Haw. Code R. § 11-280.1-25 - Under-dispenser containment

(a) Dispenser systems installed on or after August 9, 2013, other than for airport hydrant fuel distribution systems and UST systems with field-constructed tanks, must have under-dispenser containment that meets the requirements in subsection (c).
(b) Dispenser systems installed on or after July 15, 2018 must have under-dispenser containment that meets the requirements in subsection (c).
(c) Under-dispenser containment required by subsection (a) or (b) must:
(1) Be liquid-tight on its sides, bottom, and at any penetrations;
(2) Be compatible with the substance conveyed by the piping; and
(3) Meet one of the following requirements:
(A) Allow for visual inspection and access to the components in the containment system; or
(B) Be monitored for leaks from the dispenser system with a sensing device that signals the operator of the presence of regulated substances.

Notes

Haw. Code R. § 11-280.1-25
[Eff 7/15/2018] (Auth: HRS §§ 342L-3, 342L-32) (Imp: HRS §§ 342L-3, 342L-32) Comp 1/17/2020 Am and comp 7/8/21; Comp 3/21/2025