Ill. Admin. Code tit. 35, § 611.953 - Disinfection Profile
a)
Applicability. A disinfection profile is a graphical representation of a
system's level of Giardia lamblia or virus inactivation measured during the
course of a year. A Subpart B community or non-transient non-community water
system that serves fewer than 10,000 persons must develop a disinfection
profile unless the Agency, by a SEP, determines that a profile is unnecessary.
The Agency may approve the use of a more representative data set for
disinfection profiling than the data set required under subsections (c) through
(g).
b) Determination That a
Disinfection Profile Is Not Necessary. The Agency may only determine that a
disinfection profile is not necessary if the system's TTHM and HAA5 levels are
below 0.064 mg/l and 0.048 mg/l, respectively. To determine these levels, TTHM
and HAA5 samples must have been collected during the month with the warmest
water temperature, and at the point of maximum residence time in the
distribution system. The Agency may, by a SEP, approve the use of a different
data set to determine these levels if it determines that the data set is
representative TTHM and HAA5 data.
c) Development of a Disinfection Profile. A
disinfection profile consists of the following three steps:
1) First, the supplier must collect data for
several parameters from the plant, as discussed in subsection (d), over the
course of 12 months;
2) Second, the
supplier must use this data to calculate weekly log inactivation as discussed
in subsections (e) and (f); and
3)
Third, the supplier must use these weekly log inactivations to develop a
disinfection profile as specified in subsection (g).
d) Data Required for a Disinfection Profile.
A supplier must monitor the following parameters to determine the total log
inactivation using the analytical methods in Section
611.531,
once per week on the same calendar day, over 12 consecutive months:
1) The temperature of the disinfected water
at each residual disinfectant concentration sampling point during peak hourly
flow;
2) If a supplier uses
chlorine, the pH of the disinfected water at each residual disinfectant
concentration sampling point during peak hourly flow;
3) The disinfectant contact times ("T")
during peak hourly flow; and
4) The
residual disinfectant concentrations ("C") of the water before or at the first
customer and prior to each additional point of disinfection during peak hourly
flow.
e) Calculations
Based on the Data Collected. The tables in Appendix B must be used to determine
the appropriate CT99.9 value. The supplier must
calculate the total inactivation ratio as follows, and multiply the value by
3.0 to determine log inactivation of Giardia lamblia:
1) If the supplier uses only one point of
disinfectant application, it must determine either of the following:
A) One inactivation ratio
(CTcalc/CT99.9) before or at the
first customer during peak hourly flow; or
B) Successive
CTcalc/CT99.9 values,
representing sequential inactivation ratios, between the point of disinfectant
application and a point before or at the first customer during peak hourly
flow. Under this alternative, the supplier must calculate the total
inactivation ratio by determining
CTcalc/CT99.9 for each sequence
and then adding the CTcalc/CT99.9
values together to determine
[SIGMA]CTcalc/CT99.9.
2) If the supplier uses more than
one point of disinfectant application before the first customer, it must
determine the CTcalc/CT99.9 value
of each disinfection segment immediately prior to the next point of
disinfectant application, or for the final segment, before or at the first
customer, during peak hourly flow using the procedure specified in subsection
(e)(1)(B).
f) Use of
Chloramines, Ozone, or Chlorine Dioxide as a Primary Disinfectant. If a
supplier uses chloramines, ozone, or chlorine dioxide for primary disinfection,
the supplier must also calculate the logs of inactivation for viruses and
develop an additional disinfection profile for viruses using methods approved
by the Agency.
g) Development and
Maintenance of the Disinfection Profile in Graphic Form. Each log inactivation
serves as a data point in the supplier's disinfection profile. A supplier will
have obtained 52 measurements (one for every week of the year). This will allow
the supplier and the Agency the opportunity to evaluate how microbial
inactivation varied over the course of the year by looking at all 52
measurements (the supplier's disinfection profile). The supplier must retain
the disinfection profile data in graphic form, such as a spreadsheet, which
must be available for review by the Agency as part of a sanitary survey. The
supplier must use this data to calculate a benchmark if the supplier is
considering changes to disinfection practices.
Notes
Amended at 29 Ill. Reg. 2287, effective January 28, 2005
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.