes.
(Effective: January 1, 2020)
Click here to view image
GEORGIA STATE INTERNATIONAL BUILDING CODE
APPENDIX O
DISASTER RESILIENT CONSTRUCTION
The INTERNATIONAL BUILDING CODE, 2018 Edition, published by the International Code Council, when used in conjunction with the Georgia State Amendments to the INTERNATIONAL BUILDING CODE, 2028 Edition and Appendix O Disaster Resilient Construction, shall constitute the official Georgia State Minimum Standard Building Code.
FORWARD
Introduction
The Department of Community Affairs (DCA) was awarded a grant through the U.S. Department of Housing and Urban Development (HUD) to develop Disaster Resilient Building Code (DRBC) Appendices for the International Building Code (IBC) and the International Residential Code (IRC). The DRBC Appendices are optional regulations that local jurisdictions may adopt, in whole or in part, through local ordinance. A task force of stakeholders was appointed to look for opportunities to improve any code provisions relating to damage from hurricane, flood, and tornado disasters. In addition to the approved recommendations from the task force, the state has developed and will conduct a comprehensive training program for code enforcement officials on the importance, implementation and enforcement of the Disaster Resilient Construction Appendices.
The meetings for the Disaster Resilient Building Code Appendices Task Force were open to the public, interested individuals and organizations that desired participation. The technical content of currently published documents on flooding, high-wind construction, and storm shelters, were used and referenced. Those publications included documents of the International Code Council (ICC), American Society of Civil Engineers (ASCE), the Federal Emergency Management Agency (FEMA), Mitigation Assessment Team (MAT) Program, Georgia Emergency Management Agency/Homeland Security (GEMA), APA - The Engineered Wood Association, National Institute of Standards and Technology (NIST), National Oceanic and Atmospheric Administration (NOAA), National Science Foundation (NSF), The State of Florida, American Forest & Paper Association's American Wood Council, Southern Forest Products Association, NAHB Research Center, Insurance Institute for Business & Home Safety, and the Federal Alliance for Safe Homes.
Adoption
Local jurisdictions may adopt this entire appendix with chosen options or specific sections that apply to their communities through a local ordinance. The adopting ordinance must also be filed on record with DCA. A sample ordinance has been included in this document to assist the local jurisdictions with the adoption process. Recommended training is being offered to assist code enforcement officials in the implementation and enforcement of the appendices documents. Contact DCA at (404) 679-3118 or www.dca.ga.gov for more information.
Neither The Disaster Resilient Building Code Appendices Task Force, its members nor those participating in the development of Appendix O Disaster Resilient Construction accept any liability resulting from compliance or noncompliance with the provisions of Appendix O Disaster Resilient Construction.
The 2012 Disaster Resilient Building Code (DRBC) Appendices Task Force was charged with the development of two appendices. One appendix is for the International Residential Code and the other appendix is for the International Building Code. These two appendices look for opportunities to improve any provisions relating to hurricane, flood, and tornado disasters. In addition to improving existing provisions in the codes, the task force also developed new provisions to be included in the appendices that address these issues. These appendices contain increased construction requirements for disaster resilience and are intended to be made available for adoption by local jurisdictions in the State of Georgia.
These appendices have reasonable and substantial connection with the public health, safety, and general welfare. In addition, the financial impact and costs associated with these appendices have been taken into consideration.
Members:
Mr. Gregori Anderson, Chairman, States Codes Advisory Committee (SCAC)
Mr. David L. Adams, Vice Chairman, States Codes Advisory Committee (SCAC)
Mr. Bill Abballe, AIA, American Institute of Architects (AIA) - Georgia Chapter
Mr. John Hutton, P.E., S.E., American Council of Engineering Companies of Georgia (ACEC/G)
Mr. Ron Anderson, Code Consultant
Mr. Lamar Smith, Home Builders Association of Georgia (HBAG)
Mr. Thomas Harper, Georgia State Inspectors Association (GSIA)
Mr. Tom Buttram, Building Officials Association of Georgia (BOAG)
Capt. Zane Newman, Georgia State Fire Marshal's Office (Local Fire Official)
Mr. Terry Lunn, Georgia Emergency Management Agency (GEMA)
Mr. Alan Giles, CFM, Georgia Department of Natural Resources (EPD / Floodplain Management Unit)
Mr. Tony Hebert, HUD Georgia State Representative (Region IV Office)
Mr. Jim C. Beck, Sr., Georgia Underwriting Association
Mr. Tim Thornton, Georgia Association of Realtors (GAR)
Mr. Steve Harrison, Building Owners and Managers Association - Georgia (BOMA)
Mr. Tom Aderhold, Georgia Apartment Association (GAA)
Mr. Tim Bromley, Accessibility Consultant - Georgia State ADA Coordinator's Office
Mayor Mark Mathews, Georgia Municipal Association (GMA)
Commissioner Jeff Long, Association of County Commissioners of Georgia (ACCG)
Ad Hoc Subcommittee:
Mr. Tom Buttram, Chairman, DRBC Task Force Liaison (BOAG)
Mr. Ron Anderson, Vice Chairman, Code Consultant
Mr. Stephen V. Skalko, Concrete Industry
Mr. Jeffrey B. Stone, Wood Industry (AWC)
Mr. Robert Wills, Steel Industry (AISC)
Mr. Tom Cunningham, PhD., Residential Building Design
Mr. Duncan J. Hastie, P.E., Disaster Mitigation
DCA Staff:
Mr. Ted Miltiades, Director of Construction Codes & Industrialized Buildings
Mrs. Deirdre "Dee" Leclair, DRBC Grant Project Manager
Mr. Max Rietschier, Lead Codes Consultant
Mr. Bill Towson, 2012 International Residential Code Task Force Liaison, Code Consultant
Mr. Calvin Jordan, 2012 International Building Code Task Force Liaison, Code Consultant
How to Use Appendix O Disaster Resilient Construction
The appendix may be adopted in whole or in part by Local Jurisdictions to fit the needs of their community. The following sample ordinance has been provided to aid in the process of identifying Chapters and Sections of the appendix that may be adopted. The format easily allows for choosing to adopt, revise or delete individual Chapters and Sections. Download the MS Word (.doc) version from the DCA website to take advantage of the dropdown menu choices and edit ability features of the document. Note that in Chapter 3, choose one of three options for flood elevation. Only one option may be chosen and that option must be higher than what has been previously adopted and enforced by the jurisdiction. Also note that in Chapter 4, choose one of three options for increased wind load. Only one option may be chosen and that option must be higher than what has been previously adopted and enforced by the jurisdiction. The Sample Ordinance document takes into account the flood elevation option in Chapter 3 and the wind load option in Chapter 4 of this appendix.
SAMPLE ORDINANCE FOR ADOPTION OF
GEORGIA STATE INTERNATIONAL BUILDING CODE
APPENDIX O
DISASTER RESILIENT CONSTRUCTION
ORDINANCE NO. _______
An ordinance of the [JURISDICTION] adopting the latest edition as adopted and amended by the Georgia Department of Community Affairs of Appendix O Disaster Resilient Construction regulating and governing the mitigation of hazard to life and property from natural weather related disasters, high-wind damages, flooding, and establishing construction standards for storm shelters in the [JURISDICTION]; providing for the issuance of permits and collection of fees therefore; repealing Ordinance No. __ of the [JURISDICTION] and all other ordinances or parts of the laws in conflict therewith.
The [GOVERNING BODY] of the [JURISDICTION] does ordain as follows:
Choose an item. CHAPTER AO1 SCOPE AND ADMINISTRATION Choose an item.
Choose an item. SECTION AO101 ADMINISTRATION Choose an item.
Choose an item. AO101.1 Purpose Choose an item.
Choose an item. AO101.2 Objectives Choose an item.
Choose an item. AO101.3 Scope Choose an item.
AO101.3.1 Insert [Name Of Jurisdiction] for [NAME OF JURISDICTION].
Choose an item. AO101.4 Violations Choose an item.
Insert [Name Of Jurisdiction] for [NAME OF JURISDICTION].
Choose an item. SECTION AO102 APPLICABILITY Choose an item.
Choose an item. AO102.1 General Choose an item.
Choose an item. AO102.2 Other laws Choose an item.
Choose an item. AO102.3 Referenced codes and standards Choose an item.
Choose an item. SECTION AO103 POST DISASTER EVENT INSPECTIONS GUIDLINES Choose an item.
Choose an item. AO103.1 Inspections Choose an item.
Choose an item. AO103.1.1 Right of entry Choose an item.
Choose an item. AO103.2 Types of inspections Choose an item.
Choose an item. AO103.3 Post disaster building safety evaluation chart Choose an item.
Choose an item. Figure AO103.3 Post Disaster Building Safety Evaluation Chart Choose an item.
Choose an item. AO103.4 Evaluation Forms Choose an item.
Insert [Name Of Jurisdiction] for [NAME OF JURISDICTION].
Choose an item. AO103.5 Placement and remove of placards Choose an item.
Choose an item. CHAPTER AO2 DEFINITIONS Choose an item.
Choose an item. SECTION AO201 GENERAL Choose an item.
Choose an item. AO201.1 Scope Choose an item.
Choose an item. AO201.2 Terms defined in other codes Choose an item.
Choose an item. AO201.3 Terms not defined Choose an item.
Choose an item. SECTION AO202 DEFINITIONS Choose an item.
Choose an item. CHAPTER AO3 FLOOD-RESISTANT CONSTRUCTION Choose an item.
Choose an item. SECTION AO301 HAZARD IDENTIFICATION Choose an item.
Choose an item. AO301.1 Identification of flood hazard areas Choose an item.
Insert [Name Of Jurisdiction] for [NAME OF JURISDICTION].
Insert [Date of Issuance] for [DATE OF ISSUANCE].
Choose an item. SECTION AO302 SCOPE Choose an item.
Choose an item. AO301.1 Flood Loads Choose an item.
Choose an item. FLOOD ELEVATION OPTION Choose an item. Choose an item.
Choose an item. SECTION AO303 FLOOD DAMAGE-RESISTANT MATERIALS Choose an item.
Choose an item. AO303.1 Flood damage-resistant materials Choose an item.
Choose an item. AO303.2 Location of flood damage-resistant materials Choose an item.
Choose an item. AO303.3 Fasteners and connectors used for flood-resistant materials Choose an item.
Choose an item. CHAPTER AO4 HIGH-WIND RESISTIVE CONSTRUCTION Choose an item.
Choose an item. SECTION AO401 GENERAL Choose an item.
Choose an item. AO401.1 Applications Choose an item.
Choose an item. AO401.2 Limitations Choose an item.
Choose an item. AO402 DEFINITIONS AND NOTATIONS Choose an item.
Choose an item. AO403 WIND LOADS Choose an item.
Choose an item. AO403.1 Wind Directionality Factor Choose an item.
Choose an item. AO403.2 Exposure Choose an item.
Choose an item. AO403.3 Enclosure classification Choose an item.
Choose an item. AO403.4 Continuous operation of Risk Category IV buildings Choose an item.
Choose an item. SECTION Choose an item. Choose an item.
Choose an item. CHAPTER AO5 STORM SHELTERS, SAFE ROOMS AND BEST AVAILABLE REFUGE AREAS Choose an item.
Choose an item. SECTION AO501 GENERAL Choose an item.
Choose an item. AO501.1 General Choose an item.
Choose an item. AO501.2 Occupant load Choose an item.
Choose an item. AO501.3 Construction documents Choose an item.
Choose an item. AO501.4 Signage Choose an item.
Choose an item. SECTION AO502 DEFINITIONS AND NOTATIONS Choose an item.
Choose an item. AO502.1 Definitions Choose an item.
Choose an item. AO502.2 Additional definitions Choose an item.
Choose an item. SECTION AO503 BEST AVAILABLE REFUGE AREAS Choose an item.
Choose an item. AO503.1 General Choose an item.
Choose an item. AO503.2 Occupant Density Choose an item.
Choose an item. AO503.3 Identification of best available refuge areas Choose an item.
Choose an item. SECTION AO504 APPLICABILITY Choose an item.
Choose an item. AO504.1 Required storm shelters or safe rooms Choose an item.
TABLE OF CONTENTS
CHAPTER AO1 Scope and Administration ............... 8
Section
AO101 Administration......................8
AO102 Applicability ........................................................8
AO103 Post Disaster Event Inspections Guidelines ..........9
CHAPTER AO2 Definitions .........................................11
Section
AO201 General .............................................................. 11
AO202 Definitions .........................................................11
CHAPTER AO3 Flood-resistant Construction.........................................12
Section
AO301 Hazard Identification .......................................... 12
AO302 Scope .................................................................12
AO303 Flood damage-resistant materials ....................... 12
CHAPTER AO4 High-wind Resistive Construction...13
Section
AO401 General ..............................................................13
AO402 Definitions and Notations.......................13
AO403 Wind Loads..................................13
AO404 Wind Load Option A .........................................13
AO405 Wind Load Option B ........................................ 14
AO406 Wind Load Option C ........................................ 14
CHAPTER AO5 Storm Shelters, Safe Rooms and Best Available Refuge Areas .........................................15
Section
AO501 General..........................15
AO502 Definitions and Notations.................................. 15
AO503 Best Available Refuge Areas ............................ 15
AO504 Applicability ..................................................... 15
CHAPTER AO6 Resources 16
Section
AO601 Contacts ............................................................. 16
AO602 Emergency Inspection Kit ................................. 16
AO603 Safety Tips..........................................................17
AO604 Major Disaster Process ...................................... 17
AO605 Sample Evaluation Forms and Placards ............. 17
CHAPTER AO7 References .........................................24
INDEX OF FIGURES ..................................................24
APPENDIX O
DISASTER RESILIENT CONSTRUCTION
CHAPTER AO1
SCOPE AND ADMINISTRATION
SECTION AO101
ADMINISTRATION
SECTION AO102
APPLICABILITY
SECTION AO103
POST DISASTER EVENT INSPECTIONS GUIDELINES
See Section AO605 for Placards that may be reproduced for use in the field during evaluations. The jurisdiction shall alter placards to meet the jurisdiction and building department's requirements.
Figure AO103.3 Post Disaster Building Safety Evaluation Chart a
Click here to view image
(a) When Disaster Strikes by the International Code Council, Inc., Seventh Printing: November 2011, copyright 2007
CHAPTER AO2
DEFINITIONS
SECTION AO201
GENERAL
SECTION AO202
DEFINITIONS
500-YEAR FLOOD. Flood having a 0.2% annual probability of being equaled or exceeded.
ADVISORY BASE FLOOD ELEVATION (ABFE).
An advisory base flood elevation (BFE) issued by the Federal Emergency Management Agency (FEMA) that reflects post-storm conditions and vulnerability to damages from future flooding.
BASE FLOOD. Flood having a 1% chance of being equaled or exceeded in any given year, also referred to as the 100-year flood.
BASE FLOOD ELEVATION (BFE). The elevation of flooding, including wave height, having a 1% chance of being equaled or exceeded in any given year established relative to the National Geodetic Vertical Datum (NGVD), North American Vertical Datum (NAVD) or other datum specified on the Flood Insurance Rate Map (FIRM).
BUILDING OFFICIAL. The officer or other designated authority charged with the administration and enforcement of the International Building Code, or the building official's duly authorized representative.
DESIGN FLOOD. The greater of the following two flood events:
DESIGN FLOOD ELEVATION (DFE). The elevation of the design flood, including wave height, relative to the datum specified on the community's legally designated flood hazard map. In areas designated as Zone AO, the design flood elevation shall be the elevation of the highest existing grade of the building's perimeter plus the depth number (in feet) specified on the flood hazard map.
FLOOD [DAMAGE]-RESISTANT MATERIAL. Any building product [material, component or system] capable of withstanding direct and prolonged contact with floodwaters without sustaining significant damage.
FLOOD HAZARD MAP. Map delineating flood hazard areas adopted by the authority having jurisdiction.
FLOOD INSURANCE RATE MAP (FIRM). An official map of a community on which the Federal Emergency Management Agency (FEMA) has delineated both the special flood hazard areas and the risk premium zones applicable to the community.
FREEBOARD. A factor of safety expressed in feet above a flood level for purposes of floodplain management.
FUTURE-CONDITIONS FLOOD. The flood having a 1% chance of being equaled or exceeded in any given year based on future-conditions hydrology. Also known as the 100-year future-conditions flood.
FUTURE-CONDITIONS FLOOD ELEVATION. The flood standard equal to or higher than the Base Flood Elevation. The future-conditions flood elevation is defined as the highest water surface anticipated at any given point during the future-conditions flood.
CHAPTER AO3
FLOOD-RESISTANT CONSTRUCTION
Forward: This appendix provides three different options for increased freeboard. The jurisdiction may pick only one option that is higher than previously adopted and enforced by the jurisdiction. The National Flood Insurance Program (NFIP) minimum standards reference Base Flood Elevation without any freeboard in high risk flood hazard areas. Due to the flood damage prevention updates performed during the Map Modernization initiative that led to flood risks being digitally identified in all 159 Georgia counties, all Georgia NFIP participating communities have freeboard standards that meet or exceed the 1 foot standard used in the State model ordinances for areas where BFEs have been established.
SECTION AO301
HAZARD IDENTIFICATION
SECTION AO302
SCOPE
OPTION A - FLOOD ELEVATION
The higher of:
OPTION B - FLOOD ELEVATION
The higher of:
OPTION C - FLOOD ELEVATION
The higher of:
SECTION AO303
FLOOD DAMAGE-RESISTANT MATERIALS
CHAPTER AO4
HIGH-WIND RESISTIVE CONSTRUCTION
SECTION AO401
GENERAL
Exception: Compliance with AF&PA WFCM shall be permitted subject to the limitations therein and the limitations of this appendix.
SECTION AO402
DEFINITIONS AND NOTATIONS
CONVENTIONAL LIGHT-FRAME
CONSTRUCTION.
MASONRY.
Unreinforced (plain) masonry.
WIND-BORNE DEBRIS REGION.
WIND SPEED, Vult.
SECTION AO403
WIND LOADS
SECTION AO404
WIND LOAD OPTION A
Exception:
SECTION AO405
WIND LOAD OPTION B
Exception:
SECTION AO406
WIND LOAD OPTION C
be obtained from IBC Figure 1609.3(1) or 170 mph, whichever is greater.
Exception:
Table AO401.1
WIND LOAD OPTIONS:
TARGET PERFORMANCE LEVELS AND DESIGN CRITERIA4
|
OPTION |
DESIGN WIND EVENT |
Risk Category II1 |
Risk Category III1 |
Risk Category IV1 |
||||||
|
Target Performance Level2 |
Min Wind Speed Vult |
Wind-Borne Debris |
Target Performance Level2 |
Min Wind Speed Vult |
Wind-Borne Debris |
Target Performance Level2 |
Min Wind Speed Vult |
Wind-Borne Debris |
||
|
A |
EF0 & 1 Tornado - IBC level Hurricane |
CP3 |
IBC 1609.3 |
IBC 1609.2 or ASCE 7 |
CP3 |
IBC 1609.3 |
IBC 1609.2 or ASCE 7 |
CP3 |
IBC 1609.3 |
IBC 1609.2 or ASCE 7 |
|
LS |
Glazing |
IO5 |
Glazing |
|||||||
|
B |
EF2 Tornado - Cat 3 Hurricane |
CP3 for EF0-EF1-IBC Hurricane for Risk Cat. III/IV |
IBC 1609.3 for Risk Cat. III/IV |
IBC 1609.2 or ASCE 7 |
LS |
145 mph |
Req'd for glazing per IBC 1609.2 and ASCE 7 |
IO5 |
145 mph |
Exterior Envelope |
|
C |
EF3 Tornado - Cat 4 Hurricane |
CP3 for EF0-EF1-IBC Hurricane for Risk Cat. III/IV |
IBC 1609.3 for Risk Cat. III/IV |
IBC 1609.2 or ASCE 7 |
LS |
170 mph |
Req'd for glazing per IBC 1609.2 and ASCE 7 |
IO5 |
170 mph |
Exterior Envelope |
Notes:
CP: Collapse Prevention
LS: Life Safety
IO: Immediate Occupancy
OB: Operational Building
CHAPTER AO5
STORM SHELTERS, SAFE ROOMS AND BEST AVAILABLE REFUGE AREAS
SECTION AO501
GENERAL
Exception: Residential Safe Rooms and safe rooms serving a Business Group B Occupancy and having an occupant load not exceeding 16 persons may be constructed in accordance with FEMA 320.
SECTION AO502
DEFINITIONS AND NOTATIONS
DWELLING UNITS.
OCCUPANT LOAD.
STORM SHELTER.
Community Storm Shelter.
Residential Storm Shelter.
BEST AVAILABLE REFUGE AREAS. Areas in a building that have been deemed by a registered design professional to likely offer the greatest safety for building occupants during a tornado or hurricane. Because these areas were not specifically designed as storm shelters or safe rooms, their occupants may be injured or killed during a tornado or hurricane. However, people in the best available refuge areas are less likely to be injured or killed than people in other areas of a building.
SAFE ROOM. A building, structure or portions thereof, constructed in accordance with FEMA 361 and designed for use during a severe wind storm event, such as a hurricane or tornado.
Community Safe Room. A safe room not defined as a "Residential Safe Room"
Residential Safe Room. A safe room serving occupants of dwelling units and having an occupant load not exceeding 16 persons.
SECTION AO503
BEST AVAILABLE REFUGE AREAS
SECTION AO504
APPLICABILITY
CHAPTER AO6
RESOURCES
SECTION AO601
CONTACTS
Georgia Department of Community Affairs (DCA) Construction Codes
Georgia State Amendments to the State Minimum Standard Codes
Phone: 404-679-3118
Georgia Department of Natural Resources (DNR)
Floodplain Management
4220 International Parkway, Ste. 101
Atlanta, GA 30354-3902
Phone: 404-675-1757
Federal Emergency Management Agency (FEMA)
www.fema.gov; www.floodsmart.gov
www.fema.gov/rebuild/buildingscience/
FEMA Publications and Technical Bulletins:
(www.fema.gov/library/index.jsp)
(www.fema.gov/plan/prevent/floodplain/techbul.shtm)
Georgia Emergency Management Agency (GEMA)
Georgia Office of Homeland Security
P.O. Box 18055
Atlanta, GA 30316-0055
www.ready.ga.gov
Phone: 404-635-7000
Georgia Association of Regional Commissions (GARC)
www.garc.ga.gov (http://garc.ga.gov/main.php?regional-Commissions-2) (for assistance in identifying Flood Hazard Areas)
International Code Council (ICC)
National Weather Service
State Fire Marshal's Office
2 Martin Luther King Jr. Drive
Suite 920 / West Tower
Atlanta, Georgia 30334
Phone: 404-656-7087
SECTION AO602
EMERGENCY INSPECTION KIT b
|
[] Staff's disaster response management plan |
[] Safety glasses |
[] Duct tape |
|
[] Sunglasses |
[] Staples & stapler |
|
|
[] Team contact list |
[] Pocket knife |
[] Staple gun |
|
[] Area maps |
[] Matches |
[] Calculator |
|
[] Official identification |
[] Antibacterial hand wipes or alcohol-based hand sanitizer |
[] Tire repair kit |
|
[] Personal identification |
||
|
[] Inspection forms and placards |
[] Insect repellant (w/ Deet or Picaridin) |
Remember to grab: |
|
[] Communication equipment |
[] Personal identification |
|
|
[] Clipboard |
[] Sunscreen (SPF 15 or greater) |
[] Rain gear, extra clothing |
|
[] Hard hat |
[] Camera |
[] Water bottle |
|
[] Orange safety vest |
[] Black markers |
[] Prescription medication |
|
[] Dust mask |
[] Pens & pencils |
[] Cell phone and charger |
|
[] Work gloves |
[] Envelope for expense receipts |
[] Cash for personal expenses |
|
[] Steel toe and waterproof boots |
[] Compass, GPS unit |
[] Toiletries |
|
[] Whistle |
[] Backpack, waistpack |
|
|
[] First aid kit |
[] Flashlight and extra batteries |
|
|
[] Latex gloves |
[] Battery-operated radio |
(b) Disaster Mitigation: A Guide for Building Departments by the International Code Council, Inc., copyright 2009
SECTION AO603
SAFETY TIPS a
SECTION AO604
MAJOR DISASTER PROCESS
(from link https://www.fema.gov/disaster-declaration-process)
A Major Disaster Declaration usually follows these steps:
* Incident occurs and local government responds, supplemented by neighboring communities and volunteer agencies. If overwhelmed, turn to the state for assistance;
Generally the local government will issue a local state of emergency
* The State responds with state resources, such as the National Guard and state agencies;
Prior to committing state resources, the Governor will declare a state of emergency in the counties impacted by the event for which assistance is needed.
* Damage assessment by local, state, federal, and volunteer organizations determine losses and recovery needs;
Generally the locals will submit a preliminary damage assessment to the state and the state will review and determine if state and/or federal assistance is needed. If federal assistance is needed, the state will request FEMA perform a preliminary joint damage assessment. If the Governor determines that the incident is of such severity and magnitude that effective response is beyond the capabilities of the state and the affected local governments then supplementary Federal assistance is requested (next step).
* A Major Disaster Declaration is requested by the Governor, based on the damage assessment, and agreement to commit state funds and resources to the long-term recovery;
* FEMA evaluates the request and recommends action to the White House based on the disaster, the local community and the state's ability to recover;
* The President approves the request or FEMA informs the Governor it has been denied. This decision process could take a few hours or several weeks depending on the nature of the disaster.
SECTION AO605
SAMPLE EVALUATION FORMS AND INSPECTION PLACARDS b (following pages)
Figure AO605.1b
Click here to view image
Figure AO605.2 b
Click here to view image
Click here to view image
Figure AO605.3 b
Click here to view image
Click here to view image
Click here to view image
CHAPTER AO7
REFERENCES
REFERENCED STANDARDS
ASCE Standards ASCE/SEI 24-14 Flood Resistant Design and Construction
FEMA P-320, Fourth Edition / December 2014 Taking Shelter From the Storm: Building a Safe Room For Your Home or Small Business, Includes Construction Plans and Cost Estimates
FEMA 361, Third Edition / March 2015 Design and Construction Guidance for Community Safe Rooms
FEMA P-431, Second Edition/October 2009 Tornado Protection: Selecting Refuge Areas in Buildings
FEMA Technical Bulletin 2, Table 2. Types, Uses, and Classifications of Materials
REFERENCED RESOURCES
INDEX OF FIGURES:
Figure AO103.3 Post Disaster Building Safety Evaluation Chart a ........................................................................................................ 10
Figure AO605.1 ATC-45 Rapid Evaluation Form ........................................................................................................... 18
Figure AO605.2 ATC-45 Detail Evaluation Form ........................................................................................................... 19
Figure AO605.3 Inspected Placard ................................................................................................................................... 21
Figure AO605.4 Restricted Placard .................................................................................................................................. 22
Figure AO605.5 Unsafe Placard ........................................................................................................................................23
INDEX
B
Best available refuge area ......Chapter 5, AO501.1, AO502. 2, AO503
C
Connectors ........................................................................ AO303.3
Conventional Light-Frame Construction ................... AO401.2.3
E
Emergency operation centers .......................................... AO504.1
Enclosure classification .................................................... AO403.3
Essential Facility .............................................................. AO103.3
Evaluation
Detailed .........AO103.2.1, AO103 3 2.2, AO103.4
Engineering ........AO103.2.2, AO103 2.3, Figure 103.3
Rapid ........AO103.2.1, AO103.4, Figure AO605.1
Exposure .......................................................................... AO403.2
F
Fasteners.......................................................................... AO303.3
Flood
500-Year ......Chapter 2, AO302.1.2, AO302 1.3, AO302.1.4
Base ...........................................................Chapter 2, AO302.1.1
Design ..........................................................................Chapter 2
Future-conditions ......Chapter 2, AO302.1.1, AO302.1.2, AO302.1.3, AO302.1.4
Flood Elevation
Advisory Base ...Chapter 2, AO302.1.2, AO302 1.3, AO302.1.4
Base ..................Chapter 2, AO302.1.2, AO302 1.3, AO302.1.4
Design ...........Chapter 2, AO302.1.2, AO302 1.3, AO302.1.4
Futures-conditions ....................................................... Chapter 2
Flood Hazard Area ..AO102.1.1, Chapter 2, AO301.1, AO302.1, AO302.1.1
Flood-(Damage) Resistant Material ...................Chapter 2, AO303
Freeboard ...................................................... Chapter 2, Chapter 3
G
Grade Schools .....................................................................AO504
I
Impact Resistant ...............AO404.2, AO405.2, AO406.2
Inspections ..................AO103.1, AO103.2
M
Masonry
Empirical ................................................................... AO401.2.1
Unreinforced ............................................................... AO401.2.2
O
Opening Protection ........AO401.1, AO404.2, AO405.2, AO406.2
P
Placards ............. AO103.2.1, AO103.5, Figure AO605.3-AO605.5
S
Safe rooms
Community....................................................................AO502.2
Occupant density .................AO501.2, AO503.2
Residential ..........................AO501.1, AO502, AO502.2
Sample Ordinance ................................................... Page 2, 3, and 4
Storm shelters .................AO101.3.3, Table AO401.1, Chapter AO5
Substantial alterations ..................................................AO102.1.1
Substantial improvements ...................AO101 3.1, AO302.1.1
T
Table of Contents ................................................................ Page 7
U
Ultimate design wind speed ...................AO404.1, AO405.1, AO406.1
V
Violations ......................................................................... AO101.4
W
Wind Directionality Factor ............................................ AO403.1
Wind Load .....................AO401, AO403, AO404, AO405, AO406
CHAPTER 34
EXISTING BUILDINGS AND STRUCTURES
SECTION 3401
GENERAL
Exception: Existing bleachers, grandstands and folding and telescopic seating shall comply with ICC 300.
SECTION 3402
DEFINITIONS
DANGEROUS.
EXISTING STRUCTURE.
PRIMARY FUNCTION.
SUBSTANTIAL STRUCTURAL DAMAGE.
TECHNICALLY INFEASIBLE.
SECTION 3403
ADDITIONS
For buildings and structures in flood hazard areas established in Section 1612.3, any additions that do not constitute substantial improvement of the existing structure, as defined in Section 202, are not required to comply with the flood design requirements for new construction.
Exception: Any existing lateral load-carrying structural element whose demand-capacity ratio with the addition considered is no more than 10 percent greater than its demand-capacity ratio with the addition ignored shall be permitted to remain unaltered. For purposes of calculating demand-capacity ratios, the demand shall consider applicable load combinations with design lateral loads or forces in accordance with Sections 1609 and 1613. For purposes of this exception, comparisons of demand-capacity ratios and calculation of design lateral loads, forces and capacities shall account for the cumulative effects of additions and alterations since original construction.
SECTION 3404
ALTERATIONS
Exceptions:
For buildings and structures in flood hazard areas established in Section 1612.3, any alterations that do not constitute substantial improvement of the existing structure, as defined in Section 202, are not required to comply with the flood design requirements for new construction.
Exception: Any existing lateral load-carrying structural element whose demand-capacity ratio with the alteration considered is no more than 10 percent greater than its demand-capacity ratio with the alteration ignored shall be permitted to remain unaltered. For purposes of calculating demand-capacity ratios, the demand shall consider applicable load combinations with design lateral loads or forces per Sections 1609 and 1613. For purposes of this exception, comparisons of demand-capacity ratios and calculation of design lateral loads, forces, and capacities shall account for the cumulative effects of additions and alterations since original construction.
SECTION 3405
REPAIRS
Exceptions:
Wind loads for this evaluation shall be those prescribed in Section 1609. Earthquake loads for this evaluation, if required, shall be permitted to be 75 percent of those prescribed in Section 1613.
Exceptions:
For buildings and structures in flood hazard areas established in Section 1612.3, any repairs that do not constitute substantial improvement or repair of substantial damage of the existing structure, as defined in Section 202, are not required to comply with the flood design requirements for new construction.
SECTION 3406
FIRE ESCAPES
SECTION 3407
GLASS REPLACEMENT
SECTION 3408
CHANGE OF OCCUPANCY
Exceptions:
SECTION 3409
HISTORIC BUILDINGS
Exception: Historic buildings that are:
SECTION 3410
MOVED STRUCTURES
SECTION 3411
ACCESSIBILITY FOR EXISTING BUILDINGS
Exception: Type B dwelling units or sleeping units required by Section 1107 of this code are not required to be provided in existing buildings and facilities undergoing a change of occupancy in conjunction with alterations where the work area is 50 percent or less of the aggregate area of the building.
Where it is technically infeasible to comply with the new construction standards for any of these requirements for a change of group or occupancy, the above items shall conform to the requirements to the maximum extent technically feasible.
Exception: The accessible features listed in Items 1 through 6 are not required for an accessible route to Type B units.
Exceptions:
Exceptions:
Exception: Where an alteration includes alterations to an entrance, and the facility has an accessible entrance, the altered entrance is not required to be accessible, unless required by Section 3411.7. Signs complying with Section 1111 shall be provided.
TABLE 3411.8.5
RAMPS
|
SLOPE |
MAXIMUM RISE |
|
Steeper than 1:10 but not steeper than 1:8 |
3 inches |
|
Steeper than 1:12 but not steeper than 1:10 |
6 inches |
For SI: 1 inch = 25.4 mm.
Exception: Type B dwelling or sleeping units required by Section 1107 are not required to be provided in historical buildings.
Exceptions:
Signs complying with Section 1111 shall be provided at the primary entrance and the accessible entrance.
SECTION 3412
COMPLIANCE ALTERNATIVES
Where a portion of the building is changed to a new occupancy classification, and that portion is not separated from the remainder of the building with fire barriers or horizontal assemblies having a fire-resistance rating as required by Table 508.4 for the separate occupancies, or with approved compliance alternatives, the provisions of this section which apply to each occupancy shall apply to the entire building. Where there are conflicting provisions, those requirements which secure the greater public safety shall apply to the entire building or structure.
Where the separation between mixed occupancies qualifies for any category indicated in Section 3412.6.16, the score for each occupancy shall apply to each portion of the building based on the occupancy of the space.
Click here to view image
(Equation 34-1)
Click here to view image
(Equation 34-2)
where:
AH = Allowable height in feet from 2012 IBC Table 503.
EBH = Existing building height in feet.
AS = Allowable height in stories from 2012 IBC Table 503.
EBS = Existing building height in stories.
CF = 1 if (AH) - (EBH) is positive.
CF = Construction-type factor shown in Table 3412.6.6(2) if (AH) - (EBH) is negative.
Note: Where mixed occupancies are separated and individually evaluated as indicated in Section 3412.6, the values AH, AS, EBH and EBS shall be based on the height of the occupancy being evaluated.
Click here to view image
(Equation 34-3)
where:
Aa = Allowable building area per story (square feet).
At = Tabular building area per story in accordance with 2012 IBC Table 503. (square feet).
Is = Area increase factor due to sprinkler protection as calculated in accordance with 2012 IBC Section 506.3.
If = Area increase factor due to for frontage as calculated in accordance with 2012 IBC Section 506.2.
Click here to view image
(Equation 34-4)
where:
i = Value for an individual separated occupancy on a floor.
n = Number of separated occupancies on a floor.
TABLE 3412.6.4
SEPARATION VALUES
|
OCCUPANCY. |
CATEGORIES |
||||
|
a |
b |
c |
d |
e |
|
|
A-1 |
0 |
0 |
0 |
0 |
1 |
|
A-2 |
-5 |
-3 |
0 |
1 |
3 |
|
A-3, A-4, B, E, F, M, S-1 |
-4 |
-3 |
0 |
2 |
4 |
|
R |
-4 |
-2 |
0 |
2 |
4 |
|
S-2 |
-5 |
-2 |
0 |
2 |
4 |
TABLE 3412.6.5
CORRIDOR WALL VALUES
|
OCCUPANCY |
CATEGORIES |
|||
|
a |
b |
ca |
da |
|
|
A-1 |
-10 |
-4 |
0 |
2 |
|
A-2 |
-30 |
-12 |
0 |
2 |
|
A-3, F, M, R, S-1 |
-7 |
-3 |
0 |
2 |
|
A-4, B, E, S-2 |
-5 |
-2 |
0 |
5 |
TABLE 3412.6.6(1)
VERTICAL OPENING PROTECTION VALUE
|
PROTECTION |
VALUE |
|
None (unprotected opening) |
-2 times number floors connected |
|
Less than 1 hour |
-1 times number floors connected |
|
1 to less than 2 hours |
1 |
|
2 hours or more |
2 |
TABLE 3412.6.6(2)
CONSTRUCTION-TYPE FACTOR
|
FACTOR |
TYPE OF CONSTRUCTION |
||||||||
|
IA |
IB |
IIA |
IIB |
IIIA |
IIIB |
IV |
VA |
VB |
|
|
1.2 |
1.5 |
2.2 |
3.5 |
2.5 |
3.5 |
2.3 |
3.3 |
7 |
|
Click here to view image
(Equation 34-5)
where:
VO = Vertical opening value.
PV = Protection value [Table 3412.6.6(1)].
CF = Construction type factor [Table 3412.6.6(2)].
TABLE 3412.6.3
COMPARTMENTATION VALUES
|
OCCUPANCY |
CATEGORIESa |
||||
|
a Compartment size equal to or greater than 15,000 square feet |
b Compartment size of 10,000 square feet |
c Compartment size of 7,500 square feet |
d Compartment size of 5,000 square feet |
e Compartment size of 2,500 square feet or less |
|
|
A-1, A-3 |
0 |
6 |
10 |
14 |
18 |
|
A-2 |
0 |
4 |
10 |
14 |
18 |
|
A-4, B, E, S-2 |
0 |
5 |
10 |
15 |
20 |
|
F, M, R, S-1 |
0 |
4 |
10 |
16 |
22 |
For SI: 1 square foot = 0.093 m2.
TABLE 3412.6.8
AUTOMATIC FIRE DETECTION VALUES
|
OCCUPANCY |
CATEGORIES |
||||
|
a |
b |
c |
d |
e |
|
|
A-1, A-3, F, M, R, S-1 |
-10 |
-5 |
0 |
2 |
6 |
|
A-2 |
-25 |
-5 |
0 |
5 |
9 |
|
A-4, B, E, S-2 |
-4 |
-2 |
0 |
4 |
8 |
Table 3412.7 under Safety Parameter 3412.6.9, Fire Alarm Systems, for fire safety, means of egress and general safety.
TABLE 3412.6.9
FIRE ALARM SYSTEM VALUES
|
OCCUPANCY |
CATEGORIES |
|||
|
a |
ba |
c |
d |
|
|
A-1, A-2, A-3, A-4, B, E, R |
-10 |
-5 |
0 |
5 |
|
F, M, S |
0 |
5 |
10 |
15 |
TABLE 3412.6.10
SMOKE CONTROL VALUES
|
OCCUPANCY |
CATEGORIES |
|||||
|
a |
b |
c |
d |
e |
f |
|
|
A-1, A-2, A-3 |
0 |
1 |
2 |
3 |
6 |
6 |
|
A-4, E |
0 |
0 |
0 |
1 |
3 |
5 |
|
B, M, R |
0 |
2a |
3a |
3a |
3a |
4a |
|
F, S |
0 |
2a |
2a |
3a |
3a |
3a |
Under the categories and occupancies in Table 3412.6.11, determine the appropriate value and enter that value into Table 3412.7 under Safety Parameter 3412.6.11, Means of Egress Capacity, for means of egress and general safety.
TABLE 3412.6.11
MEANS OF EGRESS VALUES
|
OCCUPANCY |
CATEGORIES |
||||
|
aa |
b |
c |
d |
e |
|
|
A-1, A-2, A-3, A-4, E |
-10 |
0 |
2 |
8 |
10 |
|
M |
-3 |
0 |
1 |
2 |
4 |
|
B, F, S |
-1 |
0 |
0 |
0 |
0 |
|
R |
-3 |
0 |
0 |
0 |
0 |
TABLE 3412.6.12
DEAD-END VALUES
|
OCCUPANCY |
CATEGORIESa |
||
|
a |
b |
c |
|
|
A-1, A-3, A-4, B, E, F, M, R, S |
-2 |
0 |
2 |
|
A-2, E |
-2 |
0 |
2 |
Click here to view image
(Equation 34-6)
TABLE 3412.6.15
MEANS OF EGRESS EMERGENCY LIGHTING VALUES
|
NUMBER OF EXITS REQUIRED BY SECTION 1007 |
CATEGORIES |
||
|
a |
b |
c |
|
|
Two or more exits |
NP |
0 |
4 |
|
Minimum of one exit |
0 |
1 |
1 |
egress emergency lighting are:
TABLE 3412.6.14
ELEVATOR CONTROL VALUES
|
ELEVATOR TRAVEL |
CATEGORIES |
|||
|
a |
b |
c |
d |
|
|
Less than 25 feet of travel above or below the primary level of elevator access for emergency fire-fighting or rescue personnel |
-2 |
0 |
0 |
+2 |
|
Travel of 25 feet or more above or below the primary level of elevator access for emergency fire-fighting or rescue personnel |
-4 |
NP |
0 |
+4 |
For SI: 1 foot = 304.8 mm.
NP = Not permitted
TABLE 3412.6.16
MIXED OCCUPANCY VALUESa
|
OCCUPANCY |
CATEGORIES |
||
|
a |
b |
c |
|
|
A-1, A-2, R |
-10 |
0 |
10 |
|
A-3, A-4, B, E, F, M, S |
-5 |
0 |
5 |
TABLE 3412.6.17
SPRINKLER SYSTEM VALUES
|
OCCUPANCY |
CATEGORIES |
|||||
|
a |
b |
c |
d |
e |
f |
|
|
A-1, A-3, F, M, R, S-1 |
-6 |
-3 |
0 |
2 |
4 |
6 |
|
A-2 |
-4 |
-2 |
0 |
1 |
2 |
4 |
|
A-4, B, E, S-2 |
-12 |
-6 |
0 |
3 |
6 |
12 |
TABLE 3412.6.18
STANDPIPE SYSTEM VALUES
|
OCCUPANCY |
CATEGORIES |
|||
|
aa |
b |
c |
d |
|
|
A-1, A-3, F, M, R, S-1 |
-6 |
0 |
4 |
6 |
|
A-2 |
-4 |
0 |
2 |
4 |
|
A-4, B, E, S-2 |
-12 |
0 |
6 |
12 |
TABLE 3412.6.19
INCIDENTAL USE AREA VALUES
|
PROTECTION REQUIRED BY TABLE 509 |
PROTECTION PROVIDED |
||||||
|
None |
1 Hour |
AS |
AS with SP |
1 Hour and AS |
2 Hours |
2 Hours and AS |
|
|
2 Hours and AS |
-4 |
-3 |
-2 |
-2 |
-1 |
-2 |
0 |
|
2 Hours, or 1 Hour and AS |
-3 |
-2 |
-1 |
-1 |
0 |
0 |
0 |
|
1 Hour and AS |
-3 |
-2 |
-1 |
-1 |
0 |
-1 |
0 |
|
1 Hour |
-1 |
0 |
-1 |
0 |
0 |
0 |
0 |
|
1 Hour, or AS with SP |
-1 |
0 |
-1 |
0 |
0 |
0 |
0 |
|
AS with SP |
-1 |
-1 |
-1 |
0 |
0 |
-1 |
0 |
|
1 Hour or AS |
-1 |
0 |
0 |
0 |
0 |
0 |
0 |
AS = Automatic sprinkler system; SP = Smoke partitions (See Section 509.4.2).
Note: For Table 3412.7, see next page.
TABLE 3412.7
SUMMARY SHEET-BUILDING CODE
Click here to view image
* * * *No applicable value to be inserted.
TABLE 3412.8
MANDATORY SAFETY SCORESa
|
OCCUPANCY |
FIRE SAFETY (MFS) |
MEANS OF EGRESS (MME) |
GENERAL SAFETY (MGS) |
|
A-1 |
20 |
31 |
31 |
|
A-2 |
21 |
32 |
32 |
|
A-3 |
22 |
33 |
33 |
|
A-4, E |
29 |
40 |
40 |
|
B |
30 |
40 |
40 |
|
F |
24 |
34 |
34 |
|
M |
23 |
40 |
40 |
|
R |
21 |
38 |
38 |
|
S-1 |
19 |
29 |
29 |
|
S-2 |
29 |
39 |
39 |
MME = Mandatory Means of Egress;
MGS = Mandatory General Safety.
TABLE 3412.9
EVALUATION FORMULASa
|
FORMULA |
T.3412.7 |
T.3412.8 |
SCORE |
PASS |
FAIL |
||
|
FS-MFS >= 0 |
(FS) |
- |
_ (MFS) = |
||||
|
ME-MME >= 0 |
(ME) |
- |
(MME) = |
||||
|
GS-MGS >= 0 |
(GS) |
- |
_ (MGS) = |
ME = Means of Egress
GS = General Safety
MFS = Mandatory Fire Safety
MME = Mandatory Means of Egress
MGS = Mandatory General Safety
End of Amendments.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.