Haw. Code R. § 11-280.1-11 - Installation requirements for partially excluded UST systems
(a) Owners and operators must install an UST
system listed in section
11-280.1-10(c)(1), (3), or
(4) storing regulated substances (whether of
single or double wall construction) that meets the following requirements:
(1) Will prevent releases due to corrosion or
structural failure for the operational life of the UST system;
(2) Is cathodically protected against
corrosion, constructed of non-corrodible material, steel clad with a
non-corrodible material, or designed in a manner to prevent the release or
threatened release of any stored substance; and
(3) Is constructed or lined with material
that is compatible with the stored substance.
(b) Notwithstanding subsection (a), an UST
system without corrosion protection may be installed at a site that is
determined by a corrosion expert not to be corrosive enough to cause it to have
a release due to corrosion during its operating life. Owners and operators must
maintain records that demonstrate compliance with the requirements of this
subsection for the remaining life of the tank.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
(a) Owners and operators must install an UST system listed in section 11-280.1-10(c)(1), (3), or (4) storing regulated substances (whether of single or double wall construction) that meets the following requirements:
(1) Will prevent releases due to corrosion or structural failure for the operational life of the UST system ;
(2) Is cathodically protected against corrosion, constructed of non-corrodible material, steel clad with a non-corrodible material, or designed in a manner to prevent the release or threatened release of any stored substance; and
(3) Is constructed or lined with material that is compatible with the stored substance.
(b) Notwithstanding subsection (a), an UST system without corrosion protection may be installed at a site that is determined by a corrosion expert not to be corrosive enough to cause it to have a release due to corrosion during its operating life. Owners and operators must maintain records that demonstrate compliance with the requirements of this subsection for the remaining life of the tank .