Haw. Code R. § 11-280.1-21 - Upgrading of UST systems
(a) All UST systems
must comply with one of the following requirements:
(1) UST system performance standards in
section 11-280. 1-20(b) to (d);
(2)
For airport hydrant fuel distribution systems and UST systems with
field-constructed tanks installed before July 15, 2018:
(A) The system performance standards in
section 11-280.1-20(b) and
(c); and
(B) Not later than July 15, 2019, the system
performance standards under section
11-280.1-20(d);
or
(3) Closure
requirements under subchapter 7.
(b) UST systems other than airport hydrant
fuel distribution systems and UST systems with field-constructed tanks: Not
later than July 15, 2028, tanks and piping installed before August 9, 2013 must
be provided with secondary containment that meets the requirements of section
11-280.1-24, except for suction
piping that meets the requirements of section
11-280.1-41(b)(6).
(c) Airport hydrant fuel distribution systems
and UST systems with field-constructed tanks: Not later than July 15, 2038,
tanks and piping installed before July 15, 2018 must be provided with secondary
containment that meets the requirements of section
11-280.1-24 or must utilize a
design which the director determines is protective of human health and the
environment, except for:
(1) Suction piping
that meets the requirements of section
11-280.1-41(b)(6);
(2) Piping associated with UST systems with
field-constructed tanks with a capacity greater than 50,000 gallons;
and
(3) Piping associated with
airport hydrant systems.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
(a) All UST systems must comply with one of the following requirements:
(1) UST system performance standards in section 11-280.1-20(b) to (d);
(2) For airport hydrant fuel distribution systems and UST systems with field-constructed tanks installed before the effective date of these rules:
(A) The system performance standards in section 11-280.1-20(b) and (c); and
(B) Not later than one year after the effective date of these rules, the system performance standards under section 11-280.1-20(d); or
(3) Closure requirements under subchapter 7.
(b) UST systems other than airport hydrant fuel distribution systems and UST systems with field-constructed tanks: Not later than ten years after the effective date of these rules, tanks and piping installed before August 9, 2013 must be provided with secondary containment that meets the requirements of section 11-280.1-24, except for suction piping that meets the requirements of section 11-280.1-41(b)(6).
(c) Airport hydrant fuel distribution systems and UST systems with field-constructed tanks: Not later than twenty years after the effective date of these rules, tanks and piping installed before the effective date of these rules must be provided with secondary containment that meets the requirements of section 11-280.1-24 or must utilize a design which the director determines is protective of human health and the environment, except for;
(1) Suction piping that meets the requirements of section 11-280.1-41(b)(6);
(2) Piping associated with UST systems with field-constructed tanks greater than 50,000 gallons; and
(3) Piping associated with airport hydrant systems.