Haw. Code R. § 12-223.1-7 - Instruments, fittings, and controls
(a) The following
shall apply to steam heating boilers:
(1)
Gages. The following shall apply to gages:
(A) Each steam boiler shall have a steam
gage, or a compound steam gage connected to its steam space or to its water
column or to its steam connection. The gage or connection shall contain a
siphon or equivalent device that will develop and maintain a water seal that
will prevent steam from entering the gage tube. The connection shall be so
arranged that the gage cannot be shut off from the boiler except by a cock
placed in the pipe at the gage and provided with a tee-handle or lever-handle
arranged to be parallel to the pipe in which it is located when the cock is
open. The connections to the boiler shall be not less than NPS 1/4. Where steel
or wrought iron pipe or tubing is used, the connection and external siphon
shall be not less than NPS 1/2. The minimum size of a siphon, if used, shall be
NPS 1/4. Ferrous and nonferrous tubing having inside diameters at least equal
to that of standard pipe sizes listed above may be substituted for pipe; and
(B) The scale on the dial of a
steam boiler gage shall be graduated to not less than thirty (30) psig nor more
than sixty (60) psig. The travel of the pointer from zero (0) psig to thirty
(30) psig pressure shall be at least three (3) inches;
(2) Water gage glasses. The following shall
apply to water gage glasses:
(A) Each steam
boiler shall have one or more water-gage glasses attached to the water column
or boiler by means of valved fittings not less than NPS 1/2, with the lower
fitting provided with a drain valve of a type having an unrestricted drain
opening not less than NPS 1/4 to facilitate cleaning. Gage glass replacement
shall be possible under pressure. Water glass fittings may be attached directly
to a boiler. Heating boilers having an internal vertical height of less than
ten (10) inches should be equipped with a water level indicator of the glass
bulls-eye type provided the indicator is of sufficient size to show the water
at both normal operating and low-water cutoff levels;
(B) The lowest visible part of the water-gage
glass shall be at least one (1) inch above the lowest permissible water level
recommended by the boiler manufacturer. With the boiler operating at this
lowest permissible water level, there shall be no danger of overheating any
part of the boiler;
(C) In electric
heating boilers of the submerged electrode type, the water-gage glass shall be
so located to indicate the water levels both at startup and under maximum steam
load conditions as established by the manufacturer;
(D) In electric heating boilers of the
resistance element type, the lowest visible part of the water gage shall be
located at least one (1) inch above the lowest permissible water level
specified by the manufacturer. Each electric boiler of this type shall also be
equipped with an automatic low-water cutoff on each boiler so located as to
automatically cut off the power supply to the heating elements before the
surface of the water falls below the visible part of the glass;
(E) Tubular water glasses on electric heating
boilers having a normal water content not exceeding 100 gallons shall be
equipped with a protective shield; and
(F) Transparent material other than glass may
be used for the water gage provided that the material will remain transparent
and has proved suitable for the pressure, temperature, and corrosive conditions
expected in service;
(3)
Water column and water level control pipes.
The following shall apply to water column and water level control pipes:
(A) The minimum size of
ferrous or nonferrous pipes connecting a water column to a steam boiler shall
be NPS 1. No outlet connections, except for damper regulator, feedwater
regulator, steam gages, or apparatus that does not permit the escape of any
steam or water except for manually operated blowdown, shall be attached to a
water column or the piping connecting a water column to a boiler for
introduction of feedwater into a boiler. If the water column, gage glass,
low-water fuel cutoff, or other water level control device is connected to the
boiler by pipe and fittings, no shutoff valves of any type shall be placed in
such pipe and a cross or equivalent fitting to which a drain valve and piping
may be attached shall be placed in the water piping connection at every right
angle turn to facilitate cleaning and inspection. The water column drain pipe
and valve shall be not less than 3/4-inch diameter; and
(B) The steam connections to the water column
of a horizontal firetube wrought boiler shall be taken from the top of the
shell or the upper part of the head, and the water connection shall be taken
from a point not above the center line of the shell. For a cast-iron boiler,
the steam connection to the water column shall be taken from the top of an end
section or the top of the steam header, and the water connection shall be made
on an end section not less than six (6) inches below the bottom connection to
the water-gage glass;
(4)
Pressure control. The following shall apply to pressure control:
(A) Each automatically fired steam boiler
shall be protected from overpressure by two pressure-operated controls. Each
individual steam boiler or each system of commonly connected steam heating
boilers shall have a control that will cut off the fuel supply when the steam
pressure reaches an operating limit, which shall be less than the maximum
allowable pressure;
(B) Each
individual automatically fired steam boiler shall have a safety limit control,
with a manual reset that will cut off the fuel supply to prevent steam pressure
from exceeding the fifteen (15) psig maximum allowable working pressure of the
boiler. Each control shall be constructed to prevent a pressure setting above
fifteen (15) psig;
(C) Shutoff
valves of any type shall not be placed in the steam pressure connection between
the boiler and the controls described in subparagraphs (A) and (B). These
controls shall be protected with a siphon or equivalent means of maintaining a
water seal that will prevent steam from entering the control. The connections
to the boiler shall not be less than NPS 1/4 for lengths up to five (5) feet,
but where steel or wrought iron pipe or tubing is used, they shall not be less
than NPS 1/2 for lengths up to five (5) feet, and not less than NPS 1 for
lengths over five (5) feet. The minimum size of an external siphon shall be NPS
1/4 or 3/8 inch outside diameter nonferrous tubing. For manifold connections,
the minimum size shall be as specified in the original code of construction;
and
(D) Pressure controls should
have separate connections, however, manifolding is permitted. When multiple
pressure controls are connected to the boiler with a common manifold, the
connection at the boiler up to and including the entire manifold, for pipe of
nonferrous material, shall not be less than NPS 1/2 for lengths up to five (5)
feet, and not less than NPS 3/4 for lengths over five (5) feet. For manifolds
using ferrous material, the connection at the boiler up to and including the
entire manifold shall not be less than NPS 3/4 for lengths up to five (5) feet,
and not less than NPS 1-1/4 for lengths over five (5) feet. Individual controls
are to be piped from the manifold according to the provisions of subparagraph
(C);
(5) Automatic
low-water fuel cutoff and water feeding devices. The following shall apply to
automatic low-water fuel cutoff and water feeding devices:
(A) Each automatically fired steam boiler
shall have an automatic low-water fuel cutoff. The low-water fuel cutoffs must
be located to automatically cut off the fuel supply when the surface of the
water falls to a level not lower than the lowest visible part of the water-gage
glass. If a water feeding device is installed, it shall be so constructed that
the water inlet valve cannot feed water into the boiler through the float
chamber and so located as to supply requisite feedwater;
(B) Such a fuel cutoff or water feeding
device may be attached directly to a boiler. A fuel cutoff or water feeding
device may also be installed in the tapped openings available for attaching a
water glass directly to a boiler, provided the connections are made to the
boiler with nonferrous tees or Y fittings not less than NPS 1/2 between the
boiler and water glass so that the water glass is attached directly and as
close as possible to the boiler; the run of the tee or Y-fitting shall take the
water glass fittings, and the side outlet or branch of the tee or Y-fittings
shall take the fuel cutoff or water feeding device. The ends of all nipples
shall be reamed to full-size diameter;
(C) In addition to the requirements in
subparagraphs (A) and (B), a secondary low-water fuel cutoff with manual reset
shall be provided on each automatically fired steam boiler; and
(D) Fuel cutoffs and water feeding devices
embodying a separate chamber shall have a vertical drain pipe and a blowoff
valve not less than NPS 3/4, located at the lowest point in the water
equalizing pipe connections so that the chamber and the equalizing pipe can be
flushed and the device tested.
(b) Hot-water heating or hot-water supply
boilers. The following shall apply to hot-water heating or hot-water supply
boilers:
(1) Pressure or altitude gages:
(A) Each hot-water heating or hot-water
supply boiler shall have a pressure or altitude gage connected to it or to its
flow connection in such a manner that it cannot be shut off from the boiler
except by a cock with tee or lever handle, placed on the pipe near the gage.
The handle of the cock shall be parallel to the pipe in which it is located
when the cock is open;
(B) The
scale on the dial of the pressure or altitude gage shall be graduated
approximately to not less than one and a half (1-1/2) nor more than three and a
half (3-1/2) times the pressure at which the safety relief valve is set;
and
(C) Piping or tubing for
pressure or altitude gage connections shall be of nonferrous metal when smaller
than NPS 1;
(2)
Thermometers: each hot-water heating or hot-water supply boiler shall have a
thermometer so located and connected that it shall be easily readable. The
thermometer shall be so located that it shall always indicate the temperature
of the water in the boiler at or near the outlet;
(3) Temperature controls. Each automatically
fired hot-water heating or hot-water supply boiler shall be protected from
over-temperature by two temperature-operated controls. The following shall
apply to automatically fired hot-water heating and hot-water supply boilers:
(A) Each individual hot-water heating or
hot-water supply boiler or each system of commonly connected heating boilers
shall have at least one control that will cut off the fuel supply when the
water temperature reaches an operating limit, which shall be less than the
maximum allowable temperature; and
(B) Each individual automatically fired
hot-water heating or hot-water supply boiler shall have a safety limit control
with manual reset that will cut off the fuel supply to prevent the water
temperature from exceeding the maximum allowable temperature at the boiler
outlet;
(C) Each operating and
safety limit control shall have its own sensing element and operating switch;
and
(D) Alternately, integrated
controls with multiple sensors may be used to meet the requirements of
subparagraphs (A) and (B);
(4) Low-water fuel cutoff. The following
shall apply to automatically fired hot-water heating boilers:
(A) Each automatically fired hot-water
heating boiler shall have an automatic low-water fuel cutoff with manual reset.
The low-water fuel cutoff shall be designed for hot-water service, and it shall
be so located as to automatically cut off the fuel supply when the surface of
the water falls to the level established in subparagraph (B);
(B) As there is no normal waterline to be
maintained in a hot-water boiler, any location of the low-water fuel cutoff
above the lowest safe permissible water level established by the boiler
manufacturer is satisfactory;
(C)
In lieu of the requirements for low-water fuel cutoffs in subparagraph (A),
heating boilers requiring forced circulation to prevent overheating of the
tubes, coils, or vessel, shall have an accepted flow-sensing or
temperature-sensing device to prevent burner operation at a flow rate
inadequate to protect the boiler unit against overheating at all allowable
firing rates. This safety control(s) shall shut down the burner and prevent
restarting until an adequate flow is restored and shall be independent of all
other controls; and
(D) A means
shall be provided for testing the operation of the external low-water fuel
cutoff without resorting to draining the entire system. Such means shall not
render the device inoperable except as follows: if the means temporarily
isolates the device from the boiler during this testing, it shall automatically
return to its normal position. The connection may be so arranged that the
device cannot be shut off from the boiler except by a cock placed at the device
and provided with a tee or lever-handle arranged to be parallel to the pipe in
which it is located when the cock is open;
(c) Potable water heaters. The following
shall apply to potable water heaters:
(1)
Temperature controls. The following shall apply to the temperature controls of
potable water heaters:
(A) Each individual
automatically fired water heater, in addition to the operating control used for
normal water heater operation, shall have a separate high limit temperature
actuated combustion control that will automatically cut off the fuel supply.
The temperature range of the high limit temperature actuated control shall not
allow a setting over 210 degrees Fahrenheit;
(B) Gas-fired water heaters: the high limit
temperature control when actuated shall shut off the fuel supply with a shutoff
means other than the operating control valve. Separate valves may have a common
body;
(C) Electrically heated water
heaters: the high limit temperature control when actuated shall cut off all
power to the operating controls;
(D) Oil-fired water heaters: the high limit
temperature control when actuated shall cut off all current flow to the burner
mechanism; and
(E) Indirect water
heating systems: the high limit temperature control when activated shall cut
off the source of heat;
(2) Pressure or altitude gages. The following
shall apply to pressure or altitude gages:
(A)
Each potable water heater shall have a pressure or altitude gage connected to
it or to its flow connection in such a manner that it cannot be shut off from
the boiler except by a cock with tee or lever handle placed on the pipe near
the gage. The handle of the cock shall be parallel to the pipe in which it is
located when the cock is open;
(B)
The scale on the dial of the pressure or altitude gage shall be graduated
approximately to not less than one and a half (1-1/2) nor more than three (3)
times the maximum allowable working pressure; and
(C) Piping or tubing for pressure or altitude
gage connections shall be of nonferrous metal when smaller than 1-inch pipe
size;
(3) Thermometers:
each installed water heater shall have a thermometer so located and connected
that it shall be easily readable. The thermometer shall be so located that it
shall always indicate the temperature of the water in the water heater at or
near the outlet; and
(4)
Flow-sensing device: potable water heaters requiring forced circulation to
prevent overheating of the tubes, coils, or vessel should have an acceptable
flow-sensing device or temperature-sensing device to prevent burner operation
at a flow rate inadequate to protect the water heater unit against overheating
at all allowable firing rates. This safety controls shall shut down the burner
and prevent restarting until an adequate flow is restored and shall be
independent of all other controls.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.