Haw. Code R. § 11-280.1-44 - Methods of release detection for piping
Each method of release detection for piping used to meet the requirements of sections 11-280.1-40 to 11-280.1-42 must be conducted in accordance with the following:
MAXIMUM LEAK DETECTION RATE PER TEST SECTION VOLUME
|
Test section volume (gallons) |
Semiannual test-leak detection rate not to exceed (gallons per hour) |
Annual test-leak detection rate not to exceed (gallons per hour) |
|
<50,000..................... |
1.0 |
0.5 |
|
>=50,000 to <75,000......... |
1.5 |
0.75 |
|
>=75,000 to <100,000........ |
2.0 |
1.0 |
|
>=100,000 |
3.0 |
1.5 |
PHASE IN FOR PIPING SEGMENTS >=100,000 GALLONS IN VOLUME
|
First test................ |
Not later than July 15, 2021 (may use up to 6.0 gph leak rate). |
|
Second test........... |
Between July 15, 2021 and July 15, 2024 (may use up to 6.0 gph leak rate). |
|
Third test............... |
Between July 15, 2024 and July 15, 2025 (must use 3.0 gph for leak rate). |
|
Subsequent tests.. |
Not later than July 15, 2025 begin using semiannual or annual line testing according to the Maximum Leak Detection Rate Per Test Section Volume table above |
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
Each method of
MAXIMUM LEAK DETECTION RATE PER
| | Semiannual | Annual |
| <50,000....... | 1.0 | 0.5 |
| >=50,000 to <75,000......... | 1.5 | 0.75 |
| >=75 000 to <100,000......... | 2.0 | 1.0 |
| >=100,000...................... | 3.0 | 1.5 |
PHASE IN FOR
| First | Not later than three years after the effective date of these rules (may use up to 6.0 gph leak rate). |
| Second | Between three and six years after the effective date of these rules (may use up to 6.0 gph leak rate). |
| Third | Between six and seven years after the effective date of these rules (must use 3.0 gph for leak rate). |
| Subsequent tests.. | Not later than seven years after the effective date of these rules, begin using semiannual or annual line testing according to the Maximum Leak Detection Rate Per |