Haw. Code R. § 11-264-191 - Assessment of existing tank system's integrity
(a) For each
existing tank system that does not have secondary containment meeting the
requirements of section 11-264-193, the owner or operator must determine that
the tank system is not leaking or is unfit for use. Except as provided in
subsection (c), the owner or operator must obtain and keep on file at the
facility a written assessment reviewed and certified by an independent,
qualified registered professional engineer, in accordance with subsection
11-270-11(d), that attests to the tank system's integrity by the effective date
of these rules.
(b) This assessment
must determine that the tank system is adequately designed and has sufficient
structural strength and compatibility with the waste(s) to be stored or
treated, to ensure that it will not collapse, rupture, or fail. At a minimum,
this assessment must consider the following:
(1) Design standard(s), if available,
according to which the tank and ancillary equipment were constructed;
(2) Hazardous characteristics of the waste(s)
that have been and will be handled;
(3) Existing corrosion protection
measures;
(4) Documented age of the
tank system, if available (otherwise, an estimate of the age); and
(5) Results of a leak test, internal
inspection, or other tank integrity examination such that:
(i) For non-enterable underground tanks, the
assessment must include a leak test that is capable of taking into account the
effects of temperature variations, tank end deflection, vapor pockets, and high
water table effects, and
(ii) For
other than non-enterable underground tanks and for ancillary equipment, this
assessment must include either a leak test, as described above, or other
integrity examination, that is certified by an independent, qualified,
registered professional engineer in accordance with subsection 11-270-11(d),
that addresses cracks, leaks, corrosion, and erosion.
(c) Tank systems that store or
treat materials that become hazardous wastes on the effective date of these
rules must conduct this assessment by the effective date of these rules. Tank
systems that store or treat materials that become hazardous wastes subsequent
to the effective date of these rules must conduct this assessment within twelve
months after the date that the waste becomes a hazardous waste.
(d) If, as a result of the assessment
conducted in accordance with subsection (a), a tank system is found to be
leaking or unfit for use, the owner or operator must comply with the
requirements of section 11-264-196.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.