Electrical conductors and electrical equipment installed and
utilized on or around carnival rides shall conform to the latest adopted
edition of National Electrical Code, NFPA 70. The following rules are stated
for emphasis and clarification and are supplement to the National Code. If any
conflict exists or appears to exist, the National Code shall have
precedence.
(a) Installation. Portable
electrical systems required by amusement rides shall be installed by a
qualified electrician.
(b)
Grounding. A carnival shall not operate until all grounding electrodes,
equipment, and safety grounding connections are secured, polarized, and tested.
The grounding conductors shall conform to the National Electrical Code, as
revised. Article 250 Grounding, Paragraph 250-94 Alternating Current Systems
and 250-95 Size of Equipment Grounding Conductors. The path to ground from
circuits, equipment and conductor enclosures shall (1) be permanent and
continuous and (2) shall have ample carrying capacity to conduct currents
liable to be imposed on it, and (3) shall have impedance sufficiently low to
limit the potential ground and to facilitate the operation of the over-current
devices in the circuit.
1. Service Ground.
Equipment or generators operating from a separate supply or supplies which are
located closer than 8 feet and all service equipment within itself shall be
bonded together. The service ground shall be established by connecting the
grounding conductor to the service entrance neutral bar in the hot truck or
generator and to an approved type service grounding electrode such as ground
rods. A sufficient number of ground rods shall be spaced not less than 6 feet
apart and at secure depth to obtain and maintain 25 ohms or less resistance to
ground. A resistance of 3 ohms or less shall exist when grounding to a water
system.
2. Generator Grounding.
Where electrical power is supplied for an amusement ride by a privately
operated generating system, the generator and all equipment shall be properly
grounded if the system incorporated a ground.
3. Circuit and Equipment Safety. From the
service entrance neutral bar, the circuit grounded and equipment safety
grounding conductors shall be continuous and separate throughout the entire
system. The portable outlet and terminal boxes shall contain a service ground
through grounded receptacles for both circuit and safety. The equipment safety
grounding conductors shall be attached to each ride such that a grounding
resistance of 25 ohms or less is obtained. Separate steel tracks or steel
framework, such as relief coaster tracks or big slides, shall have grounding
the same as the service equipment.
(c) Current Limiting Devices. Conductors
shall be fused or protected to their current carrying capacities. No more than
6 disconnect switches are to be in the hot truck or generator unless a main
switch is provided. All distribution lines from hot trucks or generators shall
be either 100 amp. capacity. No fuses or current limiting devices shall be
installed in the neutral or grounding conductors. Motors and lighting circuits
shall be fused separately.
(d) High
Voltage Lines. The outlets of electric power lines carrying more than 120 volts
shall be clearly marked to show their voltages.
(e) Outdoor Apparatus and Wiring. Electrical
apparatus and wiring located outdoors shall be of such quality and so
constructed or protected that exposure to weather will not interfere with its
normal operation.
(f) Elevated
Lines. Elevated power lines crossing access or other roads within the grounds
of a carnival or fair shall be suspended as to provide minimum vertical
clearance of 12 feet from the road surface and minimum horizontal clearance of
3 feet on each side of the normal passage space of vehicles.
(g) Bus Bars. Bus bars shall be located low
or near the bottom of the cabinet. Separate bus bars shall be provided for
grounding neutral and phase conductors. Color codes painted on inside and
outside of box, but not on contact surfaces of bus bars, are to be:
Ground-Green With Yellow Strip 1st Phase-Black
Neutral-White or Natural Gray 2nd Phase-Red
3rd Phase-Blue
On a 4 wire delta connected secondary, the phase conductor
having the higher voltage to ground shall be arranged. These color codes are to
carry on through all connected wiring from service through portable power
outlets and terminal boxes. Buses shall not be less than 200 ampere capacity.
The load terminals in a switchboard or panel board shall be located so that it
will be unnecessary to reach across or beyond a live bus (hot bus) to make a
local connection.
(h)
Portable Power Outlet and Terminal Box. Boxes are to be rain tight and kept
locked during the time when the general public is in the area. Wood boxes may
be used if insulated on all sides with fire resistant material or painted with
insulating varnish. The service power shall be connected to the box by
receptacles mounted on the exterior wall which includes the safety grounding.
The distribution within the box shall be accomplished by neutral terminal
bar(s) and circuit breakers or fuses. The branch circuits which include the
equipment safety grounding shall obtain their power through receptacles mounted
on the exterior of the box. The exterior openings of the receptacles must be at
least 6 inches above ground level and provided with a protective cover,
draining eave, or canvas that will avoid the possibility of rain on the
receptacle. If it is required to run conductors directly through an opening on
the wall of the box for additional service or to obtain required amperage, the
opening(s) shall be color coded and shall be sized to prevent public
accessibility to the interior of the box. The fuses or breakers in the boxes
shall be secured permanently in place, and all connections to the bus bars
within the boxes shall be made with threaded screws and lugs of the proper size
to fasten in place.
(i) Power
Sources. Electrical power sources shall be located in a manner permitting
proper maintenance and shall be protected either by guards, fencing, or
enclosure to prevent exposure to hazard and to secure the equipment from the
public.