Ill. Admin. Code tit. 35, § 604.1215 - Booster Pumps
a) Each booster
pumping station must contain no fewer than two pumps with capacities such that
maximum demand can be satisfied with the largest pump out of service.
b) Construction must conform to Section
604.150.
c) Automatic control equipment must be
installed to prevent the pump from causing a vacuum and/or lowering water
pressure in any part of the distribution system to less than 20 psi as measured
at ground surface.
d) Automatic or
remote-control devices must have a range between the start and cutoff pressure
that will prevent excessive cycling.
e) Booster pumps must have the ability to be
bypassed.
f) Pressure for portions
of a distribution system served by a booster pump station, as required by
Section 604.1415, must be provided
during periods when the booster station is not in operation.
g) One of the following must be installed if
adequate pressure will not be available in any part of the system:
1) hydropneumatic storage designed in
accordance with Section
604.1345 on the discharge side
of the booster pump station; or
2)
elevated storage.
h) All
booster pumping stations must be fitted with a flow rate indicator and
totalizer meter.