Haw. Code R. § 6-77-56 - Compressor stations: additional safety equipment
(a) Each
compressor station must have adequate fire protection facilities. If fire pumps
are a part of these facilities, their operation may not be affected by the
emergency shutdown system.
(b) Each
compressor station prime mover, other than an electrical induction or
synchronous motor, must have an automatic device to shut down the unit before
the speed of either the prime mover or the driven unit exceeds a maximum safe
speed.
(c) Each compressor unit in
a compressor station must have a shutdown or alarm device that operates in the
event of inadequate cooling or lubrication of the unit.
(d) Each compressor station gas engine that
operates with pressure gas injection must be equipped so that stoppage of the
engine automatically shuts off the fuel and vents the engine distribution
manifold.
(e) Each muffler for a
gas engine in a compressor station must have vent slots or holes in the baffles
of each compartment to prevent gas from being trapped in the muffler.