Ill. Admin. Code tit. 8, § 215.60 - Filling Densities
a) Filling density
is limited to 85% capacity by volume at 60°F.
b) The filling densities for non-refrigerated
containers shall not exceed the following:
1)
Uninsulated aboveground 56%;
2)
Insulated aboveground 57%.
c) US Department of Transportation containers
shall be filled in accordance with
49 CFR
173.315(m)(5).
d) If containers are to be filled according
to liquid level by any gauging method other than a fixed length dip tube gauge,
each container shall have a thermometer well and thermometer so that the
internal liquid temperature can be easily determined and the amount of liquid
and vapor in the container corrected to a 60°F basis.
Notes
Amended at 27 Ill. Reg. 9922, effective July 1, 2003