Haw. Code R. § 6-77-129 - External corrosion control: monitoring
(a) Each
pipeline that is under cathodic protection must be tested at least once each
calendar year, but with intervals not exceeding fifteen months, to determine
whether the cathodic protection meets the requirements of section 6-77-128.
However, if tests at those intervals are impractical for separately protected
short sections of mains or transmission lines; not in excess of 100 feet, or
separately protected service lines, these pipelines may be surveyed on a
sampling basis. At least ten percent of these protected structures, distributed
over the entire system must be surveyed each calendar year, with a different
ten percent checked each subsequent year, so that the entire system is tested
in each ten-year period.
(b) Each
cathodic protection rectifier or other impressed current power source must be
inspected six times each calendar year, but with intervals not exceeding two
and one-half months, to insure that it is operating.
(c) Each reverse current switch, each diode,
and each interference bond whose failure would jeopardize structure protection
must be electrically checked for proper performance six times each calendar
year, but with intervals not exceeding two and one-half months. Each other
interference bond must be checked at least once each calendar year, but with
intervals not exceeding fifteen months.
(d) Each operator shall take prompt remedial
action to correct any deficiencies indicated by the monitoring.
(e) After the initial evaluation required by
sections 6-77-124(b) and (c), and section 6-77-125(b), each operator shall, at
intervals not exceeding three years, reevaluate its unprotected pipelines and
cathodically protect them in accordance with this subchapter in areas in which
active corrosion is found. The operator shall determine the areas of active
corrosion by electrical survey, or where electrical survey is impractical, by
the study of corrosion and leak history records, by leak detection survey, or
by other means.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.