Ill. Admin. Code tit. 35, § 611.1003 - Source Water Monitoring Requirements: Sampling Locations
a) A supplier required to conduct source
water monitoring under Section
611.1001 must collect samples
for each plant that treats a surface water or groundwater under the direct
influence of surface water source. Where multiple plants draw water from the
same influent, such as the same pipe or intake, the Agency may, by a SEP issued
under Section 611.110, approve one set of
monitoring results to be used to satisfy the requirements of Section
611.1001 for all of the
plants.
b) Source Water Sampling
1) A supplier must collect source water
samples prior to chemical treatment, such as coagulants, oxidants, and
disinfectants, unless the supplier meets the condition of subsection
(b)(2).
2) The Agency may, by a
SEP, approve a supplier to collect a source water sample after chemical
treatment. To grant this approval, the Agency must determine that collecting a
sample prior to chemical treatment is not feasible for the supplier and that
the chemical treatment is unlikely to have a significant adverse effect on the
analysis of the sample.
c) A supplier that recycles filter backwash
water must collect source water samples prior to the point of filter backwash
water addition.
d) Bank Filtration
1) A supplier that receives Cryptosporidium
treatment credit for bank filtration under Section
611.743(b) or
Section 611.955(c)(1),
as applicable, must collect source water samples in the surface water prior to
bank filtration.
2) A supplier that
uses bank filtration as pretreatment to a filtration plant must collect source
water samples from the well (i.e., after bank filtration). The use of bank
filtration during monitoring must be consistent with routine operational
practice. A supplier collecting samples after a bank filtration process may not
receive treatment credit for the bank filtration under Section
611.1017(c).
e) Multiple Sources. A supplier with plants
that use multiple water sources, including multiple surface water sources and
blended surface water and groundwater sources, must collect samples as
specified in subsection (e)(1) or (e)(2). The use of multiple sources during
monitoring must be consistent with routine operational practice.
1) If a sampling tap is available where the
sources are combined prior to treatment, the supplier must collect samples from
the tap.
2) If a sampling tap where
the sources are combined prior to treatment is not available, the supplier must
collect samples at each source near the intake on the same day, and it must
follow either of the following procedures for sample analysis:
A) The supplier may composite samples from
each source into one sample prior to analysis. The volume of sample from each
source must be weighted according to the proportion of the source in the total
plant flow at the time the sample is collected; or
B) The supplier may analyze samples from each
source separately and calculate a weighted average of the analysis results for
each sampling date. The weighted average must be calculated by multiplying the
analysis result for each source by the fraction the source contributed to total
plant flow at the time the sample was collected and then summing these
values.
f)
Additional Requirements. A supplier must submit a description of its sampling
locations to the Agency at the same time as the sampling schedule required
under Section 611.1002. This description must
address the position of the sampling location in relation to the supplier's
water sources and treatment processes, including pretreatment, points of
chemical treatment, and filter backwash recycle. If the Agency does not respond
to a supplier regarding sampling locations, the supplier must sample at the
reported locations.