Ga. Comp. R. & Regs. R. 391-3-5-.13 - Cross Connections
(1)
Prohibitions. No person
shall construct, maintain or operate a physical arrangement whereby a public
water system is or may be connected directly or indirectly with a non-potable
water system or non-permitted water system, sewer, drain, conduit, pool,
storage reservoir, plumbing fixture, or other device which contains or may
contain contaminated water, liquid, gasses, sewage or other waste of unknown or
unsafe quality, which may be capable of imparting contamination to the public
water system as the results of backflow, bypass arrangements, jumper
connections, removable sections, swivel or changeover devices, or other
temporary, permanent or potential connections through which or because of which
back-flow or back-siphonage could or would occur.
(2)
Contamination Prevention. A
supplier of water or any person having possession or control of facilities
which may cause the contamination of a public water system has the
responsibility to prevent water from unapproved sources or any contaminants
from entering the public water system by such physical arrangements cited in
paragraph (1) of this Section.
(3)
Purchasers and Resellers. Any person connecting to and purchasing
water from a public water system and reselling it to others is considered a
supplier of the water so purchased as well as a consumer, and is also
responsible for the quality of such water.
(4)
Cross-Connection Control
Program. A supplier shall, when requested by the Division, develop a
control program for the elimination and prevention of all cross-connections. A
written plan for the program shall be submitted to the Division for review and
approval within two (2) years or less in accordance with a written request by
the Division. When the plan is approved, the owner shall implement the program
immediately.
(5)
Conformance
with National Standards. The procedures for back-flow and back-siphonage
prevention and cross-connection control shall conform to those recommended by
the American Water Works Association, Manual 14, and the U.S. Environmental
Protection Agency Cross-Connection Manual.
(6)
Backflow Prevention Assemblies
Field Testing. The supplier shall require that all backflow prevention
assemblies installed pursuant to this section be field tested following
installation, repair, or relocation and at least annually thereafter.
(7)
Certified Backflow Testing.
After October 1, 2004, all required field testing shall be performed by persons
who are certified in the testing of backflow prevention assemblies by the
Georgia Statewide Backflow Prevention Assembly Certification Program, as
approved by the Division, the American Backflow Prevention Association (ABPA),
the American Society of Sanitary Engineers (ASSE) or the University of Florida
TREEO Center.
(8)
Gauge
Accuracy. Gauges used in the testing of backflow prevention assemblies
shall be tested for accuracy annually in accordance with the University of
Southern California Manual of Cross-Connection Control or American Water Works
Association Manual 14. Public water systems shall require testers to include
test gauge serial numbers on "Test and Maintenance" report forms and ensure
testers have gauges tested for accuracy.
(9)
Record Maintenance. Each
water supplier shall maintain records of the following for a minimum of three
(3) years:
(a) Most current hazard
assessment, conducted pursuant to Section 608 of the Georgia State Minimum
Standard Plumbing Code (International Plumbing Code);
(b) Locations and types of backflow
protection and associated hazards;
(c) Results of all backflow prevention
assembly field testing and air gap inspections; and
(d) Repairs made to, or replacement or
relocation of, backflow protection.
(e) Summaries of the information in sections
(9)(a) - (d) shall be available to the Division on request for a minimum of
three years.
(f) The supplier shall
ensure that backflow prevention assemblies that fail the field test are
repaired or replaced within thirty (30) days.
(g) The supplier shall ensure that bypass
piping installed around any approved backflow preventer is equipped with a
backflow preventer providing an equivalent level of protection.
(h) Reduced pressure principal backflow
prevention assemblies shall not be installed in any location subject to
possible flooding. This includes pits and/or vaults which are not provided with
a gravity drain to the ground's surface that is capable of exceeding the
discharge rate of the relief valve.
(i) Each supplier shall notify the Division
of any known incident of backflow into the public water system as soon as
possible but no later than the end of the next business day upon discovery of
the incident. If requested to do so by the Division, the supplier shall submit
a written report of the incident describing the nature and severity of the
backflow, the actions taken by the water supplier in response to the incident,
and the action plan intended to prevent such incidents in the future.
(j) The supplier of water shall deny or
discontinue water service to a commercial consumer if a required backflow
prevention device is not installed or properly maintained. Water service shall
not be restored to such premises until the deficiencies have been corrected or
eliminated to the satisfaction of the supplier and the Division. Residential
connections shall be maintained in accordance with the Georgia State Minimum
Standard Plumbing Code (International Plumbing Code).