(1)
Routine Coliform Monitoring.
(a)
Public water systems must collect total coliform samples at sites which are
representative of water throughout the distribution system according to a
written sample siting plan. These plans are subject to Division review and
revision.
(b) The minimum
residential population of a community water system shall be determined by a
mathematical calculation of the total number of active residential service
connections multiplied by Georgia's average population per household, as
published in the most recent Federal Census Bureau Statistics. Multiple
residential units served by a single connection (master meter) shall be
included in the determination of population for a water system. The minimum
monitoring frequency for total coliforms for community water systems is based
on the population served by the system, as follows:
|
Population
Served
|
Minimum Number of Samples per
Month
|
|
25 to
1,0001
|
1
|
|
1,001 to 2,500
|
2
|
|
2,501 to 3,300
|
3
|
|
3,301 to 4,100
|
4
|
|
4,101 to 4,900
|
5
|
|
4,901 to 5,800
|
6
|
|
5,801 to 6,700
|
7
|
|
6,701 to 7,600
|
8
|
|
7,601 to 8,500
|
9
|
|
8,501 to 12,900
|
10
|
|
12,901 to 17,200
|
15
|
|
17,201 to 21,500
|
20
|
|
21,501 to 25,000
|
25
|
|
25,001 to 33,000
|
30
|
|
33,001 to 41,000
|
40
|
|
41,001 to 50,000
|
50
|
|
50,001 to 59,000
|
60
|
|
59,001 to 70,000
|
70
|
|
70,001 to 83,000
|
80
|
|
83,001 to 96,000
|
90
|
|
96,001 to 130,000
|
100
|
|
130,001 to 220,000
|
120
|
|
220,001 to 320,000
|
150
|
|
320,001 to 450,000
|
180
|
|
450,001 to 600,000
|
210
|
|
600,001 to 780,000
|
240
|
|
780,001 to 970,000
|
270
|
|
970,001 to 1,230,000
|
300
|
|
1,230,001 to 1,520,000
|
330
|
|
1,520,001 to 1,850,000
|
360
|
|
1,850,001 to 2,270,000
|
390
|
|
2,270,001 to 3,020,000
|
420
|
|
3,020,001 to 3,960,000
|
450
|
|
3,960,001 or more
|
480
|
1Includes public water systems
which have at least 15 service connections, but serve fewer than 25
persons.
If a community water system serving 25 to 1,000 persons has
no history of total coliform contamination in its current configuration and a
sanitary survey conducted in the past five years shows that the system is
supplied solely by a protected ground water source and is free of sanitary
defects, the Division may reduce the monitoring frequency specified above,
except that in no case shall it be reduced to less than one sample per
quarter.
(c) The monitoring
frequency for total coliform for non-community water systems is as follows:
1. A non-community water system using only
ground water (except ground water under the direct influence of surface water)
and serving 1,000 persons or fewer must monitor each calendar quarter that the
system provides water to the public, except that the Division may adjust this
monitoring frequency in writing, if a sanitary survey shows that the system is
free of sanitary defects.
2. A
non-community water system using only ground water (except ground water under
the direct influence of surface water) and serving more than 1,000 persons
during any month must monitor at the same frequency as a like-sized community
water system, except that the Division may adjust this monitoring frequency, in
writing for any month the system serves 1,000 persons or fewer.
3. A non-community water system using surface
water, in total or in part, must monitor at the same frequency as a like-sized
community water system, regardless of the number of persons it
serves.
4. A non-community water
system using ground water under the direct influence of surface water must
monitor at the same frequency as a like-sized community water system. The
system must begin monitoring at this frequency beginning six months after the
Division determines that the ground water is under the direct influence of
surface water.
(d) The
public water system must collect samples at regular time intervals throughout
the month, except that a system which uses only ground water (except ground
water under the direct influence of surface water), and serves 4,900 persons or
fewer, may collect all required samples on a single day if they are taken from
different sites.
(e) Special
purpose samples, such as those taken to determine whether disinfection
practices are sufficient following pipe placement, replacement, or repair,
shall not be used to determine compliance with the MCL for total coliforms.
Repeat samples are not considered special purpose samples, and must be used to
determine compliance with the MCL for total coliforms.
(2)
Repeat Coliform Monitoring.
(a) If a routine sample is total
coliform-positive, the public water system must collect a set of repeat samples
within 24 hours of being notified of the positive result. A system which
collects more than one routine sample per month must collect no fewer than
three repeat samples for each total coliform-positive sample found. A system
which normally collects one routine sample per month or fewer must collect no
fewer than four repeat samples for each total coliform-positive sample found.
The Division may extend the 24- hour limit on a case-by-case basis if the
system has a logistical problem in collecting the repeat samples within 24
hours that is beyond its control.
(b) The system must collect at least one
repeat sample from the sampling tap where the original total coliform-positive
sample was taken, and at least one repeat sample at a tap within five service
connections upstream and at least one repeat sample at a tap within five
service connections downstream of the original sampling site. If a total
coliform-positive sample is at the end of the distribution system, or
one away from the end of the distribution system, the Division may waive the
requirement to collect at least one repeat sample upstream or downstream of the
original sampling site.
(c) The
system must collect all repeat samples on the same day, except that the
Division may allow a system with a single service connection to collect the
required set of repeat samples over a four-day period.
(d) If one or more repeat samples in the set
is total coliform-positive, the public water system must collect an additional
set of repeat samples in the manner specified in paragraph (2). The additional
samples must be collected within 24 hours of being notified of the positive
result, unless the Division extends the limit as provided in paragraph (2). The
system must repeat this process until either total coliforms are not detected
in one complete set of repeat samples or the system determines that the MCL for
total coliforms has been exceeded and notifies the Division.
(e) If a system collecting fewer than five
routine samples per month has one or more total coliform-positive samples and
the Division does not invalidate the sample(s), it must collect at least five
routine samples during the next month the system provides water to the public,
except that the Division may waive this requirement if the conditions specified
below are met. The Division cannot waive the requirement for a system to
collect repeat samples.
1. The Division may
waive the requirement to collect five routine samples the next month the system
provides water to the public if the Division, or an agent approved by the
Division, performs a site visit before the end of the next month the system
provides water to the public. Although a sanitary survey need not be performed,
the site visit must be sufficiently detailed to allow the Division to determine
whether additional monitoring and/or any corrective action is needed. The
Division cannot approve an employee of the system to perform this site visit,
even if the employee is an agent approved by the Division to perform sanitary
surveys.
2. The Division may waive
the requirement to collect five routine samples the next month the system
provides water to the public if the Division has determined why the sample was
total coliform-positive and establishes that the system has corrected the
problem or will correct the problem before the end of the next month the system
serves water to the public. The Division cannot waive the requirement to
collect five routine samples the next month the system provides water to the
public solely on the grounds that all repeat samples are total
coliform-negative. Under this paragraph, a system must still take at least one
routine sample before the end of the next month it serves water to the public
and use it to determine compliance with the MCL for total coliforms, unless the
Division has determined that the system has corrected the contamination problem
before the system took the set of repeat samples required above, and all repeat
samples were total coliform-negative.
(f) After a system collects a routine sample
and before it learns the results of the analysis of that sample, if it collects
another routine sample(s) from within five adjacent service connections of the
initial sample, and the initial sample, after analysis, is found to contain
total coliforms, then the system may count the subsequent sample(s) as a repeat
sample instead of as a routine sample.
(g) Results of all routine and repeat samples
not invalidated by the Division must be included in determining compliance with
the MCL for total coliforms.
(3)
Invalidation of Total Coliform
Samples. A total coliform-positive sample invalidated under this
paragraph does not count towards meeting the minimum monitoring requirements of
this Rule.
(a) The Division may invalidate a
total coliform-positive sample only if the conditions that follow below are
met:
1. The laboratory establishes that
improper sample analysis caused the total coliform-positive
result.
2. The Division, on the
basis of the results of repeat samples collected as required by this Rule,
determines that the total coliform-positive sample resulted from a domestic or
other non-distribution system plumbing problem. The Division cannot invalidate
a sample on the basis of repeat sample results unless all repeat sample(s)
collected at the same tap as the original total coliform-positive sample are
also total coliform-positive, and all repeat samples collected within five
service connections of the original tap are total coliform-negative (e.g., the
Division cannot invalidate a total coliform-positive sample on the basis of
repeat samples if all the repeat samples are total coliform-negative, or if the
public water system has only one service connection).
3. The Division has substantial grounds to
believe that a total coliform-positive result is due to a circumstance or
condition which does not reflect water quality in the distribution system. In
this case, the system must still collect all repeat samples required under this
Rule, and use them to determine compliance with the MCL for total coliforms.
The Division may not invalidate a total coliform-positive sample solely on the
grounds that all repeat samples are total coliform-negative.
(b) A laboratory must invalidate a
total coliform sample (unless total coliforms are detected) if the sample
produces a turbid culture in the absence of gas production using an analytical
method where gas formation is examined (e.g., the Multiple-Tube Fermentation
Technique), produces a turbid culture in the absence of an acid reaction in the
Presence-Absence (P-A) Coliform Test, or exhibits confluent growth or produces
colonies too numerous to count with an analytical method using a membrane
filter (e.g., Membrane Filter Technique). If a laboratory invalidates a sample
because of such interference, the system must collect another sample from the
same location as the original sample within 24 hours of being notified of the
interference problem, and have it analyzed for the presence of total coliforms.
The system must continue to re-sample within 24 hours and have the samples
analyzed until it obtains a valid result. The Division may waive the 24-hour
time limit on a case-by-case basis.
(4)
Sanitary Surveys.
(a) All ground water systems must undergo
sanitary surveys no less frequently than every three years for community
systems, except as provided in paragraph (4)(b), and no less frequently than
every five years for non-community systems. The initial sanitary survey for
each community ground water system must be conducted by December 31, 2012,
unless the system meets requirements of paragraph (4)(b).
(b) For community ground water systems
determined by the Division to have outstanding performance based on prior
sanitary surveys, or that provide at least 4-log (99.99%) treatment of viruses
(using inactivation, removal, or a combination of the two) subsequent sanitary
surveys may be conducted no less than every five years. The initial sanitary
survey for community systems that meet these requirements and for each
non-community system must be conducted by December 31, 2014.
(c) All surface water systems (including
ground water under the influence) must undergo sanitary surveys no less
frequently than every three years for community systems and no less frequently
than every five years for non-community systems. For community systems
determined by the Division to have outstanding performance based on prior
sanitary surveys, subsequent sanitary surveys may be conducted no less than
every five years.
(d) Sanitary
surveys must be performed by the Division or an agent approved by the Division.
The system is responsible for ensuring the survey takes place.
(5)
Fecal Coliforms -
Escherichia coli (E. coli) Testing.
(a) If any routine or repeat sample is total
coliform-positive, the system must analyze that total coliform-positive culture
medium to determine if fecal coliforms are present, except that the system may
test for E. coli in lieu of fecal coliforms. If fecal
coliforms or E. coli are present, the system must notify the
Division by the end of the day when the system is notified of the test result,
unless the system is notified of the result after the Division office is
closed, in which case the system must notify the Division before the end of the
next business day.
(b) The Division
has the discretion to allow a public water system, on a case-by-case basis, to
forego fecal coliform or E. coli testing on a total
coliform-positive sample if that system assumes that the total
coliform-positive sample is fecal coliform-positive or E.
coli-positive. Accordingly, the system must notify the Division as
specified in this Rule and the MCL applies.
(6)
Analytical Methodology.
(a) The standard sample volume required for
total coliform analysis, regardless of analytical method used, is 100
mL.
(b) Public water systems need
only determine the presence or absence of total coliforms; a determination of
total coliform density is not required.
(c) Public water systems must conduct total
coliform analyses in accordance with
40 CFR §
141.21.
(d) Public water systems must conduct fecal
coliform analyses in accordance with
40 CFR §
141.21.
(7)
Response to Violation.
(a) A public water system which has exceeded
the MCL for total coliforms must report the violation to the Division no later
than the end of the next business day after it learns of the violation, and
notify the public in accordance with this chapter.
(b) A public water system which has failed to
comply with a coliform monitoring requirement, including the sanitary survey
requirement, must report the monitoring violation to the Division within ten
days after the system discovers the violation, and notify the public in
accordance with this chapter.
(8) The provisions of paragraphs (1) and (4)
are applicable until March 31, 2016. The provisions of paragraphs (2), (3),
(5), (6), and (7) are applicable until all required repeat monitoring under
paragraph (2) and fecal coliform or
E. coli testing under
paragraph (5) that was initiated by a total coliform-positive sample taken
before April 1, 2016 is completed, as well as analytical method, reporting,
recordkeeping, public notification, and consumer confidence report requirements
associated with that monitoring and testing. Beginning April 1, 2016, the
provisions of Rule
391-3-5-.55 are applicable, with
systems required to begin regular monitoring at the same frequency as the
system-specific frequency required on March 31, 2016, except for seasonal
systems which must monitor monthly beginning April 1, 2016.