Ga. Comp. R. & Regs. R. 111-8-56-.18 - Physical Plant Standards
(1) Requirements under this rule "Physical
Plant Standards" will be enforced with the effective date of these regulations
EXCEPT that homes holding a valid permit prior to the effective date of these
regulations, shall comply with the regulations in effect at the time the home
was issued a permit or the plans were approved. Provided however, that any such
homes which hold a valid permit prior to the effective date of these
regulations must comply with these regulations when improvements or
modifications are made within any twelve (12) month period and the cost of such
improvements or modifications exceeds a total of twenty percent (20%) of the
fair market value of the home. If no such improvements are made, the homes
holding a valid permit prior to the effective date of these regulations must
then comply with these regulations within fifteen (15) years of the effective
date of these regulations. In exceptional cases and upon application to the
Department by the governing body of the home, variances may be granted at the
discretion of the Department (if it determines that these requirements will
place an undue burden or extreme hardship on the home or its occupants),
provided that the health and safety of the patients is not
jeopardized.
(2) At least two rooms
per fifty (50) beds shall be designed for single occupancy (one bed). At least
one room designed for single occupancy shall have an adjoining private
bathroom, containing a lavatory, water closet and a bathtub or shower equipped
with grab bars.
(3) All patient
rooms shall open into corridors leading to the exterior of the building. No
patient room will be so located as to make it necessary for a patient to pass
through another room to gain entrance to a corridor leading to the
exterior.
(4) Each patient room
shall be an outside room with window space equal to at least one-eighth of the
floor area with opening in area large enough to remove patient by
mattress.
(5) Patient bedrooms
shall contain not less than one hundred (100) square feet of usable floor space
in private or single rooms and no less than eighty (80) square feet per bed of
usable floor space in multibed rooms. Usable floor space is in addition to area
provided for closets, toilet rooms and entry ways.
(6) Not less than three (3) feet of space
shall be provided between beds and between the foot of the bed and wall or
other obstruction. There shall be sufficient space so beds may be made
accessible from both sides for nursing care when needed.
(7) An individual clothes closet or wardrobe
with door shall be provided per bed in every patient room. Clothes closets or
wardrobes shall be at least twenty-two (22) inches deep and twenty (20) inches
wide with at least one shelf above a hanging space equipped with a device for
clothes hangers.
(8) Each patient
room having more than one bed shall have permanently installed curtain tracks
to permit closing each bed with curtains to allow for the privacy of each
patient without obstructing the passage of other patients either to the
corridor or to the toilet or lavatory adjacent to the patient room. Curtains
used for enclosing patient beds shall be rendered and maintained flame
resistant.
(9) Employees, staff and
visitors shall not use water closets provided for patients. Toilets, including
a water closet, lavatory, soap, paper towels and dispensers shall be provided
near or adjacent to the following locations:
(a) Nurses' station or medication
area;
(b) Kitchen;
(c) Lobby area or waiting room.
(10) Patient bathing and toilet
facilities:
(a) There shall be a general
bathing area in each nursing unit. This area shall contain at least one bathtub
accessible from three sides, one stall shower equipped with grab bars with
adjacent drying space, one lavatory and one water closet. This unit shall be of
sufficient size to provide space for dressing, a wheelchair, and an attendant.
Unless the bathing fixtures are located in separate rooms, compartments must be
provided to permit independent use to afford privacy for each sex. Special
institutional tubs or showers may be approved for use if the program of service
indicates;
(b) At least one
enclosed water closet and one lavatory shall be provided for each eight beds or
major fraction thereof;
(c) At
least one bathing facility (bathtub or shower) shall be provided for each
fifteen (15) beds, or major fraction thereof, located in patient bedrooms that
do not adjoin a toilet room in which a bathing facility is located;
(d) Unless bathtubs in bathrooms adjoining
patient rooms are located so as to be accessible from three sides, handrails or
grab bars on the tub or on the wall by the tub shall be provided;
(e) All shower stalls shall be at least four
feet by four feet square and must have handrails on three sides, be equipped
with curtains and be designed for wheelchair use. Thresholds to showers must be
flush with the floor. The floor of the shower shall be designed to drain
properly;
(f) Grab bars, securely
attached to walls and conveniently located, adjacent to all bathtubs, showers
and water closets intended for patient use shall be provided.
(11) A nurses' station shall be
provided in each nursing unit. It shall contain a nurses' call system, charting
desk and supplies, medicine storage, lavatory with soap, towels and towel
dispenser, preparation area and a refrigerator. The nurses' station shall not
be more than 120 feet from the entrance of the most remote room
served.
(12) There shall be
separate clean and soiled utility rooms in each nursing unit located near the
nurses' station. The clean utility room shall contain wall and base cabinets
and stain resistant counter top, a small sink set into the counter or with
drain boards. The soiled utility room shall contain a counter with a stain
resistant top and storage cabinets underneath. In addition, it shall contain a
deep service sink with stopper for chemical sterilization of bedpans, urinals
and commode pails. The deep service sink with stopper may be omitted if a steam
autoclave for sterilizing is available to the home.
(13) At least one bedpan cleansing device
shall be provided in each nursing unit. It may be located in the soiled utility
room or in a special bedpan closet conveniently located in each nursing unit.
The bedpan cleansing device may be omitted if water closets in patient toilets
are equipped with bedpan lugs, spray hose and elevated vacuum
breaker.
(14) Sufficient space
shall be provided in each nursing unit for stretcher and wheelchair parking.
Such space shall be out of corridor traffic.
(15) There shall be a floor pantry in each
nursing unit located near or adjacent to the nurses' station. The floor pantry
shall contain a hot plate, sink, counter, cabinets and a refrigerator that
shall not be used to store drugs, biologicals or laboratory
specimens.
(16) A drinking fountain
which shall not impair any passageway shall be provided in each nursing
unit.
(17) There shall be a
treatment room convenient to patient rooms containing a treatment table,
lavatory equipped with soap, paper towels and dispenser, instrument table and
storage cabinet and providing adequate room for transfer of patients. A
treatment room may be used for consultation if appropriately
enlarged.
(18) There shall be a
patient dining and recreation area provided in each home. The minimum total
area shall be twenty (20) square feet of floor space per bed. One-half the
required space shall be for dining.
(19) A room with sufficient space for
patients' active exercise regimens including such equipment as a full-length
mirror, parallel bars, a wall-mounted wheel, and an exercise table shall be
provided. The room shall also contain a lavatory with gooseneck spout and wrist
controls. Soap, paper towels and towel dispenser shall also be
provided.
(20) There shall be a
lobby and/or waiting room in each home. The size of this area shall be
determined in relation to the size of the home and the program of
service.
(21) There shall be at
least one building exit at ground level and at least one building exit shall be
provided with a suitable ramp designed for a stretcher and a wheelchair. There
shall be one such exit leading to the outdoor recreation area.
(22) A public telephone shall be located near
the lobby. At least one telephone shall be arranged to be convenient for a
wheelchair user.
(23) The central
kitchen area shall be located to permit efficient service to the dining rooms
and the nursing units. It must be arranged and equipped for adequate food
storage; preparation and serving of foods in proper sequence; dish and utensil
cleaning and storage, and refuse storage and removal. Homes that are a distinct
part of another home may utilize the service of a central kitchen provided it
is of adequate size and adequately equipped to serve the total patient
population. Storage space shall be sufficient to store a 24-hour supply of
perishable foods and a 3-day supply of nonperishable foods.
(24) Separate and adequate clean laundry
storage and separate and adequate soiled laundry storage rooms shall be
provided appropriate to the frequency of deliveries and linen needs.
(25) Janitor's closets shall be provided on
the basis of at least one closet for the dietary area and one for the remainder
of the home. This room shall be of sufficient size to include racks for
equipment, storage space and a service sink.
(26) General storage space for the storage of
supplies, furniture, equipment and patients' possessions shall be provided.
Such space may be provided in one or more rooms and shall be commensurate with
the needs of the home, but not less than five (5) square feet per
bed.
(27) Maintenance area or areas
commensurate with the needs of the home, including storage space for building
and grounds maintenance equipment, tools, supplies and materials and shop space
for mechanical, painting and carpentry work shall be provided.
(28) Floor, wall and ceiling finishes shall
be smooth, easily cleaned and be wear-resistant appropriate to location. In
addition, the floors of the following spaces shall be waterproof: toilets,
baths, bedpan rooms, floor of pantries, kitchens, utility rooms, janitors'
closets and treatment rooms. Areas subject to wetting shall have nonslip
flooring. Carpeting, wall and ceiling finishes shall be approved by the State
Fire Marshal.
(29) Stairways, doors
and corridors:
(a) Stairways serving patient
areas shall not be less than forty-four (44) inches in clean width;
(b) Stairs shall be individually enclosed and
be separated from any public hall;
(c) A landing shall be provided at the top
and bottom of every stair run. Doors shall swing with exit travel to provide
safe exit;
(d) The minimum
dimension of landing shall be as wide as the required width of the stairway it
serves. A door swinging into a landing, when open, shall not overlap the
required width of the landing;
(e)
The width of stair to risers shall not be less than ten (10) inches plus a one
(1) inch nosing;
(f) Winders and
single risers are not acceptable;
(g) Stairs and landings shall have a non
slippery finish;
(h) Patients' room
corridor entrances and all required exits shall be not less than forty-four
(44) inches in clean width. All other doors through which patients must pass
shall be not less than thirty-six (36) inches in clean width except that doors
to toilets in patient bedrooms may not be less than thirty-two (32) inches
wide. Doors through which patients or equipment do not pass shall be not less
than thirty (30) inches wide, except that doors to patient closets may not be
less than twenty (20) inches wide;
(i) When a door swings out on any platform,
balcony, or porch or terrace, the minimum width of the platform, balcony, porch
or terrace shall be thirty (30) inches plus the width of the door, measured at
right angles to the wall containing the door. Exit doors, other than for living
units shall swing in the direction of exit from the structure;
(j) Corridors in areas used by patients shall
not be less than eight (8) feet in clean width. Handrails may project into
corridors, but drinking fountains, desk or other projections or obstructions
may not reduce the eight (8) foot minimum dimension;
(k) Ramps shall be not less than forty-four
(44) inches wide. Where ramps provide a change of corridor level, the minimum
width shall be not less than that of the corridor;
(l) The maximum slope of ramps shall be not
greater than ten (10) percent. Changes in direction, if any, shall be on level
landings with a minimum width the same as the ramp width;
(m) Ramps shall have a nonslip finish. Ramps
serving as a required means of egress shall be enclosed or protected as
indicated for required stairways;
(n) Handrails shall be provided on each side
of all patient corridors and on each side of stairways and ramps.
(30) Light and Ventilation:
(a) The total glass area in patient bedrooms
shall be not less than one-eighth of the floor area of the room. The
ventilating area shall be not less than four (4) percent of the floor
area;
(b) Openings providing
required natural light, which open on a covered porch whose depth exceeds four
(4) feet, shall be increased in area ten (10) percent per foot of depth over
four (4) feet;
(c) The heads of
windows (sash opening) shall not be more than one foot below the finished
ceiling unless they are at least six (6) feet eight (8) inches above the
finished floor. The lower level of the window glass shall be not more than
forty-eight (48) inches above the floor level;
(d) Ceiling lights shall be not less than
eight (8) feet except that seven (7) feet six (6) inches may be used in
corridors, halls, toilet rooms and bathrooms;
(e) The lower edge of patient bedroom windows
shall in every instance be above grade.
(31) Mechanical:
(a) All bathrooms and toilet rooms shall be
provided with mechanical ventilation capable of producing a minimum of ten (10)
air changes per hour. Utility rooms, community rooms and corridors shall be
provided with not less than four (4) changes per hour with at least two (2) of
the air changes being outside air. Ducts ventilating bathrooms or toilet rooms
shall not be interconnected with other duct systems but shall be discharged to
the outside. Patient rooms shall be provided with at least two (2) air changes
per hour of outside air. Corridors and exit halls shall not be used as a plenum
for supply or return air to heating or air-conditioning system;
(b) Kitchens, laundries, non-refrigerated
garbage storage rooms, and rooms used to store combustible materials, shall be
provided with an independent system of mechanical ventilation discharging above
the roof and remote from any window. A minimum of ten (10) air changes per hour
shall be provided. Exhaust hoods shall be installed over cooking
ranges;
(c) All buildings shall be
provided with a heating system designed to maintain a temperature of 75 degrees
Fahrenheit in all habitable rooms and corridors when the outside temperature is
at design level. The heating system should provide warm floors;
(d) All steam-operated equipment such as
sterilizers, laundry and kitchen units, shall be provided with steam at
temperatures and pressures as recommended by the equipment
manufacturers;
(e) The quality and
quantity of the water supply and the method of sewage disposal shall have the
approval of the Department;
(f) The
method employed to heat water shall provide an adequate supply of hot water at
necessary temperatures for all purposes, in a safe manner;
(g) Temperature controls shall be provided so
that hot water for personal uses shall not exceed 110 degrees
Fahrenheit;
(h) Hot water
temperatures for other uses shall be as required by the equipment
served;
(i) The quantity of hot
water for kitchens and laundries shall be adequate to serve the equipment
installed;
(j) Wrist control
handles shall be provided for sinks or lavatories in floor pantries, medicine
preparation rooms, clean utility rooms, soiled utility rooms, treatment or
examination rooms, rehabilitation or physical therapy rooms and at handwashing
fixtures in the kitchen area;
(k)
Gooseneck spouts shall be provided for sinks or lavatories in treatment or
examination rooms, physical therapy or rehabilitation rooms and at handwashing
fixtures in the kitchen area;
(l)
Vacuum breakers shall be provided for any plumbing fixture having a hose or
hoses attached or to any plumbing fixture having trim to which a hose may be
attached, including shampoo sinks, service sinks, combination hot and cold
water outlets at can wash areas. Hose bibs shall be provided for clean-up
purposes in the dishwash area of kitchens;
(m) Aerators shall not be included as part of
trim for plumbing fixtures;
(n)
With relationship to adjacent areas, a positive air pressure shall be provided
for clean utility rooms, floor pantries and medicine preparation
rooms;
(o) With relationship to
adjacent areas, a negative air pressure shall be provided for soiled utility
rooms, physical therapy or rehabilitation rooms, janitor's closets, soiled
laundry rooms and bathrooms or toilets. Air from these rooms shall not be
recirculated; air shall be exhausted;
(p) Floor grilles shall not be used for
supply or return air openings in heating, air-conditioning or ventilating
systems;
(q) Ventilation openings,
such as ports for exhaust fans, etc., shall be equipped with covers that close
automatically when the fan is not in operation;
(r) Intake air ducts shall be designed and
maintained so as to prevent the entrance of dust and insects;
(s) Hot air ducts from the heating system
shall not emit temperatures in excess of 150 degrees Fahrenheit.
(32) Electrical:
(a) All areas shall be adequately lighted as
required for duties performed in each space. Bedrooms and combination
living-bedrooms shall have a night light, a light for general illumination and
a reading light at the head of each bed. The outlets for general illumination
and night lights shall be switched at the door. The reading light shall be
controlled at the bedside. Each stairway, hall, corridor or general passage
shall have five (5) foot candles of illumination, doubled at building and stair
entrance, or change of floor level, or at ramps;
(b) Receptacles appropriate for the designed
space use shall be located where plug-in service is required. There shall be
not less than one duplex receptacle at the head or near the head of each bed.
All other spaces shall have general and special purpose outlets suited to the
need of the space; including an outlet in the lobby for an electric clock and
receptacles for cleaning and maintenance equipment spaced not more than fifty
(50) feet apart in corridors;
(c)
Emergency lighting supplied by an emergency generator or a battery with
automatic switch, shall be provided for exits, stairs and corridors;
(d) Each toilet room and bathroom and each
bed location shall be furnished with an electrical or mechanical nurses' call
audible or visible at the nurses' station. A duplex unit may be used for two
beds.
(33) Elevators and
Dumbwaiters:
(a) Where patients' rooms are
located on more than one floor at least one elevator shall be provided. Other
elevators shall be provided, depending upon the needs and size of the
home;
(b) At least one elevator in
multistory buildings shall be arranged of sufficient size to admit a stretcher
and an attendant;
(c) Elevator
doors shall be automatic slide type with safety interlock. Elevators shall be
equipped with hand rails and automatic self-leveling control which will
automatically bring car platforms level with the landing;
(d) Dumbwaiter cabs shall be not less than
twenty-four (24) by thirty-six (36) inches of steel with one shelf.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.