Ga. Comp. R. & Regs. R. 391-3-5-.11 - Storage Tanks
(1)
Tank Requirements. All storage tanks must be provided with a
permanent cover, screened vents and openings, overflow piping and means of
draining.
(2)
Interior
Paint. The paint used for the interior of a storage tank must be
approved by the Division.
(3)
Approval for Repairs. Repairs and renovations to existing storage
tanks that may affect the quality of the drinking water must receive approval
from the Division prior to starting such work. Upon completion of such work the
storage tank must be disinfected according to Rule
391-3-5-.12.
(4)
Contamination Prevention. It
is the owner's responsibility to maintain the storage tank or tanks to prevent
contamination of the drinking water by infiltration or other means.
(5)
Buried Tanks. Buried or
semi-buried storage tanks must have the ground surface sloping away from the
facility.
(6)
Pressure
Tanks. Hydropneumatic pressure tanks must be provided with devices for
maintaining the air-water volume at the designed water level and working
pressures.
(7)
Pre-Service
Requirements. All new storage tanks must be cleaned, tested for leakage,
and must be disinfected according to Rule
391-3-5-.12.