Haw. Code R. § 11-21-8 - Maintenance requirements
(a) It shall be the
responsibility of water users to maintain all backflow preventors and vacuum
breakers within the building or on the premises in good working order. No
piping or other arrangement for the purpose of bypassing backflow devices shall
be permitted.
(b) Periodic testing
and inspection schedule shall be established by the director for all backflow
preventors in intervals between such testing, inspection and overhauls of each
devices shall be established in accordance with age and condition of the
backflow prevention device. Inspection intervals should not exceed one year.
Backflow prevention devices should be inspected frequently after initial
installation to assure that the devices are properly installed and debris
resulting from the installation has not interfered with the functioning of the
device. The inspection and testing shall be performed by a certified tester
approved by the director. In those instances where the director deems the
hazard to be great, inspections may be required at more frequent intervals.
Records of any tests, repairs and overhauls shall be kept and made on forms
prescribed by the director. Should the water user fail to make the proper test
and provide all records on the test, the director at his discretion may perform
the necessary test, needed repairs, and replacements and charge the cost
thereof to the water consumer.