Haw. Code R. § 12-223.1-11 - Acceptable installation of temperature and pressure relief valves for potable water heaters
The following shall apply to the installation of temperature and pressure relief valves for potable water heaters:
(1) Temperature and pressure relief valves
shall be installed by either the water heater manufacturer or installer before
a water heater is placed in operation;
(2) Temperature and pressure relief valves
shall be connected directly to a tapped or flanged opening in the top of the
water heater, or to a fitting connected to the water heater by a short
nipple;
(3) Temperature and
pressure relief valves shall be installed with their spindles upright and
vertical with no horizontal connecting pipe, except when the temperature and
pressure relief valve is connected directly on the water heater vessel with no
more than four (4) inches maximum interconnecting piping, the valve may be
installed in the horizontal position with the outlet pointed down. The center
line of the temperature and pressure relief valve connection shall be no lower
than four (4) inches from the top of the shell;
(4) No piping or fitting used to install the
temperature and pressure relief valve shall be of nominal pipe size less than
that of the valve inlet;
(5) When a
potable water heater is fitted with two or more temperature and pressure relief
valves on one connection, this connection shall have a cross-sectional area not
less than the combined areas of inlet connections of all the temperature and
pressure release valves with which it connects;
(6) When a Y-base is used, the inlet area
shall be not less than the combined outlet areas;
(7) When the size of the water heater
requires a temperature and pressure relief valve larger than NPS 4 two or more
valves having the required combined capacity shall be used;
(8) When two or more valves are used on a
water heater, they may be single, directly attached, or installed on a
Y-base;
(9) A threaded connection
may be used for attaching a temperature and pressure relief valve;
(10) Temperature and pressure relief valves
shall not be connected to an internal pipe in the water heater or a cold-water
feed line connected to the water heater;
(11) No shutoff valve of any description
shall be placed between the temperature and pressure relief valve and the water
heater or on discharge pipes between such valves and the atmosphere;
and
(12) The discharge from
temperature and pressure relief valves shall be so arranged that there will be
no danger of scalding attendants. When the temperature and pressure relief
valve discharge is piped away from the water heater to the point of discharge,
there shall be provisions for properly draining the piping and valve body. The
size and arrangement of discharge piping shall be such that any pressure that
may exist or develop will not reduce the relieving capacity of the relieving
devices below that required to protect the water heater. The following shall
apply to discharge pipes:
(A) When a
discharge pipe is used, it shall be not less than the nominal size of the valve
outlet, and shall be as short and straight as possible, properly supported and
so arranged as to avoid undue stress on the valve. When an elbow is placed on a
temperature and pressure relief discharge pipe, it shall be located close to
the valve outlet;
(B) Where
multiple valves relieve into a common discharge pipe, the cross-sectional flow
area of the common discharge pipe shall be equal to or greater than the sum of
the individual temperature and pressure relief valve discharge pipe
areas;
(C) Discharge piping shall
be rated for the discharge fluid conditions of pressure and temperature
including a minimum and maximum design temperature. Material selection for the
discharge piping shall consider the reduction in material toughness at the low
end of design temperature and the reduction in material strength at the high
end of design temperature. Rigid pipe or tubing should be used for discharge
lines that carry hot water or steam;
(D) Plastic discharge pipe and fittings are
permitted (when compatible with the process fluid, system design temperatures,
and other ambient conditions such as light and humidity) and shall conform to
NSF/ANSI 14 Plastics Piping System Components and Related Materials; and
(E) Discharge piping shall be
rated for any static pressure present and the back pressure that may develop
when the pressure relief device is at full capacity. Where multiple pressure
relief devices or vents discharge into common piping, the back pressure that
could develop due to simultaneous flow from all sources shall be
considered.